DN 40 (1 1/2" NPT)AG2 1300 N24 V DC0 - 10 barKv 24 m³/hPTFE Seal Class VISAFEPOS Energy-PackIP65/IP67EC 1935/2004

BURKERT 20026082 Type 3361 Electromotive 2-Way Globe Control Valve, 1 1/2" NPT, 24 V DC

BURKERT 20026082 (Type 3361) is an electromotive 2-way globe control valve with 1 1/2" NPT ports, 24 V DC AG2 actuator, 24 m³/h Kv, PTFE seat seal, SAFEPOS fail-safe pack, and integrated display.

BURKERT 20026082 Type 3361 Electromotive 2-Way Globe Control Valve, 1 1/2" NPT, 24 V DC

BURKERT 20026082 (Type 3361) is an electromotive 2-way globe control valve engineered for continuous modulating control under demanding process conditions. Driven by an AG2 electromotive linear actuator with a precision ball screw, the unit delivers a nominal actuating force of 1,300 N at a linear travel speed of 6 mm/s. The valve features a 1 1/2" NPT female-threaded stainless steel CF3M body, a 40 mm seat diameter, an equal-percentage control cone with a 50:1 theoretical rangeability, and a full-open water flow coefficient Kv of 24 m³/h (Cv 27.7 gal/min). The sealing system employs a soft PTFE seat seal achieving DIN EN 60534-4 Leakage Class VI shut-off up to 10 bar(g) differential pressure with flow directed below the seat.

Configured under article number 20026082, this unit includes an integrated digital display with operating pushbuttons, an internal SAFEPOS energy-pack storage module that drives the valve to a predefined closed safety position upon power disruption, and an analogue I/O interface complemented by a service-büS digital port for parameterization via Bürkert Communicator software. With IP65/IP67 ingress protection, NEMA 4X housing durability, and wetted materials compliant with EC Regulation 1935/2004, Type 3361 fulfills the hygiene and wash-down criteria required across food processing, pharmaceuticals, water treatment, and industrial utilities.

Technical Specifications ​

ParameterValue
Product TypeElectromotive 2-way globe control valve
Article Number (MPN)20026082
Type Family3361
Actuator SizeAG2 (Actuator size 2)
Electromotive Driving Force1,300 N nominal force
Port Connection1 1/2" NPT internal thread (ASME B1.20.1)
Nominal Diameter (Pipe)DN 40 (NPS 1 1/2)
Seat Orifice Diameter40 mm
Flow Coefficient Kv24 m³/h (water measurement according to DIN EN 60534-2-4)
Flow Coefficient Cv27.7 gal/min
Flow CharacteristicEqual percentage (theoretical rangeability 50:1)
Operating Pressure Range0 to 10 bar(g)
Nominal Pressure ClassPN 25 (DIN EN 1333), Class 150 (DIN EN 1759)
Flow DirectionBelow seat (fluid port 2 -> port 1)
Seat Leakage ClassClass VI (DIN EN 60534-4)
Linear Travel Speed6 mm/s (AG2 1,300 N driving force)
Typical Closing Time4.4 s (4,400 ms)
Position Control Dead Band±0.1%
Duty Cycle100% continuous
Supply Voltage24 V DC ±10% (residual ripple max. 10%)
Operating CurrentMax. 3 A at max. load (including 1 A SAFEPOS charging); +2 A at min. operating temp
Standby Power Consumption2 to 5 W
Electrical Protection ClassClass III (DIN EN 61140)
Ingress ProtectionIP65 / IP67 (DIN EN 60529), NEMA 4X
Medium Temperature Range-10 °C to +130 °C (recommended for PTFE seat seals)
Ambient Temperature Range-25 °C to +65 °C (subject to module derating)
Maximum Medium ViscosityUp to 600 mm²/s
WeightApprox. 5.5 kg (actuator AG2 only; total weight depends on valve body)
Conformity & CertificationEC Regulation 1935/2004 (food contact), Ecolab detergent tested F&E/P3-E No. 40-1

Materials of Construction ​

BURKERT 20026082 Type 3361 AG2 actuator components and material breakdown

Actuator Materials (AG2) ​

ItemComponentMaterial
1Display housing / blind coverPPS (polyphenylene sulphide) standard
2Actuator coverPPS
3SealEPDM
4Actuator housingPowder-coated aluminium
6SealEPDM
7Actuator basePPS

BURKERT 20026082 Type 3361 valve body, packing gland, and seat materials

Valve Body and Wetted Components ​

ItemComponentMaterial
1SpindleStainless steel 1.4401 (316) / 1.4404 (316L)
2Spindle sealPTFE V-rings (filled) with spring compensation
3Spindle guideStainless steel 1.4404 (316L)
4Packing gland tubeStainless steel 1.4401 (316)
5Valve body sealGraphite or PTFE
6Seat sealPTFE seal washer (Leakage Class VI)
7Control coneStainless steel 1.4571
8Valve seatStainless steel 1.4571
9Valve seat O-ringEPDM or PTFE
10Valve bodyStainless steel CF3M

Dimensions and Mounting ​

BURKERT 20026082 Type 3361 AG2 linear actuator dimensional drawing

Actuator Height (AG2) ​

Nominal Diameter DNNPSH1 Standard Variant (Display / Blind Cover) [mm]H2 Fieldbus Variant (with Gateway) [mm]
103/8417489
151/2417489
203/4423495
251446518
321 1/4474546
401 1/2479551
502485557

Note: Dimensions are given without tight-closing function; the actuator rises approximately 2 mm in the fully closed position.

BURKERT 20026082 Type 3361 threaded body dimensional drawing

Threaded Body Dimensions (ASME B1.20.1 NPT) ​

DNNPSThread DNPT Engagement Length E [mm]Lay Length LM [mm]Width Across Flats AF [mm]
103/8NPT 3/810.36527
151/2NPT 1/213.76527
203/4NPT 3/414.07534
251NPT 116.89041
321 1/4NPT 1 1/417.311050
401 1/2NPT 1 1/217.312055
502NPT 217.615070
652 1/2NPT 2 1/223.718585
803NPT 330.5205100
1004NPT 433.0240125

Electrical Connections and Control Interfaces ​

BURKERT 20026082 Type 3361 AG2 circular plug-in connector arrangement

Electrical connection is established through multi-pole M12 circular connectors on the AG2 actuator base:

  • X1: M12 circular plug, 8-pin, A-coded, for analogue/digital setpoint and feedback signals.
  • X3: M12 circular plug, 5-pin, A-coded, for operating voltage 24 V DC and büS / CANopen communication.

X1 Circular Plug (8-Pin, A-Coded) Pin Assignment ​

PinSignal Assignment
1Digital input +
2GND for digital input and digital outputs
3Digital output 2 +
4Digital output 1 +
5Analogue output -
6Analogue output +
7Setpoint value / Analogue input -
8Setpoint value / Analogue input +

X3 Circular Plug (5-Pin, A-Coded) Pin Assignment ​

PinSignal Assignment
1CAN Shield / shield
2Operating voltage 24 V DC ±10%
3GND / CAN_GND
4CAN_H
5CAN_L

BURKERT 20026082 Type 3361 analogue control wiring interface diagram

Control Signal Technical Data ​

Signal CircuitElectrical Parameters
Analogue Setpoint InputGalvanically isolated from supply voltage and analogue output
0/4 to 20 mA (input resistance 70 Ω)
0 to 5/10 V (input resistance 22 kΩ)
Analogue OutputMax. 10 mA (for voltage output 0 to 5/10 V)
Load 0 to 800 Ω (for current output 0/4 to 20 mA)
Digital Input0 to 5 V = log "0", 10 to 30 V = log "1" (inverted logic configurable)
Digital OutputsPNP, current limited to 100 mA
Communication (Service-büS)Connection to PC via USB-büS interface stick, operated via Bürkert Communicator software Type 8920

Fluidic Performance and Flow Characteristics ​

Type 3361 valves operate with fluid entering below the valve seat (flow direction 2 -> 1), preventing pressure shocks from transferring force into the actuator mechanics.

BURKERT 20026082 Type 3361 equal percentage characteristic curve

Kv Flow Values at Intermediate Stroke Points (DN 40, Seat Size 40, AG2 1,300 N) ​

Stroke [%]Kv Value [m³/h]
5%0.60
10%0.70
20%1.10
30%1.70
40%2.70
50%4.00
60%6.00
70%9.20
80%13.80
90%18.20
100% (Kvs)24.00

Maximum Operating Pressure by Seat Seal Material ​

For DN 40 port connections with a 40 mm seat diameter driven by an AG2 actuator (1,300 N force):

  • PTFE soft seat seal (Article 20026082): 10 bar(g), Leakage Class VI (DIN EN 60534-4).
  • Stainless steel metallic seal: 10 bar(g), Leakage Class III.
  • PEEK seal washer: 6 bar(g), Leakage Class VI.

Operating Limits and Temperature Derating ​

Process limits are governed simultaneously by fluid temperature, line pressure, and ambient temperatures:

  • Seat Seal Limits: The PTFE seal washer in model 20026082 operates reliably between -10 °C and +130 °C. For processes consistently exceeding +130 °C, PEEK (-10 °C to +230 °C) or stainless steel (-40 °C to +230 °C) seat variants are specified in the series.
  • Pressure Ratings: Body structural limits comply with DIN EN 12516-1 (PN 25) and ASME B16.34 (Class 150).
  • Thermal Derating (AG2 Actuator): When equipped with a display module and an internal SAFEPOS energy-pack (Curve 3 in the AG2 temperature diagram), the maximum permissible ambient temperature is derated at elevated medium temperatures to protect internal electronic and capacitor components.

Medium Temperature Derating

At the maximum medium temperature of +130 °C, the ambient temperature surrounding the AG2 actuator with display and SAFEPOS must not exceed +55 °C. If the ambient temperature approaches +65 °C, medium temperature should be maintained below +90 °C.

Product Architecture and Actuation Features ​

BURKERT 20026082 Type 3361 AG2 electromechanical assembly overview

Integrated Position Controller ​

The brushless DC motor drives a planetary gear and ball screw connected to the valve spindle. An internal contactless displacement transducer continuously detects the physical spindle position (POS). The position controller compares the measured actual position with the setpoint value (CMD) and regulates the motor drive via variable CTRL, holding a dead band of ±0.1%.

BURKERT 20026082 Type 3361 integrated position controller control loop

Operating Elements and Optical Status ​

  1. Digital Display Module: Graphic screen with capacitive navigation keys enables direct configuration of setpoint modes, limits, calibration parameters, and live process views without opening the housing.
  2. 360° LED Light Ring: Integrated into the top cover assembly, the multicolor ring signals device status, target end positions, warnings, and maintenance intervals in accordance with NAMUR NE 107 recommendations.
  3. Mechanical Position Indicator: A yellow mechanical indicator marker is visible through a transparent window on the actuator base, indicating valve opening status even when the supply voltage is interrupted.
  4. Manual Override Modes:
    • Electrical Manual Override: Driven via display navigation keys in MANUAL mode.
    • Mechanical Manual Override: Accessible under the cover with a 3 mm Allen key. Permissible only in a de-energized state with a maximum torque of 2 Nm.

SAFEPOS Energy-Pack Emergency Power Module ​

Model 20026082 incorporates an internal SAFEPOS energy-pack. In the event of an external 24 V DC power failure, the energy pack provides autonomous electrical power to drive the linear actuator to the pre-programmed safety position (configured as normally closed at factory delivery). The energy pack requires a maximum of 120 seconds to achieve full operational charge upon power-up and has a service life of up to 10 years depending on operating temperatures. Capacity is continuously monitored internally, triggering predictive warnings before end-of-life.

De-energizing Procedure

Before performing maintenance, switch off the 24 V DC supply and wait until the SAFEPOS energy-pack has completely discharged and the 360° LED illuminated ring is fully extinguished. Mechanically moving internal parts present a pinching hazard if serviced while charged.

Installation, Body Torques, and X.TUNE Calibration ​

Mechanical Installation ​

The valve may be installed in any orientation, preferably with the actuator upright. Ensure that fluid flow matches the direction marked on the valve body (port 2 to port 1, flow below seat). Protect the unit against outdoor UV exposure and severe electromagnetic interference.

Tightening Torques for Assembly and Service ​

Connection ComponentSize / ApplicationTightening Torque
Valve Body ConnectionDN 40 (NPS 1 1/2)65 ±3 Nm (48 ±2 lbf·ft)
Valve Seat (screwed-in)Seat size 4085 +8 Nm
Spindle GuideSpindle ø14 mm (DN 32 to 50)60 Nm
Actuator Base ScrewsAG2 actuator base to housing5 Nm
Actuator Cover FastenersT25 hexalobular screws5 Nm
Display / Module FastenersT20 hexalobular screws1.1 Nm
SAFEPOS Locking ScrewT10 hexalobular screw1.1 Nm
Mechanical Override Key3 mm Allen keyMax. 2 Nm (do not exceed)

Positioner Calibration (X.TUNE) ​

After replacing internal wear parts, exchanging the valve seat, or reinstalling the actuator onto the valve body, an X.TUNE calibration routine must be run to adapt the positioner to the physical seat position and end stops.

No Pressure During X.TUNE

Never initiate the X.TUNE calibration while medium pressure is applied to the pipeline. Calibration under pressure produces an incorrect travel measurement, causing inaccurate control and potential process disruption.

To execute X.TUNE:

  1. Ensure line pressure is completely vented and drained.
  2. In the display menu, navigate to CONFIGURATION -> Position Controller -> MAINTENANCE -> CALIBRATION -> X.TUNE.
  3. Select the seat seal material (PTFE) as indicated on the type label.
  4. Confirm prompt to start calibration. The 360° LED ring illuminates orange during the automatic stroke travel and end-stop detection routine, returning to standard status upon completion.

Accessories and Replacement Parts ​

Component DescriptionOrder Article Number
Replacement SAFEPOS energy-pack wear part (AG2)285834
Valve seat set for Type 3361 (Seat size 40, body DN 40, with graphite seal)262177
Control cone set (Seat size 40, body DN 40, PTFE/steel cone with pin and seal)226968
Packing gland seal set (Spindle ø14 mm, DN 25 to DN 50)285722
Stainless steel spindle guide for packing gland (Body DN 40)246593
Seat installation tool (DN 40)652608
Modified socket wrench for packing gland (Spindle ø14 mm, SW21)683223
Holding device for pipe connections DN 25 to DN 50693771
SIM card for parameter backup and data transfer291773
Replacement plastic blind cover277881
USB-büS interface stick set 1 (Type 8923, with power pack and cables)772426
M12 connection cable, 8-pin A-coded, length 2 m (Signal X1)919061
M12 connection cable, 4-pin A-coded, length 5 m (Power X3, AG2 without CAN)918038
Recommended thread lubricant (Klüberpaste UH1 96-402, 100 g)Lubricant specification