41 bar Max Pressure400°C Max TempCarbon Steel

Armstrong AB-600 Bimetallic Steam Trap

The Armstrong AB-600 bimetallic steam trap features a C22.8 carbon steel body, handling up to 41 bar and 400°C. It automatically adjusts to changing conditions.

Armstrong AB-600 Bimetallic Steam Trap

Armstrong AB-600 bimetallic steam trap operates by the effect of temperature rise on the thermostatic bimetallic element. The force generated by the thermal deformation of the bimetallic element in the valve increases with the increase of temperature, which can compensate for the increasing pressure on the valve, so it can automatically adjust with the change of working conditions.

Armstrong AB-600 bimetallic steam trap exterior view

Installation

Possible connections for the AB-600 include screwed, socketweld, or flanged.

Maintenance

WARNING

Equipment under pressure - Operating temperature > 100°C - Make sure trap is cold before handling!

Armstrong AB-600 bimetallic steam trap maintenance drawing and components

Replacement of Bimetallic Elements and Screen

  • Remove the complete trap from the steam line.
  • Unscrew the 4 bolts (10) and lift the cap (1).
  • Unscrew and replace the bimetallic elements (6).
  • Clean or replace the screen (5).
  • Replace gasket (7).
  • Put the cap (1) back on the body (2) and screw the 4 bolts (10).