Burkert 556289 Type 8012 continuous flowmeter with paddle wheel. Features magnetic or optical measuring, 4-20 mA/transistor outputs, and DN06-DN65 compatibility.

Burkert 556289 Type 8012 flowmeter with paddle wheel is designed for continuous flow measurement and is available as a magnetic or an optical variant. The flowmeter in its magnetic variant is specially designed for use with neutral or mildly aggressive, particle-free liquids. The optical variant is only intended for use with infrared-transmissive liquids. It allows cost-effective integration in pipe systems without any additional pipelines.
Type 8012 consists of a fitting (Type S012) and an electronic module (Type SE12) that are screwed together. Bürkert’s proprietary fitting system ensures simple installation into all pipelines from DN 06 to DN 65. Depending on the particular electronic module variant, Type 8012 is either supplied with one pulse output or with a pulse output and a 4…20 mA current output signal. The pulse output generates a configurable frequency proportional to the volume flow rate, or can be used as a switching output.

| Property | Description |
|---|---|
| Pipe diameter | DN 06...DN 50 (DN 65 on request) |
| Measuring element | Optical, infra-red (or magnetic paddle wheel) |
| Measuring range | Flow rate: 0.5...1000 l/min (0.13...265 gpm) Flow velocity: 0.3...10 m/s |
| Measurement deviation | Teach-in: ± 1% of the measured value Standard K factor: ± 2.5% of the measured value |
| Linearity | ± 0.5% of full scale |
| Repeatability | ± 0.4% of the measured value |
| Operating voltage | 12...36 V DC ± 10%, filtered and regulated |
| Current consumption | <60 mA (at 12 V DC for current variant, without load) |
| Output | Transistor: NPN (default) or PNP, open collector, 700 mA max. Current: 4...20 mA (3 wire), sinking (default) |
| Fluid temperature | PVC: 0...+60 °C PP: 0...+80 °C Stainless steel/Brass: -15...+100 °C (if T°ambient ≤ +45 °C) |
| Fluid pressure | Plastic: max. PN 10 (145 PSI) Metal: max. PN 16 (232 PSI) |
| Viscosity | Max. 300 cSt |
| Degree of protection | IP67 with device wired and M12 female connector mounted and tightened |

| DN | H (mm) |
|---|---|
| 06 | 52.5 |
| 08 | 52.5 |
| 15 | 57.5 |
| 20 | 55.0 |
| 25 | 55.2 |
| 32 | 58.8 |
| 40 | 62.6 |
| 50 | 68.7 |

WARNING
Take the fluid pressure / temperature dependency into account according to the nature of the material of the fitting used. Pressure and temperature ratings must be respected according to the selected fitting material.
Minimum straight distances upstream and downstream of the sensor must be observed. These stabilizing distances depend on the pipe’s design. Increasing these distances or installing a flow conditioner may be necessary to obtain the best accuracy.

Installation Notes
The Type SE12 electronic module is equipped with two LED indicators. When the power is turned on, the green LED lights up and flashes proportionally to the paddle wheel rotation frequency. The lighting up of the red indicator LED indicates a malfunction of the device. When liquid flows into the pipe, the paddle wheel is rotated. The non-wetted permanent magnets inserted in the paddle wheel generate a measuring signal whose frequency is proportional to the flow velocity.

The device Type 8012 is made up of a fitting Type S012 and a transmitter Type SE12 equipped with a paddle wheel sensor. The drawing shows the assembly of a Type S012 fitting with an internal thread process connection and a Type SE12 transmitter.