Armstrong D Series 2500 lb socketweld forged steel Y-type strainers feature a leak-proof, crush-proof screen chamber. Max pressure 6000 psig at 100°F.

Armstrong D Series 2500 lb socketweld forged steel Y-type strainers feature a leak-proof, crush-proof screen chamber. Both ends of the screen chamber are precision machined, ensuring a perfectly round and smooth seating surface as well as a fixed chamber length. Because the screen sits snugly against the machined surfaces, particles larger than the screen openings cannot bypass the ends of the screen.

The bolted screen retainer design ensures easy installation and removal. Straight threads mean that less torque is required to achieve a tight seal with proper gasket engagement, and less torque is needed to remove the retainer. This design significantly reduces the risk of "freezing" compared to hard-to-break tapered pipe threads.

| Connection Size | Body | Screen Retainer | Gasket | Bolting | Standard Screen |
|---|---|---|---|---|---|
| 1/2", 3/4", 1", 1-1/4", 1-1/2", 2" (15 - 50 mm) | ASTM A182 Gr. F22 | ASTM A182 Gr. F22 | 347 SS Spiral Wound Non-asbestos | Studs ASTM A193 Gr. B16 Nuts ASTM A194 Gr. 2H | 304 SS .045" perforated |
Note: Other screen materials and meshes are available upon request.

| Size | Ordering Code | Weight | A | B | C* | Max Pressure (Saturated Steam) | Max Pressure (100°F / 38°C non-shock) | Retainer Type | Connections |
|---|---|---|---|---|---|---|---|---|---|
| 1/2" (15 mm) 3/4" (20 mm) 1" (25 mm) | D1SW | 26 lb (12 kg) | 5-1/8" (130 mm) | 5-5/8" (143 mm) | 1/2" (15 mm) | 2500 psig (172 barg) | 6000 psig (414 barg) | Bolted | ANSI B16.11 Socketweld |
| 1-1/4" (32 mm) 1-1/2" (40 mm) 2" (50 mm) | D1SW | 56 lb (25 kg) | 6-5/8" (168 mm) | 7-3/8" (187 mm) | 1/2" (15 mm) | 2500 psig (172 barg) | 6000 psig (414 barg) | Bolted | ANSI B16.11 Socketweld |
* Socketweld blowdown connections for 1/2" (15 mm) pipe.
To ensure against untimely shutdown of equipment, strainers should be installed ahead of pumps, loading valves, control valves, meters, steam traps, turbines, compressors, solenoid valves, nozzles, pressure regulators, burners, unit heaters, and other sensitive equipment.
Clean all threaded areas of pipe thoroughly before installing the strainer. The strainer can be installed in the horizontal or vertical down position.

CAUTION: WELDING D-SERIES STRAINERS
When installing socket weld strainers, be aware that the D-Series strainer has a non-metal gasket that can be damaged by excessive heat. Try to minimize welding time, and cool the strainer after welding. If pre- and post-weld heating is needed (as is typical for the D-Series F22 material), removing the gasket prior to welding is highly advisable.
After the initial operation of the system, the strainer should be blown down to remove any installation debris caught in the screen. Repeat the blowdown procedure on a regular schedule thereafter. Frequency of blowdown depends on the operating conditions to which the strainer is subjected.
If no blowdown valve is installed, the strainer can be cleaned by removing the screen retainer and screen.
ISOLATE BEFORE MAINTENANCE
Equipment under pressure - Operating temperature > 100°C. Always isolate the strainer from the pressurized system and ensure it is cold before opening to clean or handle.
Internals Maintenance Steps:
The strainer screen should be inspected one to two times per year. Recommended spare parts are one screen and three gaskets per strainer.
When ordering replacement strainer gaskets or retainers, state the type of connection, connection size, and body material of the strainer.
Standard Replacement Gaskets for Forged Steel Strainers (D Series):
| Strainer Size | Forged Steel "D" Part No. |
|---|---|
| 1/2", 3/4", 1" | A6254 |
| 1-1/4", 1-1/2", 2" | A6259 |