BURKERT 20024510 8652 AirLINE Valve Island for Process Automation

Burkert Type 8652 AirLINE valve island optimized for process automation. Features LC display diagnostics, PROFINET S2, ATEX/IECEx Zone 2 approvals, and AirLINE Quick cabinet mounting.

BURKERT 20024510 8652 AirLINE Valve Island for Process Automation

Burkert Type 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.

The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability; for instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks.

BURKERT 20024510 Burkert 8652 AirLINE valve island main product overview

General Technical Data

Product propertiesDescription
Body MaterialPA (polyamide)
Seal MaterialNBR and PUR
Width per station11 mm
Manual overrideLatching, spring return (optional: lockable)
Number of valve slotsMax. 24
Maximum number of valve functionsMax. 48
Pneumatic intermediate supplyOptional for the variants with 16, 20 and 24 valve slots
Pressure rangeVac...10 bar
External supply air3...10 bar
Flow rate QNn value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Flow rate with Hot SwapFlow reduced by approx. 3%
Operating voltage24 V DC (±10% tolerance)
Nominal power of each valve0.7 W (0.175 W after power reduction)
Nominal current of each valve29 mA (10 mA after power reduction)
Digital inputMax. 48
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Degree of protectionIP20, IP65 in closed control cabinets
Ambient temperature-10 °C...+55 °C

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • Makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet
Product propertiesDescription
AirLINE Quick Adapter PlateStainless steel 1.4301, Anodised aluminium
Pneumatic connectionStainless steel 1.4401, Nickel-plated brass
Valve functions per station8, 16, 24, 32, 40 and 48
Pneumatic Supply / ExhaustPush-in D 10 mm, 3/8"
Pneumatic working portsPush-in D 6 mm, 1/4"

BURKERT 20024510 Burkert 8652 AirLINE Quick Adapter in stainless steel or anodised aluminium

Circuit Functions

Standard Functions

Circuit functionDescription
C (CF C)3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed
C (CF C)2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed
D (CF D)2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally open
H (CF H)5/2-way solenoid valve, Servo-controlled, with manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure.
L (CF L)5/3-way solenoid valve, With manual override, In middle position all ports locked
M (CF M)5/3-way solenoid valve, Servo-controlled, with manual override, In middle position ports 2 and 4 ventilated
N (CF N)5/3-way solenoid valve, With manual override, In middle position ports 2 and 4 exhausted
Z (CF Z)5/2-way solenoid valve, Impulse variant with 2 coils and manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure.
Circuit functionDescription
C (CF C)3/2-way solenoid valve, Servo-controlled, Normally closed
C (CF C)2 × 3/2-way solenoid valve, Servo-controlled, Normally closed
H (CF H)5/2-way solenoid valve, Servo-controlled. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure.
L (CF L)5/3-way solenoid valve, Servo-controlled, In middle position all ports locked

Approvals and Conformities

ApprovalDescription
Explosion protectionOptional: As a category 3 device suitable for zone 2/22. ATEX: BVS 20 ATEX E 031 U (II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc). IECEx: IECEx BVS 20.0024 U (Ex ec IIC Gc / Ex tc IIIC Dc).
North America (USA/Canada)Optional: UL Listed for the USA and Canada (UL 61010-1). UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Div 2).
CCCOptional: China Compulsory Certification (CCC). Products with Ex approval are suitable for import and use for hazardous applications in China.

Dimensions

Variant 4-, 8- and 12-fold

BURKERT 20024510 Burkert 8652 AirLINE dimensions for 4, 8, and 12-fold variants

VariantA (mm)B (mm)Cmn
4-fold66-4 x M531
8-fold351118 x M572
12-fold7715410 x M5113

Variant 16-, 20- and 24-fold

BURKERT 20024510 Burkert 8652 AirLINE dimensions for 16, 20, and 24-fold variants

VariantA (mm)B (mm)CD (mm)mm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116
16-fold without intermediate supply9919810 x M5-15-4
20-fold without intermediate supply12124210 x M5-19-5
24-fold without intermediate supply14328610 x M5-23-6

Product Installation

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 20024510 Burkert 8652 AirLINE installation situation inside the control cabinet

Product Connections

Power Supply

  • Communication and displays: 5-pin spring-loaded terminal (24 V DC, CAN_H, SHIELDING, CAN_L, GND).
  • Pneumatic valves: 2-pin spring-loaded terminal (AUX 24 V, GND).

Fieldbus Interface

  • CANopen/büS: 5-pin spring terminal. Requires 2 terminating resistors (approx. 60 Ω between CAN_H and CAN_L).
  • Industrial Ethernet / PROFINET S2: Interface X1 and X2 RJ45.
  • PROFIBUS DPV1: D-Sub socket 9-pin.

Product Design and Assembly

Electronic Module with Digital Inputs (Optional)

The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.

BURKERT 20024510 Burkert 8652 AirLINE electronic module with digital inputs

Possible data3-wire sensors2-wire sensorsMechanical limit switches
Sensor actuatedXXX
Sensor not actuatedXXX
Short circuitX--
Wire break-X-

Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).

Module-Based Safety Shutdown (Optional)

Connections for module-based safety shutdown: Terminal 1 = valve unit 1, Terminal 2 = valve unit 2, etc. Connect the connection to a potential-free contact (mechanical switch or relay). Required switching capacity of the contact is 1.5 A / 24 V DC.

Example Configuration

The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

BURKERT 20024510 Burkert 8652 AirLINE example network configuration with Industrial Ethernet

Explosion Protection (EX) Supplementary Notes

When using the device in explosion hazardous areas, special conditions apply.

Voltage and Electrostatic Hazards

  • Voltage: Disconnect power before working on the device or system. Prevent reconnection.
  • In explosive atmospheres, connection terminals for 24 V power supply, SIA, EVS, and digital inputs must only be plugged in or unplugged when de-energized.
  • Electrostatic charge: Sudden discharge of electrostatically charged devices or persons can cause an explosion. Take appropriate measures to ensure no electrostatic charge occurs. Clean surfaces only by wiping gently with a damp or anti-static cloth.

Special Conditions for Hot Swap

  • The use of the Hot Swap function is strictly prohibited in explosive atmospheres.
  • If it can be proven and ensured by means of suitable testing equipment that no explosive atmosphere is present for a certain period of time, it is permissible to remove/insert valves using Hot Swap during this period.
  • The Hot Swap function must only be used by appropriately trained personnel.

Enclosure Requirements

  • For explosion protection type "ec", install the device in an enclosure meeting EN/IEC 60079-0 and EN/IEC 60079-7 requirements with a protection degree of at least IP54.
  • For explosion protection type "tc" (dust), install in an enclosure meeting EN/IEC 60079-31 requirements with a protection degree of at least IP6X.