Burkert Type 8652 AirLINE valve island (SKU 20031878) optimised for process automation. Features LC display, pneumatic functions, ATEX/IECEx Zone 2 approval, and PROFINET S2.

Burkert Type 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.
The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability. For instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks. The system supports safety-related shut-off of valves, higher plant availability with PROFINET S2 (system redundancy), and features EX-variants for ATEX / IECEx Zone 2, CCC, and cURus HazLoc CL I, II, III Div 2.
| Product properties | Description |
|---|---|
| Body Material | PA (polyamide) |
| Seal Material | NBR and PUR |
| Width per station | 11 mm |
| Manual override | Latching, spring return (optional: lockable) |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Pneumatic intermediate supply | Optional for the variants with 16, 20 and 24 valve slots |
| Performance data | Description |
|---|---|
| Pressure range | Vac...10 bar |
| External supply air | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Flow rate with Hot Swap | Flow reduced by approx. 3% |
| Nominal operating mode | Continuous operation (100 % duty cycle) |
| Electrical data | Description |
|---|---|
| Operating voltage | 24 V DC (±10% tolerance) |
| Residual ripple (at DC) | 1 Vss |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Nominal current of each valve | 29 mA (10 mA after power reduction) |
| Digital input | Max. 48 |
| Protection class | III according to DIN EN 61140, VDE 0140 |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages:

INFO
The approvals and conformities listed below must be stated when making enquiries. Not all available variants can be supplied with the below mentioned approvals or conformities.
| Approval | Description |
|---|---|
![]() | Explosion protection: As a category 3 device suitable for zone 2/22. ATEX: II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc. IECEx: Ex ec IIC Gc / Ex tc IIIC Dc. |
| UL Listed | UL Listed for the USA and Canada according to UL 61010-1 and CAN/CSA-C22.2 No. 61010-1. |
| UL Recognized | UL Recognized for Hazardous Locations for the USA and Canada for use in Class I, Zone 2; Class II, Zone 22; Class I, Division 2; Class II, III, Division 2. |
| CCC | China Compulsory Certification (CCC) for hazardous applications in China. |

| Variant | A | B | C | m | n |
|---|---|---|---|---|---|
| 4-fold | 66 | - | 4 x M5 | 3 | 1 |
| 8-fold | 35 | 111 | 8 x M5 | 7 | 2 |
| 12-fold | 77 | 154 | 10 x M5 | 11 | 3 |

| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply | 112 | 224 | 10 x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10 x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10 x M5 | 158.3 | 11 | 11 | 6 |
| 16-fold without intermediate supply | 99 | 198 | 10 x M5 | - | 15 | - | 4 |
| 20-fold without intermediate supply | 121 | 242 | 10 x M5 | - | 19 | - | 5 |
| 24-fold without intermediate supply | 143 | 286 | 10 x M5 | - | 23 | - | 6 |
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.
TIP
Maximum cable length for digital inputs is < 30 m. Possible cable cross-section: ≤ 1.5 mm².
Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).