Burkert Type 8652 AirLINE valve island optimized for process automation. Features LC display diagnostics, PROFINET S2, ATEX/IECEx Zone 2 approvals, and AirLINE Quick adapter.

Burkert Type 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, though installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that prevent unplanned actuation due to pressure peaks.
| Product properties | |
|---|---|
| Material | |
| Body | PA (polyamide) |
| Seal | NBR and PUR |
| Width per station | 11 mm |
| Manual override | Latching, spring return (optional: lockable) |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Pneumatic intermediate supply | Optional for the variants with 16, 20 and 24 valve slots |
| Performance data | |
| Pressure range | Vac...10 bar |
| External supply air (auxiliary pilot air) | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Flow rate QNn value air with integrated Hot Swap | Flow reduced by approx. 3% |
| Nominal operating mode | Continuous operation (100 % duty cycle) |
| Electrical data | |
| Operating voltage | 24 V DC (Voltage tolerance ±10%) |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Nominal current of each valve | 29 mA (10 mA after power reduction) |
| Digital input | Max. 48 |
| Protection class | III according to DIN EN 61140, VDE 0140 |
| Medium data | |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Compressed air quality | ISO 8573-1: 2010, Class 7.4.4 |
| Environment and installation | |
| Installation position | Any |
| Storage temperature | -20 °C...+60 °C |
| Ambient temperature | -10 °C...+55 °C |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages:

| Product properties | |
|---|---|
| Material | |
| AirLINE Quick Adapter Plate | Stainless steel 1.4301 / Anodised aluminium |
| Pneumatic connection | Stainless steel 1.4401 / Nickel-plated brass |
| Valve functions per station | 8, 16, 24, 32, 40 and 48 |
| Product connections | |
| Pneumatic Supply / Exhaust | Push-in D 10 mm, 3/8" |
| Pneumatic working ports | Push-in D 6 mm, 1/4" |
| Circuit function | Description |
|---|---|
| C (CF C) | 3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed |
| C (CF C) | 2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed |
| D (CF D) | 2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally open |
| H (CF H) | 5/2-way solenoid valve, Servo-controlled, with manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
| L (CF L) | 5/3-way solenoid valve, With manual override. In middle position all ports locked |
| M (CF M) | 5/3-way solenoid valve, Servo-controlled, with manual override. In middle position ports 2 and 4 ventilated |
| N (CF N) | 5/3-way solenoid valve, With manual override. In middle position ports 2 and 4 exhausted |
| Z (CF Z) | 5/2-way solenoid valve, Impulse variant with 2 coils and manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
| Circuit function | Description |
|---|---|
| C (CF C) | 3/2-way solenoid valve, Servo-controlled, Normally closed |
| C (CF C) | 2 × 3/2-way solenoid valve, Servo-controlled, Normally closed |
| H (CF H) | 5/2-way solenoid valve, Servo-controlled. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
| L (CF L) | 5/3-way solenoid valve, Servo-controlled. In middle position all ports locked |

| Variant | A | B | C | m | n |
|---|---|---|---|---|---|
| 4-fold | 66 | - | 4 x M5 | 3 | 1 |
| 8-fold | 35 | 111 | 8 x M5 | 7 | 2 |
| 12-fold | 77 | 154 | 10 x M5 | 11 | 3 |

| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply | 112 | 224 | 10 x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10 x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10 x M5 | 158.3 | 11 | 11 | 6 |
| 16-fold without intermediate supply | 99 | 198 | 10 x M5 | - | 15 | - | 4 |
| 20-fold without intermediate supply | 121 | 242 | 10 x M5 | - | 19 | - | 5 |
| 24-fold without intermediate supply | 143 | 286 | 10 x M5 | - | 23 | - | 6 |
Connect 5-pin spring-loaded terminal according to the pin assignment. Possible cable cross-section: ≤ 1.5 mm².
| Pin | Colour | Assignment |
|---|---|---|
| 1 | Red | 24 V DC |
| 2 | White | CAN_H (büS connection) |
| 3 | Green | SHIELDING |
| 4 | Blue | CAN_L (büS connection) |
| 5 | Black | GND |
The interface plate has a 2-pin spring-loaded terminal to which the pneumatic valves’ power supply is connected.
| Clip | Colour | Assignment |
|---|---|---|
| 1 | Red | AUX 24 V |
| 2 | Black | GND |
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.
| Possible data | 3-wire sensors | 2-wire sensors | Mechanical limit switches |
|---|---|---|---|
| Sensor actuated | X | X | X |
| Sensor not actuated | X | X | X |
| Short circuit | X | - | - |
| Wire break | - | X | - |
Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).
Optional connections for module-based safety shutdown: Terminal 1 = valve unit 1, Terminal 2 = valve unit 2, etc. To use the switch-off function, connect the connection to a potential-free contact (mechanical switch or relay).

When using the device in potentially explosive areas (ATEX Directive 2014/34/EU / NEC 500, 505, 506), special conditions apply.
Danger from voltage
Danger of explosion due to electrostatic charge
In the event of a sudden discharge from electrostatically charged devices or individuals, there is a danger of explosion in the potentially explosive area.
Special conditions for safe use
Explore similar products in our catalog