Skip to content
DN 1.5 mmG 1/424 V DC0-15 barIP54PWM InputPEEK / EPDM

BURKERT 20061314 Type 3280 Electromotive 2-Way Globe Proportional Valve, G 1/4, DN 1.5

Burkert 20061314 (Type 3280) is an electromotive 2-way globe proportional valve with G 1/4 brass body, DN 1.5 orifice, PEEK/EPDM seal, 24 V DC power supply, 0-15 bar operating pressure, and PWM control.

BURKERT 20061314 Type 3280 Electromotive 2-Way Globe Proportional Valve, G 1/4, DN 1.5

BURKERT 20061314 (Type 3280) is an electromotive direct-acting 2-way globe proportional control valve designed for dosing neutral liquids and gases in open or closed control loops. Driven by a linear stepper motor via a threaded spindle, the valve continuously repositions a parabolic control cone against media flow entering below the valve seat. Article 20061314 features a G 1/4 threaded brass body, a 1.5 mm nominal seat diameter (Kv 0.065 m³/h), a PEEK seat seal backed by EPDM elastomer, and an integrated electronic assembly operating from 24 V DC.

BURKERT 20061314 BURKERT Type 3280 electromotive 2-way globe proportional valve overview

Maintaining a set valve position does not require motor power; holding power drops below 1 W once positioned. The unit responds to an 800 Hz PWM set-point command and provides a PNP digital output signal confirming the fully closed end position.

Technical Specifications ​

ParameterValue
Article Number20061314
Model FamilyType 3280
DesignElectromotive 2-way direct-acting globe control valve
Port ConnectionG 1/4 internal thread (EN ISO 228-1)
Seat Orifice DN1.5 mm (1/16")
Kv Value (Water, +20 °C, Δp = 1 bar)0.065 m³/h
Flow DirectionUnder seat (flow against closing direction)
Operating Pressure Range0...15 bar(g) for fluid media; 0...22 bar(g) for gaseous media
Supply Voltage24 V DC ±10% (max. residual ripple 10%)
Power Consumption< 1 W holding position; max. 12 W (high-pressure variant)
Set-point Input SignalPWM signal (800 Hz, 24 V logic level, min. 10 V, max. 30 V)
Digital Feedback OutputPNP, max. 100 mA current limit, active when valve is closed
Actuating Time (0...100% stroke)Approx. 2.5 s (normal speed) / 5 s (slow speed)
Dead Band±0.5% of end value (setting range 1:100)
Duty CycleUp to 100% (subject to ambient temperature derating)
Medium Temperature Range0 °C...+70 °C
Permissible Ambient Temperature-10 °C...+50 °C (for high-pressure specification)
Max. Medium Viscosity600 mm²/s (cSt)
Degree of ProtectionIP54 (with suitable connected cable plug)
WeightApprox. 0.7 kg

Construction and Material Specifications ​

The actuator housing isolates electronic and electromechanical components from the process medium. Linear force is delivered by the stepper motor via an internal threaded spindle coupled to the valve stem.

BURKERT 20061314 BURKERT Type 3280 sectional view with material components

Item No.ComponentMaterial
1Actuator Housing CoverPolycarbonate (PC GF10)
2Actuator Housing BasePolyphenylene sulphide (PPS GF40)
3Stem SealEPDM / FKM / NBR
4SpindleStainless steel 1.4305
5Upper Valve BodyBrass
6Piston with Parabolic Control Element & Guiding ShaftStainless steel 1.4305 / PTFE
7Seat SealPEEK (seat size 1.5 mm) backed by EPDM
8O-ringEPDM
9Valve SeatStainless steel 1.4301 / 1.4305
10Valve BodyBrass

Seat Tightness Note for Seat Size 1.5 mm

For seat sizes 1.0 mm and 1.5 mm, PEEK seat seals are used instead of soft elastomeric discs. The seat tightness of the valve is consequently lower compared to pure elastomer seals.

Electrical Connection and DIP Switch Settings ​

Electrical connection is established through an 8-pin A-coded M12 circular male connector located on the actuator base. Input/output signals share supply potential without galvanic isolation.

M12 PinWire Color (Cable 919061)ConfigurationFunction / Signal Level
1WhiteSupply +24 V DC ±10%, max. residual ripple 10%
2BrownSupply GND24 V DC GND
3GreenInternal useDo not connect; insulate wire
4YellowInternal useDo not connect; insulate wire
5GreyInternal useDo not connect; insulate wire
6PinkSet-point input +PWM input (800 Hz) / 4...20 mA / 0...10 V
7BlueDigital outputPNP, 0...5 V (log. 0), 10...30 V (log. 1, closed)
8RedSignal GNDSignal reference GND
BodyShieldShieldingConnected to valve body

BURKERT 20061314 BURKERT Type 3280 DIP switch configuration location inside actuator

Configuration parameters are accessible via a 4-pole internal DIP switch block on the electronics board after loosening the actuator housing cover:

DIP SwitchPositionPWM Version FunctionStandard Analog Function
1OFFIncreasing: 0...100% PWM duty cycle corresponds to 0...100% strokeNormal: 4...20 mA corresponds to 0...100% stroke
1ONDecreasing: 100...0% PWM duty cycle corresponds to 0...100% strokeReversal: 20...4 mA corresponds to 0...100% stroke
2OFFNo functionSet-point input 4...20 mA
2ONNo functionSet-point input 0...10 V
3OFFActuating speed normal (0...100% in 2.5 s)Actuating speed normal (0...100% in 2.5 s)
3ONActuating speed slow (0...100% in 5.0 s)Actuating speed slow (0...100% in 5.0 s)
4OFFLow power mode: OFFLow power mode: OFF
4ONLow power mode: ON (reduced holding force/heating)Low power mode: ON (reduced holding force/heating)

Low Power Mode Pressure Restriction

Activating DIP switch 4 reduces motor drive current, lowering operating heat. This setting must only be enabled when differential pressure across the valve does not exceed 1 bar and maximum media pressure does not exceed 3 bar. Exceeding these limits will cause positioning failure.

Performance, Pressure, and Flow Characteristics ​

The motor valve produces a linear operating characteristic when sized properly relative to total circuit friction.

BURKERT 20061314 BURKERT Type 3280 linear flow characteristic curve

Pressure Ranges by Orifice Size ​

Orifice Seat Size (mm)Port ConnectionKvs Value (m³/h)Standard Pressure Range (bar)High-Pressure Liquids (bar)High-Pressure Gases (bar)
1.0G 1/40.0300...60...150...22
1.5 (20061314)G 1/40.0650...60...150...22
2.0G 1/4, G 3/80.1300...60...150...22
3.0G 1/4, G 3/80.3000...60...150...22
4.0G 3/80.5000...60...120...12
5.0G 3/80.7500...60...120...12
6.0G 3/80.9000...60...150...16
8.0G 1/21.5000...60...120...12
10.0G 1/21.9000...60...100...10

Flow Calculation and Seat Dimensioning

Select the seat diameter so that valve pressure drop represents at least 25% of the total system pressure loss (Δp_valve > 0.25 · Δp_total). A smaller pressure drop causes the linear characteristic to deform into a non-linear system response.

Flow Coefficient Formulae ​

Flow ConditionLiquids Kv [m³/h]Gases Kv [m³/h]
Sub-critical: $p_2 > \frac{p_1}{2}$$Q \cdot \sqrt{\frac{\rho}{1000 \cdot \Delta p}}$$\frac{Q_N}{514} \cdot \sqrt{\frac{T_1 \cdot \rho_N}{p_2 \cdot \Delta p}}$
Supercritical: $p_2 < \frac{p_1}{2}$$Q \cdot \sqrt{\frac{\rho}{1000 \cdot \Delta p}}$$\frac{Q_N}{257 \cdot p_1} \cdot \sqrt{T_1 \cdot \rho_N}$

Motor Duty Cycle Derating ​

Motor duty cycle designates the operational active running time of the stepper drive, not the continuous energized duration of the electronic assembly.

BURKERT 20061314 BURKERT Type 3280 duty cycle derating diagram against ambient temperature

Operating above recommended duty cycle percentages causes thermal overload. At an ambient temperature of +50 °C, the permissible motor duty cycle for standard seats DN 1...6 is derated, requiring lower continuous cycling rates.

Dimensions ​

Dimensions for threaded body variants in millimetres:

BURKERT 20061314 BURKERT Type 3280 threaded variant dimensional drawing

Port DA (NPT)B (NPT)C (G thread)Dimension E (mm)Dimension F (mm)Dimension G (mm)Dimension H (mm)
G 1/4 (20061314)——1296.4134.21027.5
NPT 1/45.810.0—96.4134.21027.5
G 3/8——1297.4137.21227.5
NPT 3/86.010.3—97.4137.21227.5
G 1/2——1497.4139.21429.5
NPT 1/28.213.7—97.4139.21429.5

Accessories and Safety Position in Case of Power Failure ​

During an interruption of electrical power, Type 3280 retains its instantaneous physical position. Moving to a fail-safe position requires an external capacitive buffer module.

Accessory DescriptionSpecification / FunctionArticle No.
Capacitive Buffer Module Type 1573Supplies 18 V DC backup for several seconds upon power failure to drive valve closed773440
Power Supply Unit Phoenix Class 285...240 V AC / 24 V DC, 1.25 A, NEC Class 2 (UL 1310)772438
Power Supply Unit for DIN Rail100...240 V AC / 24 V DC, 1.0 A, NEC Class 2772361
Power Supply Unit for DIN Rail100...240 V AC / 24 V DC, 2.0 A, NEC Class 2772362
Power Supply Unit for DIN Rail100...240 V AC / 24 V DC, 3.8 A, NEC Class 2772898
M12 Shielded Cable Socket, 8-pinCable length: 2 m, flying leads for analog/digital I/O918991
M12 Unshielded Cable Socket, 8-pinCable length: 2 m, flying leads for analog/digital I/O919061

Installation and Maintenance ​

Mount the valve preferably in an upright vertical position with the actuator cover pointing upwards. The flow direction must correspond to the arrow on the brass body (fluid entering under the seat).

Upstream Media Filtration

Solid particulates in the fluid stream can cause seat leakage or mechanical blockage. Install an upstream dirt filter with a mesh width ≤ 0.3 mm before the valve inlet.

When tightening port fittings, apply wrench counterforce only to the brass valve body flats. Never use the plastic actuator housing as a lever arm. Clean housing surfaces with damp cloths and neutral detergents; alkaline cleaning agents must not be used on PPS or PC components.