BURKERT 20016839 Type 3361 electromotive 2-way globe control valve. Features stainless steel body, G 1/2" connection, 24 V DC supply, and 0-25 bar pressure range.

BURKERT 20016839 Type 3361 is an innovative electromotive 2-way globe control valve designed for demanding operating conditions. The electromotive actuator with a ball screw positions the control cone with the highest precision. A unique feature is its high positioning speed of up to 6 mm/s, which reacts almost delay-free to process signals and can be varied according to customer demands. Pressure variations or shocks in the medium are not transferred to the valve position.
Each flow-optimized valve body can be equipped with up to 5 different valve seats for precise adaptation to customer needs. If necessary, the safety position can be approached by an optional energy storage in case of power failure. The actuator and valve are perfectly adapted to each other with a closed design and robust surface, ensuring the hygienic requirements of fast and residue-free cleaning. With a degree of protection of IP65/IP67 and high impact and vibration resistance, the Type 3361 is ideal for harsh environmental conditions.

| Product properties | Description |
|---|---|
| Design | Globe control valve |
| Nominal diameter | DN 10...DN 100, NPS 3/8...4 |
| Safety setting in case of power failure | With energy storage SAFEPOS energy-pack: open, closed or freely programmable position. Without energy storage: blocked in last position |
| Flow direction | Against closing direction (below seat) |
| Controller variant | Positioner or process controller (option) |
| Operating pressure | 0...25 bar(g), 40 bar(g) on request. Vacuum variant...-0.9 bar(g) (optional) |
| Nominal pressure | PN 25/PN 40 (DIN EN 1333), Class 150 (DIN EN 1759) |
| Flow characteristic | Equal percentage, linear (on request) |
| Seat leakage | Class III, IV and VI (DIN EN 60534-4) |
| Theoretical rangeability | Up to 50:1 |
| Operating voltage | 24 V DC ± 10 % (maximum residual ripple 10 %) |
| Protection class | III (DIN EN 61140) |
| Duty cycle | 100 % |
| Operating medium | Steam, neutral gases, water, alcohols, oils, fuels, hydraulic fluids, salt solutions, organic solvents, oxygen (optional), hydrogen (optional), lyes (optional) |
| Medium temperature | -40 °C...+230 °C |
| Ambient temperature | -25 °C...+65 °C (only without additional modules) |
| Degree of protection | IP65/IP67 (DIN EN 60529), NEMA 4X |

AG2 Actuator Materials:
| No. | Component | Material |
|---|---|---|
| 1 | Display housing/blind cover/gateway housing | PPS (standard), stainless steel 1.4301 (for ATEX/IECEx) |
| 2 | Actuator cover | PPS |
| 3 | Seal | EPDM |
| 4 | Actuator housing | Powder-coated aluminium |
| 6 | Seal | EPDM |
| 7 | Actuator base | PPS |
Actuator AG2

| Nominal diameter (port connection) | NPS | Height H1 (Standard variant) | Height H2 (Fieldbus variant) |
|---|---|---|---|
| DN 10 | 3/8 | 417 mm | 489 mm |
| DN 15 | 1/2 | 417 mm | 489 mm |
| DN 20 | 3/4 | 423 mm | 495 mm |
| DN 25 | 1 | 446 mm | 518 mm |
| DN 32 | 1 1/4 | 474 mm | 546 mm |
| DN 40 | 1 1/2 | 479 mm | 551 mm |
| DN 50 | 2 | 485 mm | 557 mm |
Flow Characteristics

Operating Limits for Medium Temperature and Operating Pressure

In addition to the maximum operating pressures, the application range of Bürkert process valves is limited by the nominal pressure in accordance with the relevant standard.
Danger due to uncontrolled process after running the X.TUNE function
If the X.TUNE is run under medium pressure, the controller will be incorrectly adjusted. This will result in an uncontrolled process. Never run the X.TUNE under medium pressure. Secure system against unintentional activation.
Adjusting the position control
Do not run X.TUNE without requirement! The X.TUNE function must be run again only when the actuator has been removed afterwards or the valve body has been changed. When the X.TUNE function is run, the position control is adjusted to the physical stroke of the actuating element used.