DN 25 / 1" FlangeKvs 12 m³/h24 V DCSAFEPOS Energy PackATEX / IECEx Zone 2/22EC 1935/2004IP65 / IP67

BURKERT 20051195 Type 3361 Electromotive Globe Control Valve, 1" ANSI Class 150 Flange, AG2 Actuator

BURKERT 20051195 Type 3361 electromotive globe control valve with 1" ANSI Class 150 flange, stainless steel body, AG2 1300 N actuator, 24 V DC power, display, and SAFEPOS energy pack.

BURKERT 20051195 Type 3361 Electromotive Globe Control Valve, 1" ANSI Class 150 Flange, AG2 Actuator

BURKERT 20051195 (Type 3361) is an electromotive 2-way globe control valve engineered for demanding process automation tasks. It integrates a stainless steel CF3M valve body with 1" ANSI B16.5 Class 150 flange connections and an electromotive AG2 actuator delivering 1,300 N nominal driving force. The brushless DC motor and precision ball screw actuate a 25 mm seat orifice with an equal percentage control cone, achieving a rated flow capacity of 12 m³/h (Cv = 14 gpm) and a positioning speed of 6 mm/s with a typical closing time of 3.3 s. The flow direction is set below the seat (port 2 to port 1).

Equipped with the factory-fitted SAFEPOS energy-pack internal electrical storage module, BURKERT 20051195 automatically moves to a defined safety position (normally closed in delivery status) upon power disruption. The device incorporates an integrated digital positioner with ±0.1% control dead band, a rugged display module with push buttons, and a 360° multi-colour LED light ring. Electrical interfaces include M12 circular connectors handling standard analogue signals (0/4 to 20 mA, 0 to 5/10 V), digital I/O, and the büS service interface for configuration via the Bürkert Communicator software. The unit complies with ATEX and IECEx Zone 2/22 explosion protection standards as well as European Regulation EC 1935/2004 for food contact materials.

BURKERT 20051195 Type 3361 electromotive globe control valve overview

Technical Specifications & Operating Parameters ​

BURKERT 20051195 is configured specifically with AG2 actuator mechanics, a metallic stainless steel seat seal, and standard analogue communication with büS service access.

Specification ParameterValue / Technical Rating
Product TypeType 3361 Electromotive 2-way globe control valve
Article Number20051195
Nominal Diameter (DN / NPS)DN 25 / NPS 1"
Process Connection StandardANSI B16.5 Flange, Class 150 (FTF 37 according to DIN EN 558-2)
Flow DirectionBelow seat (against closing direction, port 2 to port 1)
Seat Orifice Diameter25 mm
Flow Coefficient Kvs (Water)12 m³/h (14 gal/min Cv)
Flow Characteristic CurveEqual percentage (theoretical rangeability 50:1)
Seat Leakage ClassClass IV (DIN EN 60534-4)
Operating Pressure Range0 to 25 bar(g)
Medium Temperature Range-10 °C to +150 °C
Permissible Ambient Temperature-25 °C to +55 °C (derated for configuration with display and SAFEPOS)
Actuator Size & Driving ForceAG2 (1,300 N driving force)
Linear Travel Speed6 mm/s
Typical Closing Time3.3 s
Supply Voltage24 V DC ±10% (residual ripple maximum 10%)
Operating Current DrawMax. 3 A at max load (includes 1 A SAFEPOS charging current); +2 A at minimum temp
Standby Power Draw2 to 5 W
Duty Cycle100% continuous
Protection Class (DIN EN 61140)Class III
Ingress Protection RatingIP65 / IP67 (DIN EN 60529), NEMA 4X
Fail-Safe Energy StorageSAFEPOS energy-pack internal module (Normally Closed delivery state)
Control Unit & ElectronicsIntegrated Positioner (Analogue control + Service-büS)
Position Dead Band±0.1%
Operator InterfaceDisplay module with configuration keys and 360° LED status ring
Electrical Connection TypeM12 multipole circular connectors (A-coded)
Explosion Protection RatingsATEX: II 3 G Ex ec IIC T4 Gc, II 3 D Ex tc IIIC T135 °C Dc; IECEx: Ex ec IIC T4 Gc, Ex tc IIIC T135 °C Dc
Food Contact ComplianceRegulation (EC) 1935/2004 Manufacturer Declaration

Temperature Limits & Operational Derating ​

The maximum permissible ambient temperature and process medium temperature are interdependent. BURKERT 20051195 incorporates both an integrated display module and the SAFEPOS energy-pack module, placing its thermal limits on characteristic curve 3 of the AG2 operating chart.

BURKERT 20051195 Type 3361 AG2 ambient and medium temperature limits chart

  • At medium temperatures up to +130 °C, the ambient temperature may reach up to +55 °C.
  • At medium temperatures reaching +150 °C, thermal derating applies to ensure reliable actuator electronics operation.
  • Fluid viscosity must remain below 600 mm²/s.

Fluidic Characteristics & Flow Capacity ​

BURKERT 20051195 features an equal percentage flow profile in accordance with DIN EN 60534-2-4. The theoretical rangeability is 50:1. The KvR value represents the lowest flow value where angularity tolerances remain compliant with DIN EN 60534-2-4 (at 5% stroke for seat sizes greater than 10 mm).

BURKERT 20051195 Type 3361 equal percentage flow curve

Stroke Opening (%)Kv Flow Value (m³/h)Cv Flow Value (gpm)Operating Differential Pressure LimitSeat Leakage Class
5%0.350.4125 bar(g)Class IV
10%0.380.4425 bar(g)Class IV
20%0.650.7625 bar(g)Class IV
30%1.01.1625 bar(g)Class IV
40%1.51.7425 bar(g)Class IV
50%2.22.5625 bar(g)Class IV
60%3.43.9525 bar(g)Class IV
70%5.15.9325 bar(g)Class IV
80%7.08.1425 bar(g)Class IV
90%9.410.9325 bar(g)Class IV
100% (Kvs)12.013.9525 bar(g)Class IV

Metallic Seat Sealing Properties

The metallic stainless steel seat seal configuration allows up to 0.01% leakage of nominal flow under DIN EN 60534-4 Class IV testing. It maintains dimensional stability under demanding process conditions and medium temperatures without seat elastomer degradation.

Construction Materials ​

The Type 3361 AG2 electromotive actuator and valve body utilize corrosion-resistant industrial alloys and engineered polymers.

BURKERT 20051195 Type 3361 AG2 actuator component materials diagram

BURKERT 20051195 Type 3361 globe valve body and seat materials

Item NumberComponent NameMaterial Specification
1 (Actuator)Display housing / Blind coverPolyphenylene sulphide (PPS) standard / Stainless steel 1.4301 (ATEX/IECEx)
2 (Actuator)Actuator coverPolyphenylene sulphide (PPS)
3 (Actuator)Housing cover sealEPDM
4 (Actuator)Actuator housingPowder-coated cast aluminium
6 (Actuator)Housing bottom sealEPDM
7 (Actuator)Actuator basePolyphenylene sulphide (PPS)
1 (Valve body)Spindle (stem)Stainless steel 1.4401 (316) / 1.4404 (316L)
2 (Valve body)Spindle seal packPTFE V-seals (filled) with spring compensation
3 (Valve body)Spindle guideStainless steel 1.4404 (316L)
4 (Valve body)Packing gland tubeStainless steel 1.4401 (316)
5 (Valve body)Valve body sealGraphite or PTFE
6 (Valve body)Seat sealStainless steel 1.4571
7 (Valve body)Control coneStainless steel 1.4571
8 (Valve body)Valve seat (screwed-in)Stainless steel 1.4571
9 (Valve body)Valve seat O-ringEPDM or PTFE
10 (Valve body)Globe valve bodyStainless steel CF3M

Dimensions & ANSI Flange Connection ​

BURKERT 20051195 utilizes a DN 25 (1") ANSI B16.5 Class 150 flanged body with a face-to-face length of 184 mm (DIN EN 558-2, face-to-face series 37).

BURKERT 20051195 Type 3361 AG2 actuator dimensions drawing

BURKERT 20051195 Type 3361 ANSI B16.5 flanged valve body dimensions

Dimension CodeParameter DescriptionDimension (mm)Dimension (inch)
NPSNominal Pipe Size1" (DN 25)1.00"
H1Actuator overall height (standard variant)446 mm17.56"
LFFace-to-face body length (DIN EN 558-2 Series 37)184 mm7.24"
∅ DFFlange outer diameter108 mm4.25"
∅ BFFlange pitch circle diameter79.2 mm3.12"
AFFlange thickness14.2 mm0.56"
∅ DBolt hole diameter15.7 mm (4 holes × 90°)0.62"
∅ MFRaised face diameter26.7 mm1.05"

Height Variation in Sealing State

Actuator height dimensions are specified without sealing compression. In the closed position, the AG2 actuator mechanism is raised by approximately 2 mm.

Electrical Connections & Pin Assignment ​

BURKERT 20051195 features two M12 circular connectors located on the AG2 actuator base: connector X1 for input and output signals, and connector X3 for operating power supply and büS communication.

BURKERT 20051195 Type 3361 AG2 circular plug-in connector arrangement

Connector X1 — Input and Output Signals ​

M12 circular plug, 8-pin, A-coded.

Pin NumberSignal AssignmentSignal Parameter Description
1Digital input +0 to 5 V = log "0", 10 to 30 V = log "1"
2GNDCommon ground for digital input and digital outputs
3Digital output 2 +PNP transistor, current-limited to 100 mA
4Digital output 1 +PNP transistor, current-limited to 100 mA
5Analogue output -Galvanically isolated analogue reference
6Analogue output +0/4 to 20 mA (load 0 to 800 Ω) or 0 to 5/10 V (max. 10 mA)
7Set-point value / Analogue input -Galvanically isolated set-point reference
8Set-point value / Analogue input +0/4 to 20 mA (input resistance 70 Ω) or 0 to 5/10 V (input resistance 22 kΩ)

Connector X3 — Power Supply & büS / CANopen ​

M12 circular plug, 5-pin, A-coded.

Pin NumberSignal AssignmentParameter Description
1CAN ShieldCable shielding connection
2Operating voltage +24 V DC ±10%
3GND / CAN_GNDPower supply ground and CAN ground reference
4CAN_HCAN high communication line (büS)
5CAN_LCAN low communication line (büS)

Control Architecture & Commissioning ​

BURKERT 20051195 utilizes an internal positioner loop. The internal displacement transducer detects the linear position (POS) of the actuator spindle, comparing it continuously against the set-point value (CMD) received from the analogue input or digital system bus.

BURKERT 20051195 Type 3361 integrated position controller control loop diagram

BURKERT 20051195 Type 3361 AG2 electromotive valve design and assembly

Manual Actuation ​

  1. Electrical Manual Actuation: Available in MANUAL operating state through the display module push buttons under View 1 (home screen) or via the Bürkert Communicator software.
  2. Mechanical Manual Override: A manual mechanical interface is situated under the display cover. It is actuated using a 3 mm Allen key.

De-energized Mechanical Operation

The mechanical manual override may only be actuated when the valve is completely de-energized. Applying mechanical torque while electrical power is present can cause permanent drive damage. The maximum permissible torque is 2 Nm. Turn counter-clockwise to open and clockwise to close.

Positioner Calibration (X.TUNE Routine) ​

The X.TUNE automatic adjustment routine adapts the positioner to the physical stroke of the seat and cone assembly. It must be initiated after remounting an actuator or replacing seat components.

Do Not Run X.TUNE Under Pressure

Never execute the X.TUNE function while the valve body is pressurized with process medium. Running X.TUNE under media pressure results in improper travel limits, causing process control malfunction. Ensure lines are completely depressurized before running calibration.

  • Via buttons: In de-energized fluid lines, remove cover and simultaneously press OPEN and CLOSE buttons for 5 seconds until the LED ring illuminates orange.
  • Via display: Navigate to Position Controller → MAINTENANCE → CALIBRATION → X.TUNE, select the seat seal material (stainless steel), and confirm.

Installation & Maintenance Guidelines ​

Actuator Assembly Torques ​

When replacing the control cone, seat, or packing gland, observe specified tightening torques across all mechanical threaded connections.

Assembly JointTool RequiredSpecified Tightening Torque
Valve body connection (DN 25)Open-end wrench on body connection hex60 ±3 Nm (44 ±2 lbf ft)
Actuator base fastening screwsT25 hexalobular key5 Nm
Spindle guide (DN 25, 14 mm spindle)Modified socket wrench SW21 (Article 683223)25 Nm
Screwed valve seat (Seat size 25)Installation tool DN 25 (Article 652606)40 +5 Nm
SAFEPOS module locking screwT10 hexalobular key1.1 Nm
Mechanical manual override3 mm Allen keyMax. 2 Nm

Actuator Separation Precondition

When removing the AG2 actuator from the valve body, the valve must always be at least 1/3 open. Never unscrew the actuator connection while the valve seat is pressed against the sealing face.

SAFEPOS Energy-Pack Servicing

The SAFEPOS energy-pack internal electrical storage module (wearing part Article 285834 for AG2) has a rated operating life of up to 10 years depending on thermal conditions. The controller continuously monitors storage cell health and displays a preventive service warning when capacity degrades. Recharging takes a maximum of 120 seconds upon power connection.