Skip to content
Type 86528-BankAirLINE Quick VAIndustrial EthernetIP20 / IP65 CabinetATEX / IECEx Zone 2

BURKERT 20034183 (Type 8652) 8-Bank AirLINE Quick Stainless Steel Valve Island

BURKERT 20034183 is an 8-slot Type 8652 AirLINE valve island with stainless steel AirLINE Quick plate, 4x 2x3/2-way CF-C valves, D10 supply, D6 working ports, and RJ45 Industrial Ethernet.

BURKERT 20034183 (Type 8652) 8-Bank AirLINE Quick Stainless Steel Valve Island

BURKERT 20034183 is an 8-slot Type 8652 AirLINE valve island engineered for discrete control in process automation plants. This specific configuration features a stainless steel 1.4301 AirLINE Quick adapter plate, four pre-installed Type 6534 dual 3/2-way normally closed solenoid valve modules (circuit function C) on positions 1 through 4, and four blanking plates on positions 5 through 8. Pneumatic supply connection 1 is executed via D10 mm stainless steel push-in fittings, while working ports 2 and 4 are configured with D6 mm stainless steel push-in fittings. Communications are handled through an integrated Industrial Ethernet gateway supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic via two RJ45 connectors.

Type 8652 integrates an LC display that shows diagnostic and status messages in clear text and standardized symbols directly at the island, simplifying commissioning and on-site troubleshooting. Diagnostic telegrams are simultaneously transmitted over the fieldbus network to the supervisory PLC. The assembly is optimized for mechanical integration into control cabinet cutouts, providing IP65 ingress protection and NEMA Type 4X integrity when installed on enclosure walls or floors using the stainless steel AirLINE Quick interface.

BURKERT 20034183 Type 8652 AirLINE valve island overview with LC display and pneumatic sub-base

Technical Data and Unit Setup ​

Article 20034183 is factory-assembled with dedicated slot assignments and hardware selections as detailed below:

FeatureSpecification
Type8652 AirLINE
Article Number20034183
Number of Valve Slots8 PCE
Valve Position 12x 3/2-way CF-C (normally closed)
Valve Position 22x 3/2-way CF-C (normally closed)
Valve Position 32x 3/2-way CF-C (normally closed)
Valve Position 42x 3/2-way CF-C (normally closed)
Valve Positions 5 to 8Blind plates (expansion capacity up to 8 stations / 16 valve functions)
Width per Station11 mm
Body MaterialPolyamide (PA)
Seal MaterialNBR and PUR
Supply Connection (1)D10 mm push-in, Stainless steel 1.4401
Working Ports (2, 4)D6 mm push-in, Stainless steel 1.4401
Additional Air Supply LeftPush-in connector D6 and D10
Additional Air Supply RightPush-in connector D6 and D10
Additional Supply MiddleWithout intermediate feed (standard for 8-slot base)
Auxiliary Pilot AirInternal feed
Nominal Operating Pressure-1.00 bar to 10.00 bar (vacuum to 10 bar)
Pilot Pressure Range3.00 bar to 10.00 bar
Air Flow Rate QNn310 l/min (measured at +20 °C, 6 bar inlet, 1 bar differential)
Operating MediumLubricated or non-lubricated dry compressed air, neutral gases (5 µm filter recommended)
Compressed Air QualityISO 8573-1:2010, Class 7.4.4
Operating Voltage24 V DC (±10%, residual ripple 1 Vss)
Nominal Power per Valve0.7 W (0.175 W after electronic power reduction)
Nominal Current per Valve29 mA (10 mA after electronic power reduction)
Operating Mode100% continuous operation (ED)
Switching TimeMeasured according to ISO 12238 (Opening: 15 ms, Closing: 15 ms for CF-C)
Digital Inputs ModuleNone (0 DI fitted)
Check Valves in Exhaust 3/5Not fitted in this variant
Pneumatic HotSwap in Port 1Not fitted in this variant
Protection ClassClass III according to DIN EN 61140, VDE 0140
Ingress ProtectionIP20 standalone; IP65 inside closed cabinet with AirLINE Quick
Enclosure RatingType 4X (NEMA 250) in closed enclosures with stainless steel variant
Ambient & Medium Temperature-10 °C to +55 °C
Storage Temperature-20 °C to +60 °C

AirLINE Quick Stainless Steel Adapter System ​

The AirLINE Quick system allows the pneumatic valve terminal to be fastened directly into a rectangular cutout on the control cabinet bottom or side wall. Compressed air tubing connects directly to the outside face of the enclosure, eliminating bulkhead fittings, internal tubing runs, and excessive wiring.

BURKERT 20034183 AirLINE Quick stainless steel adapter plate and push-in connection layout

PropertyValue
Adapter Plate MaterialStainless steel 1.4301
Pneumatic Fitting MaterialStainless steel 1.4401
Supply / Exhaust PortsPush-in D10 mm (3/8")
Working PortsPush-in D6 mm (1/4")
Mounting LocationControl cabinet floor or control cabinet wall
Ingress SealTight seal to cabinet wall fulfilling IP65 and NEMA 4X

Installation Advantage

Direct mounting through the cabinet floor reduces enclosure volume requirements, cuts installation labour, and prevents internal air contamination within the electrical enclosure during line venting.

Circuit Functions ​

Article 20034183 contains four dual 3/2-way pilot valve blocks of circuit function C. Each 11 mm slice houses two independent 3/2-way valves serving ports 2 and 4.

Function CodeValve SchematicDescription
CF C (Fitted)2x 3/2-way solenoid valveServo-controlled, normally closed, equipped with manual override. De-energized state shuts off flow from supply (1) to ports (2) and (4), exhausting to (3) and (5).
CF D (Compatible)2x 3/2-way solenoid valveServo-controlled, normally open, equipped with manual override.
CF H (Compatible)5/2-way solenoid valveServo-controlled, with manual override. Supply pressure at port (1) pressurizes either port (2) or (4).
CF L (Compatible)5/3-way solenoid valveServo-controlled, with manual override. In middle position, all ports are closed/locked.
CF M (Compatible)5/3-way solenoid valveServo-controlled, with manual override. In middle position, ports (2) and (4) are pressurized.
CF N (Compatible)5/3-way solenoid valveServo-controlled, with manual override. In middle position, ports (2) and (4) are exhausted.
CF Z (Compatible)5/2-way impulse valveBistable double-solenoid impulse valve with 2 coils and manual override.

Positions 5, 6, 7, and 8 are covered by blanking plates (article no. 335779). They can be retrofitted with additional standard 6534 valves or SIA safety shut-off variants at any time.

Mechanical Dimensions and Cabinet Mounting ​

For an 8-slot terminal, the physical mounting envelope is governed by the 8-fold base parameters shown in the dimension drawing:

BURKERT 20034183 dimensional drawing for 4-, 8-, and 12-slot Type 8652 valve islands

Terminal SizeDimension A (mm)Dimension B (mm)Fastening Pattern CMultiplier mMultiplier n
4-fold66—4x M531
8-fold (20034183)351118x M572
12-fold7715410x M5113

Alternative DIN-rail mounting is supported via standard rail EN 50022 (35 x 7.5 mm or 35 x 15 mm). When positioning the valve island inside the cabinet, observe maintenance clearances between the island and the enclosure door or side wall to allow manual operation and module extraction.

BURKERT 20034183 control cabinet installation clearance and mounting arrangement

Electrical and Fieldbus Connections ​

Type 8652 uses distinct, galvanically separated power circuits for logic/communication and pneumatic coil actuation. Wiring is implemented using pluggable spring-loaded terminal connectors.

BURKERT 20034183 24 V interface plate assembly and terminal layout without modular shut-off

Logic and Display Power Supply (5-Pin Connector) ​

Connected via pluggable 5-pin spring terminal (article no. 920180, wire cross-section ≤ 1.5 mm²):

Pin / TerminalWire ColourSignal Assignment
1Red+24 V DC (Electronics & Display)
2WhiteCAN_H (büS interface)
3GreenShielding
4BlueCAN_L (büS interface)
5Black0 V DC (GND)

Pneumatic Valve Power Supply (2-Pin Connector) ​

Actuation power for pilot coils is routed through an independent 2-pin spring-loaded terminal (article no. 920442):

Pin / TerminalWire ColourSignal Assignment
1RedAUX +24 V DC (Coil power supply)
2Black0 V DC (GND)

Power Separation Notice

The pneumatic valves and the primary communication/display logic must be powered from independent supplies or separate fused branches to ensure that an emergency trip of valve coil power does not interrupt fieldbus communication or diagnostic reporting.

Industrial Ethernet Dual RJ45 Interface ​

Article 20034183 includes an ME43 Industrial Ethernet communication module with two 100BASE-TX RJ45 ports (X1 and X2), providing an integrated Ethernet switch for line or ring network topologies.

BURKERT 20034183 Industrial Ethernet dual RJ45 port interface and pin assignment

PinSignalDescription
1TX+Transmit Data +
2TX-Transmit Data -
3RX+Receive Data +
4N.C.Not connected
5N.C.Not connected
6RX-Receive Data -
7N.C.Not connected
8N.C.Not connected

The module automatically supports PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic. PROFINET S2 system redundancy is also supported to maintain plant availability during controller changeovers.

BURKERT 20034183 Industrial Ethernet network topology with master terminal and büS slave islands

Approvals and Standards ​

Type 8652 conforms to applicable European Union harmonisation legislation and carries certifications for hazardous industrial installations:

  • Explosion Protection (ATEX & IECEx): Category 3G/3D equipment for Zone 2 (Gas) and Zone 22 (Dust).
    • ATEX: BVS 20 ATEX E 031 U, II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc
    • IECEx: IECEx BVS 20.0024 U, Ex ec IIC Gc / Ex tc IIIC Dc
  • North America (cURus / UL):
    • UL Listed under UL 61010-1 and CAN/CSA-C22.2 No. 61010-1
    • UL Recognized for Hazardous Locations: Class I, Zone 2, AEx ec IIC Gc; Class II, Zone 22, AEx tc IIIC Dc; Class I, Division 2, Groups A, B, C, D; Class II/III, Division 2, Groups F, G
  • China Compulsory Certification (CCC): Certified by SITIIAS according to GB/T 3836 series for hazardous locations
  • Enclosure Rating: NEMA 250 Type 4X when fitted in a closed enclosure with stainless steel AirLINE Quick plate

Hazardous Area Installation Conditions

When installed in Zone 2 or Zone 22 explosive atmospheres, the valve island must be housed inside an enclosure providing at least IP54 (for 3G Gas) or IP6X (for 3D Dust). Transient protection must be set not to exceed 140% of the peak rated voltage. Spring terminals must not be plugged or unplugged while energized under an explosive atmosphere.

Replacement Components and Accessories ​

Original factory spare parts and compatible accessories for Type 8652 8-bank islands:

Article No.Component Description
301374Type 6534 replacement solenoid valve, 2x 3/2-way CF-C (normally closed), 24 V DC, 270 l/min, with manual override and screws
301375Type 6534 solenoid valve, 2x 3/2-way CF-D (normally open), 24 V DC, 310 l/min
301376Type 6534 solenoid valve, 5/2-way CF-H, 24 V DC, 290 l/min
335779Blind plate kit (covers 1 unused valve slot), including screws and seal
9201805-pin spring-loaded terminal plug for electronics and display power supply
9204422-pin spring-loaded terminal plug for pneumatic valve coil power supply
308661Screw set M5x10 A2 DIN 6912 (10 pieces, for cabinet floor mounting)
754960AirLINE Quick height adapter for 8-slot base without intermediate feed
60005566AirLINE Quick retaining plate for 8-slot base without intermediate feed
301799ME43 fieldbus gateway module for Industrial Ethernet (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT)
772426USB büS interface set 1 (Type 8923) for Bürkert Communicator software connection