Burkert Type 2101 pneumatically operated 2/2-way globe valve for decentralised automation. Features a stainless steel body, PPS actuator, and high cycle life for steam, gases, and liquids up to 25 bar.

BURKERT Type 2101 pneumatically operated 2/2-way globe valve is specially optimised for decentralised process automation and meets all practical requirements even under difficult operating conditions. Its unique design allows easy integration of automation units in all expansion stages, from electrical/optical position feedback to pneumatic control and integrated fieldbus interface. Maximum service life and tightness are achieved by the proven self-adjusting v-seal packing gland. The highly integrated system of valve and automation unit is characterised by its compact and smooth design, integrated pilot air ducts, protection classes IP65/67, NEMA Type 4X, and high resistance to chemicals.

| Product Properties | Description |
|---|---|
| Design | Globe valve |
| Nominal diameter | DN 10...DN 100, NPS 3/8...NPS 4 |
| Safety setting | Normally closed (control function A), normally open (control function B) |
| Flow direction | Against closing direction (below seat), with closing direction (above seat) |
| Operating pressure | 0 bar(g)...25 bar(g), 40 bar(g) on request. Vacuum variants down to -0.9 bar(g) |
| Medium temperature | -40 °C...+230 °C |
| Ambient temperature | -10 °C...+100 °C |
| Operating medium | Steam, water, neutral gases, alcohols, oils, fuels, hydraulic fluids, salt solutions, organic solvents, oxygen, fuel gases, hydrogen (optional) |
| Degree of protection | IP65/67 |
The globe valve consists of a pneumatically actuated piston actuator and a 2-way body. The actuator is made from polyphenylene sulphide (PPS) or stainless steel (for actuator size 225). Depending on the variant, the valve seat is closed in the direction of or against the medium flow.

Depending on the variant, the valve is closed against the medium flow either with spring force (CFA) or pilot pressure (CFB or CFI). As the medium is present under the swivel plate, the operating pressure contributes to the opening of the valve.

WARNING
Valve leak if there is too little minimum pilot pressure or high operating pressure! Minimum pilot pressure for CFB and CFI that is too low, or failing to meet the permitted operating pressure, can cause a leak in the valve seat. Adhere to minimum pilot pressure and do not exceed the operating pressure.
The valve is closed with the medium flow via spring force (CFA). Because the operating pressure is above the swivel plate, it helps the valve close and also contributes to sealing the valve seat. The valve opens via pilot pressure.

DANGER
Risk of damage due to bursting pipes and bursting equipment when the flow is above the seat. In the case of liquid mediums, water hammer can occur causing pipes and the device to burst. Do not use valves with flow above the seat for liquid mediums.
| Element | Material |
|---|---|
| Actuator cover | PPS |
| Actuator casing | Stainless steel 1.4561 (316Ti) |
| Spindle packing | PTFE V-Rings (filled), with spring compensation |
| Spindle | Stainless steel 1.4401 (316)/1.4404 (316L) |
| Swivel plate | Stainless steel 1.4401 (316)/1.4404 (316L) |
| Seat seal | PTFE, PEEK (option) |
| Valve body | Stainless steel 316L / CF3M |
In addition to the maximum operating pressures, the operating range of Bürkert process valves is limited by the nominal pressure according to the relevant standard.

Explore similar products in our catalog