The Armstrong ASG Clean Steam Generator uses industrial steam to heat pure water, producing low-pressure clean steam meeting EN285 standards. Features 316 SS construction and automatic operation.

The Armstrong ASG Clean Steam Generator is designed to meet high requirements for steam quality. It uses industrial steam as a heat source to heat pure water (demineralized or deionized water) to generate clean steam, satisfying the steam cleanliness requirements of process systems and equipment in various industries such as food, beverage, pharmaceutical, electronics, fine chemicals, and hospitals. The clean steam quality meets the relevant requirements of EN285 for sterilization.

The clean steam generation tank is designed and manufactured according to Class I pressure vessel standards. All welded parts are made of 316 stainless steel to ensure high corrosion resistance.
Accurate control of the water level in the clean steam generation tank is an important guarantee for the efficient operation of the system and prevents moisture carryover in the steam. It uses a magnetic or capacitive level gauge and an electronic controller to automatically control the liquid level.

Armstrong steam traps ensure that condensate in the heat exchanger is discharged immediately, improving heat exchange efficiency, achieving efficient heating, and reducing water accumulation corrosion and water hammer hazards.

Depending on process requirements, sanitary gasketed, brazed, or fully welded plate heat exchangers, or fully welded plate-and-shell heat exchangers can be used. All parts in contact with pure water and clean steam are made of 316 stainless steel. A pre-heater is optional to fully absorb the residual heat of the condensate discharged from the main heat exchanger to preheat the pure water, achieving high-efficiency heating and energy utilization.

A stainless steel safety valve is installed on the steam generation tank. At the same time, an electronic pressure sensor outputs a high-pressure alarm signal to the controller to prevent excessive pressure from damaging the clean system and equipment.

The automatic blowdown control system uses an Armstrong CC-5 cooler, timer, and solenoid valve to periodically blow down and cool automatically, ensuring steam quality and reducing thermal pollution to the environment.

The pneumatic control valve features rapid response to meet the requirements of quick reaction to industrial steam during sudden load changes, ensuring smooth and accurate control of clean steam pressure. Steam separator/trap stations and filters are also provided to ensure a high-quality industrial steam heating source.
For example, if the industrial steam pressure is 0.6 MPa and you need to generate clean steam with a pressure of 0.2 MPa and a capacity of 700 kg/h, you can use the clean steam generator model "ASG0700-02".

| Parameter | Value |
|---|---|
| Piping Design Pressure | PN16 |
| Max Clean Steam Pressure | 0.3 MPa |
| Min Compressed Air Pressure | 0.4 MPa |
| Available Clean Steam Capacity | 80 to 2000 kg/h |
Note
Using a plate-and-shell heat exchanger or a fully welded plate heat exchanger can provide a clean steam generator with higher pressure and larger capacity. Please consult Armstrong for specific details.


| Model | A | B | C | D | Max Capacity | Industrial Steam | Condensate | Clean Steam | Clean Water | Auto Blowdown | Manual Blowdown | Return |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ASG0500-02 | 1650 | 1200 | 2400 | 1250 | 500 kg/h | DN50 | DN25 | DN65 | DN25 | DN15 | DN25 | DN25 |
| ASG0700-02 | 2800 | 1600 | 2600 | 1650 | 700 kg/h | DN65 | DN40 | DN100 | DN25 | DN15 | DN40 | DN40 |
| ASG1000-02 | 3000 | 2200 | 2750 | 2250 | 1000 kg/h | DN65 | DN40 | DN100 | DN25 | DN15 | DN40 | DN40 |
Ordering Instructions
When ordering, please specify:
All dimensions are approximate. It is recommended to use certified dimensions. Subject to change without notice due to design and material modifications.