Armstrong 2000 Series all-stainless steel inverted bucket steam traps feature a 360° universal connector, freeze resistance, and continuous air venting.

Armstrong 2000 Series all-stainless steel inverted bucket steam traps combine savings in three important areas: energy, installation, and replacement. With the 2000 Series’ 360° universal connector, you can install inverted bucket efficiency and long service life in any piping configuration with little or no repiping. You get the reliability of the inverted bucket operating principle, plus all the benefits of an all-stainless steel construction.
The 360° universal connector provides quick, easy in-line replacement along with all the proven advantages of inverted bucket operation. It is available with a standard connector or an optional IS-2 integral strainer connector.
Maximum Allowable Pressure (Vessel Design):
Maximum Operating Pressure:
| Component | Material |
|---|---|
| Body | ASTM A240 Grade 304L Stainless Steel |
| Internals | All stainless steel—304 |
| Valve and Seat | Hardened chrome steel—17-4PH or Titanium |
| Connector Body (Std & IS-2) | Stainless steel—304 |
| Flange | ASTM A105 Zinc plated (or ASTM A-105N) |
| Connector Gasket | Graphite + 304 Stainless Steel |
360° Connector Styles:
Options:
INFO
Allow 2-1/2" clearance for Trap installation and removal for all connectors.

| 2000 Series Traps With Standard Connector | 2010 | 2011 | 2022 |
|---|---|---|---|
| Pipe Connections (in) | 1/2, 3/4 | 1/2, 3/4 | 1/2, 3/4 |
| "A" (Diameter) (in) | 2-11/16 | 2-11/16 | 3-7/8 |
| "B" (Height) (in) | 6 | 6-15/16 | 8-11/16 |
| "C" (Face to Face) (in) | 2-3/8 | 2-3/8 | 2-3/8 |
| Weight lb (kg) | 4-1/4 (1.9) | 4-1/2 (2.0) | 7 (3) |

| Series 2010-2022 With IS-2 Connector | 2010 | 2011 | 2022 |
|---|---|---|---|
| Pipe Connections (in) | 1/2, 3/4, 1 | 1/2, 3/4, 1 | 1/2, 3/4, 1 |
| "A" (Diameter) (in) | 2-11/16 | 2-11/16 | 3-7/8 |
| "B" (Height) (in)* | 6 | 6-15/16 | 8-11/16 |
| "C" (Face to Face) (in) | 3-1/2 (1/2", 3/4"), 4 (1") | 3-1/2 (1/2", 3/4"), 4 (1") | 3-1/2 (1/2", 3/4"), 4 (1") |
| Weight lb (kg) | 4-3/4 (2.2) to 5-1/4 (2.4) | 5 (2.3) to 5-1/2 (2.5) | 7 (3) |
(Add 1/2" to "B" and "D" dimensions when optional probe connection is required.)
TIP
Because the orifice is located at the top, inverted bucket steam traps handle dirt and scale better than other types of traps. However, in applications where extremely dirty conditions exist, care should be exercised in the use of all types of restricted-orifice, reduced-capacity traps.
Model 2010 Capacity
Model 2011 Capacity
Model 2022 Capacity
Steam trap installation is critical from both a performance and maintenance aspect. Installation of the trap is simplified if you follow these guidelines:
WARNING
Use of wrenching surfaces other than specified on the Series 2000 connector can result in damage to the gasket seating area. Use crosshatched area only for wrenching surface.

Maintenance: When the steam trap is suspected of malfunctioning, it can be checked by observing the discharge of the trap. Inverted bucket traps discharge intermittently except under very low load conditions. If the trap is locked shut, check the pressure differential to verify that the maximum differential pressure is not exceeded. If the trap is blowing live steam, close the inlet valve for a few minutes, then gradually open so that the trap can catch its prime. Do not confuse the discharge of flash steam with live steam loss.