Skip to content
IP65/IP67NEMA 4XPN 25Class 150

BURKERT 20016839 Type 3361 Electromotive 2-Way Globe Control Valve

BURKERT 20016839 Type 3361 electromotive 2-way globe control valve. Features stainless steel body, G 1/2" connection, 24 V DC supply, and 0-25 bar pressure range.

BURKERT 20016839 Type 3361 Electromotive 2-Way Globe Control Valve

BURKERT 20016839 Type 3361 is an innovative electromotive 2-way globe control valve designed for demanding operating conditions. The electromotive actuator with a ball screw positions the control cone with the highest precision. A unique feature is its high positioning speed of up to 6 mm/s, which reacts almost delay-free to process signals and can be varied according to customer demands. Pressure variations or shocks in the medium are not transferred to the valve position.

Each flow-optimized valve body can be equipped with up to 5 different valve seats for precise adaptation to customer needs. If necessary, the safety position can be approached by an optional energy storage in case of power failure. The actuator and valve are perfectly adapted to each other with a closed design and robust surface, ensuring the hygienic requirements of fast and residue-free cleaning. With a degree of protection of IP65/IP67 and high impact and vibration resistance, the Type 3361 is ideal for harsh environmental conditions.

BURKERT 20016839 Type 3361 electromotive control valve

General Technical Data

Product propertiesDescription
DesignGlobe control valve
Nominal diameterDN 10...DN 100, NPS 3/8...4
Safety setting in case of power failureWith energy storage SAFEPOS energy-pack: open, closed or freely programmable position. Without energy storage: blocked in last position
Flow directionAgainst closing direction (below seat)
Controller variantPositioner or process controller (option)
Operating pressure0...25 bar(g), 40 bar(g) on request. Vacuum variant...-0.9 bar(g) (optional)
Nominal pressurePN 25/PN 40 (DIN EN 1333), Class 150 (DIN EN 1759)
Flow characteristicEqual percentage, linear (on request)
Seat leakageClass III, IV and VI (DIN EN 60534-4)
Theoretical rangeabilityUp to 50:1
Operating voltage24 V DC ± 10 % (maximum residual ripple 10 %)
Protection classIII (DIN EN 61140)
Duty cycle100 %
Operating mediumSteam, neutral gases, water, alcohols, oils, fuels, hydraulic fluids, salt solutions, organic solvents, oxygen (optional), hydrogen (optional), lyes (optional)
Medium temperature-40 °C...+230 °C
Ambient temperature-25 °C...+65 °C (only without additional modules)
Degree of protectionIP65/IP67 (DIN EN 60529), NEMA 4X

Approvals and Conformities

  • Explosion protection (optional): As a category 3 device suitable for zone 2/22. ATEX: II 3G Ex ec IIC T4 Gc, II 3D Ex tc IIIC T135 °C Dc. IECEx: Ex ec IIC T4 Gc, Ex tc IIIC T135 °C Dc.
  • North America (USA/Canada): Actuators UL Listed for the USA and Canada (UL 61010-1, CAN/CSA-C22.2 No. 61010-1).
  • Drinking water (optional): Suitable for use in drinking water applications. Materials comply with UBA assessment principles. Suitable for products with a maximum temperature of +85 °C.
  • Foods and beverages/Hygiene: FDA – Code of Federal Regulations compliant. USP – United States Pharmacopeial Convention compliant. EC Regulation 1935/2004 compliant. China food GB Standards compliant.
  • Others: Suitability for oxygen (optional), Suitability for hydrogen (optional), TA Luft compliant.

Materials

BURKERT 20016839 Type 3361 AG2 actuator materials

AG2 Actuator Materials:

No.ComponentMaterial
1Display housing/blind cover/gateway housingPPS (standard), stainless steel 1.4301 (for ATEX/IECEx)
2Actuator coverPPS
3SealEPDM
4Actuator housingPowder-coated aluminium
6SealEPDM
7Actuator basePPS

Dimensions

Actuator AG2

BURKERT 20016839 Type 3361 AG2 actuator dimensions

Nominal diameter (port connection)NPSHeight H1 (Standard variant)Height H2 (Fieldbus variant)
DN 103/8417 mm489 mm
DN 151/2417 mm489 mm
DN 203/4423 mm495 mm
DN 251446 mm518 mm
DN 321 1/4474 mm546 mm
DN 401 1/2479 mm551 mm
DN 502485 mm557 mm

Performance Specifications

Flow Characteristics

BURKERT 20016839 Type 3361 equal percentage flow curve

  • Equal-percentage flow characteristic according to DIN EN 60534-2-4 (linear characteristic curve on request).
  • Theoretical rangeability: Kvs / Kv0.
  • The globe control valve has different theoretical rangeabilities depending on the seat size.

Operating Limits for Medium Temperature and Operating Pressure

BURKERT 20016839 Type 3361 operating limits for medium temperature and pressure

In addition to the maximum operating pressures, the application range of Bürkert process valves is limited by the nominal pressure in accordance with the relevant standard.

Maintenance and Service

Danger due to uncontrolled process after running the X.TUNE function

If the X.TUNE is run under medium pressure, the controller will be incorrectly adjusted. This will result in an uncontrolled process. Never run the X.TUNE under medium pressure. Secure system against unintentional activation.

Adjusting the position control

Do not run X.TUNE without requirement! The X.TUNE function must be run again only when the actuator has been removed afterwards or the valve body has been changed. When the X.TUNE function is run, the position control is adjusted to the physical stroke of the actuating element used.