16 Valve SlotsIndustrial EthernetAirLINE Quick Aluminium12x 5/2-Way CF-H4x Blind Plate24 V DCIP20 / IP65

BURKERT 20075342 Type 8652 AirLINE 16-Slot Valve Island, Industrial Ethernet, Aluminium Base

BURKERT 20075342 (Type 8652) is an AirLINE valve island with 16 valve slots (12x 5/2-way CF-H, 4x blind plates), Industrial Ethernet (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT), D10/D6 brass ports, and IP20 rating.

BURKERT 20075342 Type 8652 AirLINE 16-Slot Valve Island, Industrial Ethernet, Aluminium Base

BURKERT 20075342 (Type 8652) is an AirLINE valve island developed for process automation applications, combining high-density pneumatic piloting with multi-protocol fieldbus communication. Configured as a 16-slot assembly on an anodised aluminium AirLINE Quick base, this unit is equipped with 12 monostable 5/2-way solenoid valves (Circuit Function H) in positions 1 through 12, while positions 13 through 16 are fitted with blind plates for future expansion. The integrated Industrial Ethernet interface supports PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic over dual RJ45 ports.

Diagnostic messages are displayed on the built-in LC display in both clear text and standard symbols, allowing direct on-site troubleshooting during commissioning and maintenance while relaying diagnostic data to the central controller. The AirLINE Quick mounting system passes pneumatic supply and working lines directly through the control cabinet floor or wall, eliminating separate bulkhead pass-through fittings and keeping installation footprint minimal.

BURKERT 20075342 Type 8652 AirLINE Quick anodised aluminium adapter plate

Configured Layout and Slot Allocation ​

Article 20075342 is delivered pre-assembled with the following valve slot allocation and connection hardware:

Slot PositionPopulated ComponentCircuit Function / Details
Position 1 to 12Solenoid Valve Type 65345/2-way monostable CF-H, servo-controlled, manual override
Position 13 to 16Blind PlateDummy plate sealing unpopulated valve stations
Supply Port (1 / P)Push-in Fitting D10 mmNickel-plated brass connection
Working Ports (2, 4)Push-in Fitting D6 mmNickel-plated brass connections
Additional Supply LeftPush-in Fitting D6 and D10 mmIncluded on left connection module
Additional Supply MiddleNoneBase without intermediate supply module
Pilot Air FeedInternalAuxiliary pilot air tapped internally from supply pressure

General Technical Specifications ​

Technical ParameterSpecification Value
Valve Island TypeType 8652 AirLINE
Article Number (MPN)20075342
Housing MaterialPolyamide (PA)
Seal MaterialsNBR and PUR
Station Width11 mm per valve slice
Maximum Number of Valve SlotsUp to 24 slots (16 slots populated/reserved on this unit)
Pressure Range-1.0 bar to 10.0 bar (vacuum to 10 bar)
Auxiliary Pilot Air Pressure3.0 bar to 10.0 bar
Nominal Flow Rate QNn (Air)310 l/min (measured at +20 °C, 6 bar inlet, 1 bar pressure drop)
Operating Voltage24 V DC (±10%, residual ripple 1 Vss)
Nominal Power per Valve0.7 W inrush (0.175 W after electronic power reduction)
Nominal Current per Valve29 mA (10 mA after electronic power reduction)
Operating ModeContinuous operation (100% duty cycle)
Switching TimeMeasured in accordance with ISO 12238
Operating MediumOil-free or lubricated compressed dry air, neutral gases
Compressed Air Purity ClassISO 8573-1:2010, Class 7.4.4 (5 μm filtration recommended)
Ambient & Medium Temperature-10 °C to +55 °C
Storage Temperature-20 °C to +60 °C
Electrical Protection ClassClass III in accordance with DIN EN 61140, VDE 0140
Degree of ProtectionIP20 bare; IP65 inside closed cabinet with AirLINE Quick base
NEMA RatingType 4X in closed enclosures (stainless steel variant)

AirLINE Quick Installation System ​

The AirLINE Quick adapter plate allows direct mounting to the base or side wall of an industrial control cabinet. All pneumatic supply and service lines connect on the outside of the enclosure, saving internal duct space and reducing wiring and piping hours.

PropertyAdapter Plate Specification
Base Plate MaterialAnodised aluminium
Fitting MaterialsNickel-plated brass (stainless steel 1.4401 optional)
Supply / Exhaust PortsPush-in connector D10 mm (3/8" optional)
Working PortsPush-in connector D6 mm (1/4" optional)
Mounting PositionsControl cabinet floor or control cabinet wall

Dimensional Drawing (16-Slot Variant) ​

BURKERT 20075342 Type 8652 16-valve slot dimensional diagram

Dimensions for 16-, 20-, and 24-valve slot base variants:

Configuration VariantA (mm)B (mm)C (Mounting Screws)D (mm)mm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116
16-fold without intermediate supply (20075342)9919810 x M5—15—4
20-fold without intermediate supply12124210 x M5—19—5
24-fold without intermediate supply14328610 x M5—23—6

Mounting Fasteners

Base installation requires screw set M5x10 A2 DIN 6912 (Article no. 308661) to secure the valve island to the control cabinet cut-out.

Electrical and Fieldbus Connections ​

The valve island utilizes independent electrical feeds for communication electronics and pneumatic valve coils, isolating digital logic from actuator load switching.

InterfaceTerminal TypePin / Terminal Assignment
Communication & Display Power5-pin spring-loaded terminal (max. 1.5 mm²)Red: 24 V DC
White: CAN_H (büS)
Green: Shielding
Blue: CAN_L (büS)
Black: GND (0 V DC)
Pneumatic Valve Power (AUX)2-pin spring-loaded terminalTerminal 1 (Red): AUX 24 V DC
Terminal 2 (Black): GND (0 V DC)

Industrial Ethernet Interface (X1 / X2 RJ45) ​

BURKERT 20075342 Type 8652 Industrial Ethernet RJ45 terminal diagram

RJ45 PinSignal Assignment
Pin 1TX+ (Transmit Data +)
Pin 2TX- (Transmit Data -)
Pin 3RX+ (Receive Data +)
Pin 4Not connected (N.C.)
Pin 5Not connected (N.C.)
Pin 6RX- (Receive Data -)
Pin 7Not connected (N.C.)
Pin 8Not connected (N.C.)

Control Cabinet Installation Clearances ​

BURKERT 20075342 Type 8652 control cabinet mounting clearance

Maintenance Clearance Requirements

Maintain minimum clearance distances to the control cabinet front door and internal structures to allow valve replacement and module access. In installations utilizing pneumatic hot-swap valves, ensure adequate mechanical tool clearance.

Modular Structure and Assembly ​

BURKERT 20075342 Type 8652 24 V interface plate and valve island assembly

Article 20075342 includes a standard 24 V interface plate without individual safety shut-off (SIA) wiring. The modular architecture permits servicing individual valve slices without disassembling adjacent pneumatic blocks.

Network Topology and Gateway Integration ​

BURKERT 20075342 Type 8652 Industrial Ethernet network topology

The Type 8652 valve island can operate as a direct Industrial Ethernet slave on fieldbus networks (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT) or function as an active master terminal interfacing downstream Type 8652 sub-stations via the CANopen-based büS backbone.

Replacement Valves and Spare Components ​

Replacement valve slices and dummy plates for Type 8652 valve terminals must be ordered by their specific spare part article numbers:

Valve Function / DesignationCircuit FunctionOrifice (mm)QNn Air (l/min)Pressure Range (bar)Response Open / Close (ms)Spare Part Article No.
5/2-way monostable (Configured on 20075342)CF H4290Vac to 1020 / 25301376 (Set: 296033)
Blind Plate (Configured on 20075342)Dummy————335779 (Set: 327614)
3/2-way single NCCF C4270Vac to 1015 / 1520102334 (Set: 20088974)
2x 3/2-way NCCF C4270Vac to 1015 / 15301374 (Set: 296031)
2x 3/2-way NOCF D4310Vac to 1015 / 15301375 (Set: 296032)
5/2-way bistable (impulse)CF Z4290Vac to 1020 / 25301377 (Set: 296034)
5/3-way mid-position closedCF L4275Vac to 1015 / 15301380 (Set: 296036)
5/3-way mid-position ventilatedCF M4300Vac to 1020 / 20301379 (Set: 296035)
5/3-way mid-position exhaustedCF N4300Vac to 1020 / 20301381 (Set: 296039)

Accessories and Software Tools ​

Item DescriptionOrdering Article No.
ME43 Fieldbus Gateway Industrial Ethernet (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT)301799
ME43 Fieldbus Gateway Profibus DP301803
ME43 Fieldbus Gateway CANopen / büS301802
ME43 Fieldbus Gateway PROFINET S220081296
5-Pin Spring-Loaded Terminal (Communication & Display Power)920180
2-Pin Spring-Loaded Terminal (Valve AUX Power)920442
USB büS Interface Set 1 (Type 8923) for Bürkert Communicator Software772426
Bürkert Communicator Configuration SoftwareType 8920
Screw Set M5x10 A2 DIN 6912 (Pack of 10 for cabinet base mounting)308661
Height Adapter for 16-Valve Base without Intermediate Feed60041928
Retaining Plate for 16-Valve Base without Intermediate Feed60005880

Approvals and Compliance ​

  • ATEX: BVS 20 ATEX E 031 U, II 3G Ex ec IIC Gc, II 3D Ex tc IIIC Dc
  • IECEx: IECEx BVS 20.0024 U, Ex ec IIC Gc, Ex tc IIIC Dc
  • North America: UL Listed to UL 61010-1 and CAN/CSA-C22.2 No. 61010-1
  • Hazardous Locations (cURus): Class I, Zone 2, AEx ec IIC Gc / Ex ec IIC Gc U; Class II, Zone 22, AEx tc IIIC Dc / Ex tc IIIC Dc U; Class I, Div 2, Groups A, B, C, D; Class II/III, Div 2, Groups F, G
  • CCC: Certified in accordance with GB/T 3836 for explosion-proof environments in China
  • Enclosure Rating: Type 4X according to NEMA 250 in closed control cabinets