Burkert 773288 Type 1061 position feedback unit for pneumatic rotary actuators. Features electromechanical feedback, AS-Interface, integrated 3/2-way solenoid valve, and M12 4-pin connection.

Burkert 773288 Type 1061 combines the functions of a position feedback indicator and a solenoid valve in one compact box. It is perfectly suited for pneumatic rotary actuators such as Type 2051 and Type 2052. This specific model features electromechanical feedback with an AS-Interface plug-in card, an integrated 3/2-way solenoid valve, and an M12 4-pin connector. The adjustable mounting console enables use with actuators of different sizes.
| Feature | Specification |
|---|---|
| Housing Material | Aluminium |
| Seal Material | PUR |
| Base / Cover | RAL9005 (powder-coated) / RAL7016 (powder-coated) |
| Dome | Polycarbonate |
| Switching Precision | < 1.5° |
| Bracket | Adjustable Hole gauge: 80/130 mm x 30 mm, Height: 20/30 mm |
| Degree of Protection | IP65 according to EN 60529 |
| Component | Specification |
|---|---|
| Limit Switch | Crouzet 83.161.8 micro switch |
| Contacts | Gold |
| Plug-in Card | ASi, 2 inputs, 1 output |
| Operating Voltage | 26.5...31 V DC |
| System Connection | M12 connector, male, 4-pin |
| Ambient Temperature | -10 °C...55 °C |
| Feature | Specification |
|---|---|
| Bürkert Type | Type 6524 |
| Ways | 3/2 |
| Operating Voltage | 24 V DC |
| Nominal Power | 0.8 W |
| Orifice | 4 mm |
| Supply/Exhaust Air | G 1/4, G 1/8 |
Dimensions in mm, unless otherwise stated.




Risk of Injury
The electric components inside the box carry dangerous voltage. Moreover, there is a risk of bruising by rotating parts. Do not open the housing while operating!

Ex factory, the modules are adjusted as follows:
If readjustment is necessary:

The integrated 3/2-way solenoid valve is already wired on the terminal block, meaning the supply voltage comes via the system connection. The pneumatic connection to the solenoid valve is realized by an external connection block.

Maintenance Recommendation
Long-time outdoor usage can cause gaskets to become brittle. Safe operation can only be guaranteed with leak-proof boxes. Seals should be checked and, if necessary, exchanged at least after five years by qualified personnel.