BURKERT 20016744 Type 8652 AirLINE Valve Island

BURKERT 20016744 Type 8652 AirLINE valve island for process automation. Features 16 valve ports, Industrial Ethernet, LC display diagnostics, and ATEX/IECEx Zone 2 approval.

BURKERT 20016744 Type 8652 AirLINE Valve Island

BURKERT 20016744 Type 8652 AirLINE valve island has been especially developed for process automation requirements. This specific configuration features a 16-bank setup with Industrial Ethernet (PROFINET IO, EtherNet IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) connectivity. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.

The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is also possible. Moreover, key pneumatic functions ensure increased process reliability. For instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks.

BURKERT 20016744 Type 8652 AirLINE valve island

General Technical Data

Product properties
Material
BodyPA (polyamide)
SealNBR and PUR
Width per station11 mm
Manual overrideLatching, spring return (optional: lockable)
Number of valve slotsMax. 24 (16 PCE in this configuration)
Maximum number of valve functionsMax. 48
Performance data
Pressure dataOverpressure to atmospheric pressure
Pressure rangeVac...10 bar (-1 to 10 bar)
External supply air3...10 bar
Flow rate QNn value air310 l/min measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure
Nominal operating modeContinuous operation (100 % duty cycle)
Electrical data
Operating voltage24 V DC
Voltage tolerance±10%
Nominal power of each valve0.7 W (0.175 W after power reduction)
Nominal current of each valve29 mA (10 mA after power reduction)
Medium data
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Compressed air qualityISO 8573-1: 2010, Class 7.4.4
Environment and installation
Ambient temperature-10 °C...+55 °C
Degree of protectionIP20, IP65 in closed control cabinets

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • This makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

BURKERT 20016744 Type 8652 AirLINE Quick Adapter

Circuit Functions

Standard Functions

SymbolDescription
Circuit function C (CF C)
3/2-way solenoid valve
Servo-controlled, with manual override
Normally closed
Circuit function C (CF C)
2 × 3/2-way solenoid valve
Servo-controlled, with manual override
Normally closed
Circuit function D (CF D)
2 × 3/2-way solenoid valve
Servo-controlled, with manual override
Normally open

Approvals and Conformities

ApprovalDescription
Explosion protection
As a category 3 device suitable for zone 2/22.
ATEX: BVS 20 ATEX E 031 U II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc
IECEx: IECEx BVS 20.0024 U Ex ec IIC Gc / Ex tc IIIC Dc
UL Listed for the USA and Canada
UL 61010-1, CAN/CSA-C22.2 No. 61010-1

Product Connections

Power Supply for Communication and Displays

INFO

Connect 5-pin spring-loaded terminal according to the pin assignment. Possible cable cross-section: ≤ 1.5 mm².

Spring-loaded terminal 5-pinColourAssignment
Red24 V DC
WhiteCAN_H (büS connection)
GreenSHIELDING
BlueCAN_L (büS connection)
BlackGND

Fieldbus Interface

Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) or PROFINET S2 – Interface X1 and X2 RJ45PinAssignment
1TX+
2TX-
3RX+
6RX-

Product Installation

WARNING

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 20016744 Type 8652 installation situation in control cabinet

Example Configuration

The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

BURKERT 20016744 Type 8652 example network configuration

Safety Instructions for Ex Zones

Danger from electrical voltage

  • Before working on the device or system, disconnect the power supply. Secure against reactivation.
  • In an existing explosive atmosphere, the connection terminals for 24 V supply, SIA, EVS, and digital inputs may only be plugged in or unplugged when the power is switched off.
  • The use of the Hot Swap function is not permitted in an existing explosive atmosphere.