Skip to content
IP65/67NEMA 4XATEX / IECExFDA / USPPN 25

BURKERT 20113047 Type 2100 Pneumatically Operated 2/2-Way Angle Seat Valve

Burkert Type 2100 pneumatically operated 2/2-way angle seat valve ELEMENT for decentralized automation. Features high flow rates, stainless steel body, and IP65/67 protection.

BURKERT 20113047 Type 2100 Pneumatically Operated 2/2-Way Angle Seat Valve

Burkert Type 2100 angle seat valve is specially optimized for decentralized process automation and fulfills the tough criteria in process environments. Its unique design allows easy integration of automation units in all expansion stages, from electrical/optical position feedback to pneumatic control and integrated fieldbus interfaces. Maximum service life and tightness are achieved by the proven self-adjusting v-seal packing gland. The highly integrated system of valve and automation unit is characterized by its compact and smooth design, integrated pilot air ducts, protection classes IP65/67, NEMA Type 4X, and high resistance to chemicals.

BURKERT 20113047 Burkert Type 2100 pneumatically operated 2/2-way angle seat valve

Key Features

  • High flow rates and long service life.
  • Easy integration of automation units with ELEMENT.
  • Flow-optimized stainless steel valve body with sleeve, clamp, or weld connection.
  • Suitable for steam, water, neutral gases, alcohols, oils, fuels, hydraulic fluids, salt solutions, alkalis, and organic solvents.

Product Overview

BURKERT 20113047 Burkert Type 2100 product overview and component diagram

ComponentDescription
1Transparent cap with position
2Actuator cover
3Actuator housing
4Relief bore
5Valve body
6Flow direction marking
7Port connection
8Body connection
9Actuator connection
10Pilot air port 1
11Pilot air port 2

Materials

BURKERT 20113047 Burkert Type 2100 material specifications and cross-section

No.ElementMaterial
1Ground terminalStainless steel 1.4301/1.4305 (only for ATEX variant)
2Optical position indicatorPolysulfone PSU
3Pilot air portsPush-in connector PP (Standard) / Thread G 1/8" Stainless steel 1.4305 (On request)
4Actuator coverPPS
5Actuator casingStainless steel 1.4561 (316Ti)
6Piston sealFKM
7SpringStainless steel 1.4310
8PipeStainless steel 1.4401 (316)/1.4404 (316L)
9Packing glandPTFE V-Rings (filled), with spring compensation
10SpindleStainless steel 1.4401 (316)/1.4404 (316L)
11Spindle guidePEEK
12Body sealGraphite, PTFE (Option)
13Swivel plateStainless steel 1.4401 (316)/1.4404 (316L)
14Seat sealPTFE, PEEK (Option)
15Valve bodyStainless steel CF3M

INFO

The lubricants for the packing gland and actuator are classified according to NSF H1.

Control Functions and Flow Direction

Flow Direction Below the Seat

Only use flow direction below the seat for liquid media, gases, and vapors. As the medium is present under the swivel plate, the operating pressure contributes to the opening of the valve.

BURKERT 20113047 Burkert Type 2100 flow direction below seat diagram

Flow Direction Above the Seat

Only use flow direction above the seat for gases and vapors, and for valves with control function A (closed by spring force in rest position). As the medium is present above the swivel plate, the operating pressure contributes to the closing of the valve. The operating pressure also supports the sealing of the valve seat.

BURKERT 20113047 Burkert Type 2100 flow direction above seat diagram

DANGER

WARNING! Risk of damage due to bursting pipes and bursting equipment when the flow is above the seat. In the case of liquid mediums, water hammer can occur causing pipes and the device to burst. Do not use valves with flow above the seat for liquid mediums.

Approvals and Conformities

  • Explosion Protection: EPS 18 ATEX 2 008 X II 2G Ex h IIC T4…T2 Gb / II 2D Ex h IIIC T135 °C…T300 °C Db. IECEx EPS 18.0007X.
  • Drinking Water: Suitable for use in drinking water applications. Materials comply with the assessment principles (UBA).
  • Foods and Beverages/Hygiene: FDA (Code of Federal Regulations), USP (United States Pharmacopeial Convention), EC Regulation 1935/2004, China food GB Standards.
  • DNV GL Classification: Accepted for installation on all vessels classed by DNV GL.
  • Oxygen: Optional suitability for gaseous oxygen.
  • Fuel Gases: Complies with Regulation (EU) 2016/426 and DVGW DIN EN 161 / DIN EN 16678.

Operating Limits for Optional Variants

  • High-temperature variant: Suitable for applications with steam, neutral gases, and other heat transfer mediums up to +230 °C.
  • Water variant: For applications with water up to +200 °C, a special configuration of the packing gland increases service life significantly (recommended starting at +85 °C).
  • Drinking water variant: Wetted materials are tested for suitability with drinking water up to +85 °C.
  • Vacuum variant: Without leakage bore, suitable for pressures down to -0.9 bar(g).
  • Low-temperature variant: Suitable for minimum medium temperatures down to -40 °C.
  • Variant for oxygen: Non-metallic wetted materials are tested for suitability with oxygen up to 25 bar(g) and +60 °C.