Skip to content
Type 3280Article 20022079DN4G 3/80-15 barPWM Control24 V DCIP54

BURKERT 20022079 (Type 3280) Electromotive 2-Way Globe Control Valve, G 3/8, DN4

BURKERT 20022079 (Type 3280) is an electromotive 2-way globe control valve with G 3/8 connections, DN4 orifice, 24 V DC supply, 0-15 bar pressure range, EPDM seal, and PWM position control.

BURKERT 20022079 (Type 3280) Electromotive 2-Way Globe Control Valve, G 3/8, DN4

BURKERT 20022079 (Type 3280) is a direct-acting electromotive 2-way globe control valve designed for continuous metering and flow regulation of clean neutral liquids and gases. This specific configuration features a G 3/8 female threaded brass body, an orifice seat diameter of 4 mm (DN4), an EPDM seat seal, and an operating pressure range of 0 to 15 bar(g). The valve is driven by an internal linear stepper motor and managed by integrated control electronics, accepting a 24 V PWM control input (800 Hz) with an active digital feedback output indicating the closed position.

Position control operates with a position dead band of ±0.5%, matching a setting range of 1:100, and achieves full stroke actuation in approximately 2.5 seconds at standard speed. Once the target position is reached, the stepper motor powers off, requiring under 1 W in holding mode while mechanically maintaining its position via a threaded spindle drive. Fluid flows under the seat, closing against the media flow to ensure defined shut-off characteristics.

Energy Consumption in Holding Position

The linear actuator mechanism mechanically locks the spindle in place once the requested stroke position is reached. The internal stepper motor consumes no energy to maintain position, reducing standby electrical demand to under 1 W compared to continuous-draw proportional solenoids.

Technical Specifications ​

Specification ParameterValue
Article Number20022079
Valve TypeType 3280
Control FunctionContinuous position control (proportional control valve)
Fluidic Ports2 ports (2-way), G 3/8 internal thread (EN ISO 228-1)
Orifice Size (Seat Diameter)4 mm (5/32", DN4)
Flow Coefficient ($K_{vs}$, Water)0.5 m³/h
Operating Pressure Range0 to 15 bar(g)
Operating Voltage24 V DC ±10% (max. residual ripple 10%)
Power Consumption< 1 W holding; max. 8 W operating
Input Signal (Set-Point)PWM (800 Hz, 24 V, min. 10 V, max. 30 V)
Output Signal (Actual State)Digital output: PNP, max. 100 mA (active when valve closed)
Stroke Actuation Time (0 to 100%)Approx. 2.5 s (normal mode), 5.0 s (slow mode)
Position Control Dead Band±0.5% (setting range 1:100)
Duty CycleUp to 100% (subject to ambient temperature derating)
Medium Temperature0 °C to +70 °C
Permissible Ambient Temperature-10 °C to +60 °C
Max. Viscosity600 mm²/s (cSt)
Degree of ProtectionIP54 (with properly attached electrical connection)
WeightApprox. 0.7 kg
Flow DirectionBelow seat (against closing direction)

Materials and Construction ​

BURKERT 20022079 BURKERT Type 3280 electromotive globe valve material cross-section

The electromotive actuator is completely separated from the fluid path. The actuator housing is fabricated from polyphenylene sulphide (PPS GF40) at the base and polycarbonate (PC GF10) at the upper cover. Internal fluid-contacting mechanical parts, including the spindle, seat, and guiding elements, are manufactured from stainless steel and PTFE.

ItemComponentMaterial
1Housing coverPolycarbonate (PC GF10)
2Housing basePolyphenylenesulfide (PPS GF40)
3Spindle sealEPDM (Ethylene-propylene-diene rubber)
4SpindleStainless steel 1.4305
5Upper valve bodyBrass
6Piston with parabolic control element and guiding shaftPTFE / Stainless steel 1.4305
7Elastomer seat sealEPDM
8O-ringEPDM
9Valve seatStainless steel 1.4301 / 1.4305
10Valve bodyBrass

Dimensions and Installation ​

BURKERT 20022079 BURKERT Type 3280 threaded variant dimensional drawing

Dimensions for threaded body variants of Type 3280 are listed in millimeters below. For article 20022079, the relevant connection is $G^{3/8}$:

ABCDEFGH
——12 mm$G^{3/8}$97.4 mm137.2 mm12 mm27.5 mm
6.0 mm10.3 mm—$NPT^{3/8}$97.4 mm137.2 mm12 mm27.5 mm
——12 mm$G^{1/4}$96.4 mm134.2 mm10 mm27.5 mm
5.8 mm10.0 mm—$NPT^{1/4}$96.4 mm134.2 mm10 mm27.5 mm
——14 mm$G^{1/2}$97.4 mm139.2 mm14 mm29.5 mm
8.2 mm13.7 mm—$NPT^{1/2}$97.4 mm139.2 mm14 mm29.5 mm

BURKERT 20022079 BURKERT Type 3280 flow direction below valve seat

Piping Cleanliness and Strainer Requirement

Particulate contamination damages the elastomer seat seal and disrupts precise metering. Install a dirt filter or strainer with a mesh size $\le 0.3\text{ mm}$ directly upstream of the valve inlet. When threading the valve into the pipeline, hold the brass valve body using an open-end wrench; never use the plastic actuator housing as a lever arm.

The valve may be installed in any physical position, though an upright vertical orientation with the actuator positioned upwards is preferred. Medium flow must follow the arrow cast onto the body, directing fluid from under the valve seat.

Electrical Connections ​

Article 20022079 is equipped with an 8-pin A-coded M12 circular connector for power and control. Inputs and outputs share a common non-isolated reference with the power supply.

PinWire Color (Cable 919061)ConfigurationSignal Description / External Circuit
1WhiteSupply +24 V DC ±10%, max. residual ripple 10%
2BrownSupply GND24 V DC GND
3GreenDo not connectElectrically insulate wire on connection cable
4YellowDo not connectElectrically insulate wire on connection cable
5GreyDo not connectElectrically insulate wire on connection cable
6RoseSet-point value input +PWM signal (800 Hz, 24 V, min. 10 V, max. 30 V), non-isolated
7BlueDigital outputPNP, max. 100 mA, active (10 to 30 V) when valve closed
8RedSignal GNDSignal reference ground
BodyShieldShieldingConnected to valve body; ground externally for EMC compliance

DIP Switch Configuration and Status Display ​

BURKERT 20022079 BURKERT Type 3280 DIP switch location on actuator PCB

Setting switches are located beneath the actuator cover. Before loosening the four housing screws, disconnect the power supply. Tighten housing cover screws to 2 Nm upon reassembly.

SwitchPositionStandard PWM Version Function
1OFFNormal operating direction: PWM duty cycle 0–100% corresponds to valve position 0–100% (increasing)
1ONInverted operating direction: PWM duty cycle 0–100% corresponds to valve position 100–0% (decreasing)
2OFF / ONNo function for PWM device variant
3OFFActuating speed: Normal mode (full stroke in approx. 2.5 s)
3ONActuating speed: Slow mode (full stroke in approx. 5.0 s)
4OFFLow power function: Off (nominal motor torque)
4ONLow power function: On (reduced motor current/heat; limited to $\Delta p \le 1\text{ bar}$ and $p_{med} \le 3\text{ bar}$)

Low Power Mode Pressure Limits

Activating DIP switch 4 reduces motor drive current and internal heat generation. However, motor torque decreases accordingly. This mode must only be used with differential pressures $\le 1\text{ bar}$ and total medium pressures $\le 3\text{ bar}$. Exceeding these limits will cause the valve to stall or fail to reach position.

LED Status Indication ​

LED ColorStateOperating Meaning
WhiteContinuously onNormal operation
YellowContinuously onValve completely open (100%)
GreenContinuously onValve closed (0%)
YellowFlashing (alternating)Out of specification: Ambient or process conditions outside permissible range
RedFlashing (alternating)Fault / error condition detected
OffUnlitNo power supply connected

Performance and Derating ​

BURKERT 20022079 BURKERT Type 3280 duty cycle derating diagram for seat sizes DN1 to DN6

The permissible duty cycle of the stepper motor depends directly on ambient temperature. The motor runs only while adjusting position; frequent set-point adjustments elevate the motor duty cycle. Operating the actuator outside the recommended derating limits reduces service life.

High-Pressure Range Overview ​

Seat SizeConnection$K_{vs}$ Value (Water)Liquid Pressure RangeGas Pressure Range
DN1G 1/40.030 m³/h0 to 15 bar(g)0 to 22 bar(g)
DN1.5G 1/40.065 m³/h0 to 15 bar(g)0 to 22 bar(g)
DN2G 3/80.130 m³/h0 to 15 bar(g)0 to 22 bar(g)
DN3G 3/80.300 m³/h0 to 15 bar(g)0 to 22 bar(g)
DN4 (20022079)G 3/80.500 m³/h0 to 15 bar(g) (EPDM)0 to 15 bar(g) (EPDM)
DN5G 3/80.750 m³/h0 to 15 bar(g) (EPDM)0 to 15 bar(g) (EPDM)
DN6G 3/80.900 m³/h0 to 15 bar(g)0 to 16 bar(g)
DN8G 1/21.500 m³/h0 to 12 bar(g)0 to 12 bar(g)
DN10G 1/21.900 m³/h0 to 10 bar(g)0 to 10 bar(g)

Flow Dimensioning Recommendation

To preserve an approximately linear operating characteristic in the actual system, size the valve seat such that the pressure drop across the fully opened valve constitutes at least 25% of the total system pressure drop: $\Delta p_{valve} > 25%\text{ of }\Delta p_{total}$.