Burkert Type 8647 AirLINE SP pneumatic valve island for direct integration into Siemens SIMATIC ET 200SP and ET 200SP HA. Features LC display and safety shut-off.

Burkert Type 8647 AirLINE SP is a modular, electropneumatic automation system consisting of connection and valve modules. It has been especially developed for safe and complete integration into the decentralised peripheral system "SIMATIC ET 200SP" and "SIMATIC ET 200SP HA" from Siemens. Pneumatically operated process valves, pneumatic cylinders or other pneumatic components can be connected to the pneumatic outputs.

The valve block is used to incorporate pneumatic pilot valves directly in SIMATIC ET 200SP/SP HA and to activate them via SIMATIC ET 200SP/SP HA. If feedback indicators are installed at pneumatic components, the position of the actuated pneumatic components can be displayed on the associated pilot valve. This ensures problems during installation or ongoing operation are easy to identify.
| Product properties | Type 0460, Type 6524, Type 6525 |
|---|---|
| Width per station | 11 mm |
| Manual override | Standard |
| Number of valve slots | For single valves: max. 64. For impulse and double valves: max. 32 |
| Pressure range | Vac...10 bar (with UL approval Vac...8 bar) |
| Operating voltage | 24 V DC |
| Communication module | Siemens SIMATIC ET 200SP / SP HA |
| Communication interface | PROFIBUS DP, PROFINET IO |
| Degree of protection | IP20, IP65 in closed control cabinets |

The pilot valve Type 6524 (single and double valve) and Type 6525 (single valve) consist of a pilot flipper solenoid valve Type 6144 and a pneumatic seat valve. The circuit function allows switching of high pressures with low power consumption and short switching times.

The solenoid valve Type 0460 consists of a pneumatic valve body fitted with a double coil pilot valve. The principle allows switching of high pressures together with low power consumption and fast switching times.

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Note
The valves of Type 0460 cannot be installed with AirLINE Quick due to their size.
Optionally, electronic base modules (EVS variants) can be connected with an external, potential-free switching contact. As a result, the safety shutdown of all valves of this base module is possible (e.g. for "Central system off"). Variants of valve Types 6524 and 6525 are available that allow the connection of an external switching contact (e.g. safety relay) for safety shutdown per channel.

Explore similar products in our catalog