Bürkert Type 3361 (SKU 20044550) electromotive 2-way globe control valve. Features DN 15 flange connection, 24V DC supply, 0-25 bar operating pressure, and highly precise dynamic closed-loop control.

Bürkert 20044550 (Type 3361) is an electromotive 2-way globe control valve designed for highly precise, dynamic closed-loop control under demanding operating conditions. This specific model features a DN 15 flange connection (DIN EN 1092-1), operates on a 24 V DC supply, and handles operating pressures from 0 to 25 bar. The electromotive actuator with a ball screw positions the control cone with exceptional precision, achieving a high positioning speed of up to 6 mm/s that reacts almost delay-free to process signals.
The Type 3361 features a weather, impact, and vibration-resistant design with an IP65/IP67 protection rating, making it suitable for harsh environmental conditions. The flow-optimized stainless steel valve body is equipped with a removable valve seat, providing an equal percentage 50:1 flow characteristic and a Kv value of 1.25 m³/h. This model includes an integrated positioner and is configured as normally closed (delivery status) with electrical energy storage (SAFEPOS energy-pack) to ensure a safe position in case of power failure.
| Feature | Specification |
|---|---|
| Design | Globe control valve |
| Port connection | Flange DIN EN 1092-1, DN 15 |
| Operating pressure | 0 to 25 bar (PN 25) |
| Kv value (water) | 1.25 m³/h |
| Flow characteristic | Equal percentage 50:1 |
| Flow direction | Below seat (against closing direction) |
| Supply voltage | 24 V DC ± 10 % (maximum residual ripple 10 %) |
| Medium temperature | -10 °C to +185 °C |
| Ambient temperature | -25 °C to +65 °C |
| Protection class | IP65/IP67 (DIN EN 60529), NEMA 4X |
| Safety setting | Normally closed, with electrical energy storage |
The Type 3361 series supports various approvals and conformities depending on the specific configuration and variable codes:
| Component | Material |
|---|---|
| Valve body | Stainless steel CF3M |
| Spindle | Stainless steel 1.4401 (316) / 1.4404 (316L) |
| Spindle seal | PTFE V-seals (filled) with spring compensation |
| Seat seal | Stainless steel (optionally hardened), PTFE or PEEK seal washer |
| Actuator housing | Powder-coated aluminium |
| Display housing / blind cover | PPS (standard), stainless steel 1.4301 (for ATEX/IECEx) |
| Seals (Actuator) | EPDM |
The valve features an equal-percentage flow characteristic according to DIN EN 60534-2-4. The theoretical rangeability varies depending on the seat size, reaching up to 50:1.

In addition to the maximum operating pressures, the application range of Bürkert process valves is limited by the nominal pressure in accordance with the relevant standard.

The maximum permissible temperature for the environment and the medium are dependent on each other. The maximum allowable temperature curves are determined for maximum operating conditions.
AG2 Actuator Limits:
AG3 Actuator Limits:
The position of the actuator is regulated according to the position set-point value, specified either by an external standard signal or via a fieldbus (digital).

Control Data
The electromotive linear drive consists of a brushless DC motor, a gear, and a spindle system that transfers the force to the closing element. The integrated electronics are controlled either by standard signals or via a fieldbus.

The position of the actuator (stroke) is controlled according to the position set-point value. The displacement transducer records the actual position (POS) of the electric linear actuator. The positioner compares the actual position value with the position set-point value (CMD). If there is a system deviation (Xd1), the electric motor drive is controlled via the actuating variable CTRL and the actual position value is changed accordingly.

The additionally implemented PID controller allows process control. The set-point position of the valve is calculated from the external signal (e.g., level, pressure, flow rate, temperature) for the process set-point and the actual process value via the control parameters.

X.TUNE Calibration
Do not run the X.TUNE function without requirement! The X.TUNE function must be run again only when the actuator has been removed afterwards or the valve body has been changed. Never run the X.TUNE under medium pressure, as this will result in an incorrectly adjusted controller and an uncontrolled process.
Available replacement part sets for the Type 3361 include:
Explore similar products in our catalog