BURKERT 20016875 (Type 8652) AirLINE valve island for process automation. Features 20 valve ports, PROFIBUS DPV1, -1 to 10 bar pressure, and ATEX/IECEx Zone 2 approvals.

BURKERT 20016875 (Type 8652) AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller. This, therefore, enables a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is, of course, also possible. Moreover, key pneumatic functions ensure increased process reliability. For instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks.
Key Features

| Product properties | Description |
|---|---|
| Material | |
| Body | PA (polyamide) |
| Seal | NBR and PUR |
| Width per station | 11 mm |
| Manual override | Latching, spring return (optional: lockable) |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Performance data | |
| Pressure range | Vac...10 bar |
| External supply air (auxiliary pilot air) | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Nominal operating mode | Continuous operation (100 % duty cycle) |
| Electrical data | |
| Operating voltage | 24 V DC (Voltage tolerance ±10%) |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Nominal current of each valve | 29 mA (10 mA after power reduction) |
| Protection class | III according to DIN EN 61140, VDE 0140 |
| Medium data | |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Compressed air quality | ISO 8573-1: 2010, Class 7.4.4 |
| Environment and installation | |
| Ambient temperature | -10 °C...+55 °C |
| Degree of protection | IP20, IP65 in closed control cabinets |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages:
| Product properties | Description |
|---|---|
| AirLINE Quick Adapter Plate | Stainless steel 1.4301 / Anodised aluminium |
| Pneumatic connection | Stainless steel 1.4401 / Nickel-plated brass |
| Valve functions per station | 8, 16, 24, 32, 40 and 48 |
| Pneumatic Supply / Exhaust | Push-in D 10 mm, 3/8" |
| Pneumatic working ports | Push-in D 6 mm, 1/4" |
| Installation position | Control cabinet wall / Control cabinet floor |

| Circuit function | Description |
|---|---|
| C (CF C) | 3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed |
| C (CF C) | 2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed |
| D (CF D) | 2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally open |
| H (CF H) | 5/2-way solenoid valve, Servo-controlled, with manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
| L (CF L) | 5/3-way solenoid valve, With manual override, In middle position all ports locked |
| M (CF M) | 5/3-way solenoid valve, Servo-controlled, with manual override, In middle position ports 2 and 4 ventilated |
| N (CF N) | 5/3-way solenoid valve, With manual override, In middle position ports 2 and 4 exhausted |
| Z (CF Z) | 5/2-way solenoid valve, Impulse variant with 2 coils and manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
Note
Dimensions in mm, unless otherwise stated.

| Variant | A | B | C | m | n |
|---|---|---|---|---|---|
| 4-fold | 66 | - | 4 x M5 | 3 | 1 |
| 8-fold | 35 | 111 | 8 x M5 | 7 | 2 |
| 12-fold | 77 | 154 | 10 x M5 | 11 | 3 |
Power supply for communication and displays Connect 5-pin spring-loaded terminal according to the pin assignment. Possible cable cross-section: ≤ 1.5 mm².
| Pin | Colour | Assignment |
|---|---|---|
| 1 | Red | 24 V DC |
| 2 | White | CAN_H (büS connection) |
| 3 | Green | SHIELDING |
| 4 | Blue | CAN_L (büS connection) |
| 5 | Black | GND |
Power supply for pneumatic valves The interface plate has a 2-pin spring-loaded terminal to which the pneumatic valves’ power supply is connected.
| Clip | Colour | Assignment |
|---|---|---|
| 1 | Red | AUX 24 V |
| 2 | Black | GND |
Installation situation of the valve terminal inside the control cabinet To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.


Example configuration The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

Bürkert Communicator software The Bürkert Communicator is the most important software component of the EDIP (Efficient Device Integration Platform). Various features of this universal tool simplify the configuration and parametrisation of devices equipped with a digital CANopen-based interface. With this tool the user has a complete overview of cyclic process values as well as acyclic diagnostic data.
Explore similar products in our catalog