Skip to content
Modular DesignAirLINE QuickIP20

BURKERT 20073142 Type 8640 Modular Valve Island

Burkert 20073142 Type 8640 modular valve island for pneumatics. Features 11mm width, 16x 5/2 valve function H, G 1/4 pressure port, and collective socket module.

BURKERT 20073142 Type 8640 Modular Valve Island

The BURKERT 20073142 Type 8640 valve unit system is designed to solve diverse and complex control problems due to its systematic modular construction and combination of pneumatic and electrical interfaces. By putting together a row of pneumatic modules with different numbers of valves, 2 to 24 valve functionalities may be realized on one valve unit. Electrical connectivity is achieved by either fieldbus interfaces, common connection (parallel connection technique) or multipin interfaces. The valves allow different applications to be covered. Bodies and connection modules are made of high-quality plastic (polyamide) and are easy to assemble by means of the built-in snap connectors.

BURKERT 20073142 Type 8640 modular valve island overview

Key Features

  • Compact design and modular configuration.
  • Higher flexibility in the control cabinet due to AirLINE Quick.
  • Simple exchange of valves (with option “P-shut-off” – also possible during operation).

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

BURKERT 20073142 Type 8640 AirLINE Quick adapter

Advantages:

  • Reduced space requirement in the control cabinet.
  • Makes it possible to use more compact control cabinets.
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet.

INFO

Type 0460 valves cannot be installed with AirLINE Quick because of their size.

Product Design and Assembly

Electronics

BURKERT 20073142 Type 8640 electronics assembly

No.Element
1Electrical end module, left
2Terminal module for feedback
3Extension module for electrical inputs
4Multi-pin digital inputs (initiators)
5Electrical end module, left
6Basic electrical module standard
7Fieldbus module
8Multipin valve outputs
9Common connection module

Pneumatics 11 mm Width per Station

BURKERT 20073142 Type 8640 pneumatics 11mm assembly

No.Element
1Pneumatic connection module, left
2Basic pneumatic modules
3Pneumatic connection module, right
4Valves (for example 5/2-way)

Installation

Manual Override

To operate the valve manually, press the manual override and turn it 90° clockwise (until it stops). The manual override is locked and does not reset automatically.

BURKERT 20073142 Type 8640 manual override operation

WARNING

Only operate the manual override when the power is off.

Installing Multiple Blocks

BURKERT 20073142 Type 8640 multi-block installation

  1. Begin installation with connection module on the left.
  2. Check modules for complete installation with 2 O-rings each.
  3. Lightly oil or grease all O-rings before engaging.
  4. Engage the lower latch hooks of the module to be attached in the latch grooves of the preceding module. Make sure that the O-rings are properly seated.
  5. Press the module to be locked upwards slightly and engage the upper latch hook.
  6. Insert 3 O-rings into the recess on the back of the valve and ensure that the seal is properly fitted.

DANGER

Crushed O-rings and profile seals lead to leaky blocks.

Valve Block Installation

BURKERT 20073142 Type 8640 valve block installation

Standard rail installation:

  • Hook the valve block with the upper groove into the standard rail (35 x 15 or 35 x 7.5 EN 50022).
  • Snap the lower clamping pieces into the standard rail.
  • Tighten the screws on the clamping pieces.

Wall installation: