Yoshitake TAV-2 Air & Gas Vent, Cast Bronze, 1.0 MPa

Yoshitake TAV-2 automatic air and gas vent for city water. Features cast bronze body, 0.05-1.0 MPa working pressure, and prevents backflow during negative pressure.

Yoshitake TAV-2 Air & Gas Vent, Cast Bronze, 1.0 MPa

Yoshitake TAV-2 is an automatic air and gas vent designed for city water applications. It sucks in air promptly when pressure becomes negative in piping or tanks, effectively preventing backflow. The valve intakes and exhausts air automatically as required by the system conditions.

Features

  • Sucks in air promptly when pressure becomes negative in piping or tank, preventing back flow.
  • Intakes / Exhausts air automatically as required.

Specifications

ApplicationCity water
Working pressure0.05-1.0 MPa
Operating pressure of air intake valve-1.0 kPa {-100 mmAq} or less (air intake less than pressure 0)
Maximum temperature0-80°C (no freeze condition)
Material (Body)Cast bronze (NPb-treated)
Material (Float)Synthetic resin
Material (Exhaust packing)Synthetic rubber
Connection portJIS R
Intake and exhaust portJIS Rc 1/4 (φ8 hose joint)

Dimensions and Weights

Nominal sizedH (mm)Intake and exhaust portWeight (kg)
15ARc 1/2107Rc 1/40.8

Yoshitake TAV-2 dimensions

Performance and Piping

Intake/Exhaust Capacity ChartYoshitake TAV-2 capacity chart

Piping ExampleYoshitake TAV-2 piping example

Construction and Parts

Yoshitake TAV-2 parts drawing

No.Name of PartsMaterialQ.TY
1Float BodyPE1
2Exhaust Valve SeatBronze (CAC406C)1
4O RingNBR1
5Exhaust PackingEPDM1
6O RingNBR1
7Exhaust SpringStainless Steel (SUS304)1
8Exhaust ValveBronze (CAC406C)1
9Spring HolderBronze (CAC406C)1
10Lever BordPPO1
11BodyBronze (CAC406)1
12CoverBronze (CAC406)1
15C Type Retaining Rings for HolesStainless Steel (SUS420J2)1
16C Type Retaining Rings for HolesStainless Steel (SUS420J2)1
20O RingNBR1
21O RingNBR1
22SpringStainless Steel (SUS304)1
23Cartridge APPO1
24Cartridge BPPO1
25Cartridge CPPO1
26Float ShaftPE1
40Hose JointBrass (C3604)1

Precautions for Installation

Installation and Safety

  • In anticipation of water leakage from the air inlet or outlet of the product, connect induction piping to the air inlet and outlet, and guide it to the hopper (drain ditch). Keep a clearance of 25 mm or more between the end of the induction piping and the overflow line of the hopper.
  • When hot water is used, its leakage may cause burns or contamination in the area where the product is installed.
  • Drain water when the atmospheric temperature is low, in winter for example, or water is not to be used for a long period of time.

Maintenance and Piping

  • Before connecting the product, carefully wash the inside of piping to remove dirt, scale, etc.
  • When connecting the product to piping, pay attention to the quantity and application position of sealing agent or where to attach seal tape.
  • Do not disassemble the product.
  • Prepare enough space for inspections, maintenance, and repairs. Do not install the product under the roof or inside the wall.
  • Vertically install the product in a position where air tends to accumulate.
  • Use a stop valve (gate valve, ball valve, cock, etc.) for maintenance and inspections in any case. Do not use a globe valve.

Yoshitake Air & Gas Vents

TA, TAV, and VB series air and vacuum valves for automatic venting, rapid air release, and vacuum protection.