TLV VAS is a cast iron rapid initial air vent with a free float design. It vents large volumes of initial air at start-up and functions as a vacuum breaker. Max 10 barg, 100°C.

TLV VAS is a float-type mechanical rapid initial air vent designed for water systems. It rapidly vents large volumes of initial air at system start-up. After venting the initial air, the vent can also serve as a vacuum breaker to facilitate drainage by introducing air into the system.

INFO
Once the valve closes after discharging initial air, it will not open again, even if air accumulates inside the product, until the internal pressure drops to near atmospheric pressure. If air is expected to accumulate in the piping during operation, use it together with an automatic air vent.

| No. | Description | Material | DIN | ASTM/AISI |
|---|---|---|---|---|
| 1 | Body | Cast Iron FC250 | 0.6025 | A126 Cl.B |
| 2 | Union | Cast Iron FC250 | 0.6025 | A126 Cl.B |
| 3 | Cap Nut | Cast Iron FC250 | 0.6025 | A126 Cl.B |
| 4 | Valve Seat | Nitrile Rubber NBR | NBR | D2000BF |
| 5 | Valve Seat Holder | Stainless Steel SUS303 | 1.4305 | AISI303 |
| 6 | Float | Stainless Steel SUS316L | 1.4404 | AISI316L |
| 7 | Float Guide | Polypropylene PP | PP | PP |
| 8 | Snap Ring | Stainless Steel SUS304 | 1.4301 | AISI304 |
| 9 | Valve Seat Gasket | Fluorine Resin PTFE | PTFE | PTFE |
| 10 | Union Gasket | Nitrile Rubber NBR | NBR | D2000BF |
| 11 | Nameplate | Stainless Steel SUS304 | 1.4301 | AISI304 |
| Specification | Value |
|---|---|
| Connection | Screwed |
| Size | Inlet: 3/4", Outlet: 1/2" |
| Maximum Operating Pressure (PMO) | 10 barg |
| Minimum Operating Pressure | 0.1 barg |
| Maximum Operating Temperature (TMO) | 100 °C |
| Applicable Fluid | Water |
WARNING
Do not use for toxic, flammable or otherwise hazardous fluids. To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range.

| Size (Inlet x Outlet) | L (mm) | W (mm) | Weight (kg) |
|---|---|---|---|
| 3/4" x 1/2" | 97 | 55 (59.5) | 0.6 |
(W shows face-to-face / diagonal dimensions)



| Problem | Cause | Remedy |
|---|---|---|
| No initial air discharged or discharge is poor (blocked) | Air is not reaching the vent because the liquid in the piping is not being displaced by air | Correct the inlet piping (Inner diameter should be at least 16mm [5/8"]) |
| Valve seat is clogged | Clean valve seat | |
| Inlet or outlet piping is clogged | Clean piping | |
| Liquid leaks when valve is closed | Build-up on the surface of the valve seat or the valve seat is damaged | Clean or replace with new valve seat |
| Float is dirty, coated with a film, or is deformed | Clean or replace with new float | |
| Improper installation | Correct the installation | |
| Valve does not close, and liquid spurts out | Liquid is inside the float | Replace with new float |
| Specific gravity of the liquid is not suitable for this product | Select a product with suitable specifications for the operating conditions |
Explore similar products in our catalog