Skip to content
16 Valve SlotsIndustrial EthernetAirLINE Quick AluminiumIP20D10/D6 Brass Ports24 V DC

BURKERT 20081087 Type 8652 AirLINE 16-Slot Industrial Ethernet Valve Island with AirLINE Quick Aluminium Base

BURKERT 20081087 Type 8652 AirLINE 16-slot valve island features an aluminium AirLINE Quick base, Industrial Ethernet RJ45 connectivity, 13 pre-installed 2x3/2 CF-C valves, and IP20 rating.

BURKERT 20081087 Type 8652 AirLINE 16-Slot Industrial Ethernet Valve Island with AirLINE Quick Aluminium Base

BURKERT 20081087 Type 8652 AirLINE is a 16-slot electro-pneumatic valve island engineered for process automation environments, pre-configured with 13 dual 3/2-way normally closed valves (CF-C) and 3 blind plates on an AirLINE Quick anodised aluminium base. The system integrates an ME43 fieldbus gateway supporting Industrial Ethernet protocols (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic) via dual RJ45 ports. Operating from a 24 V DC supply across a pressure range of -1 bar to 10 bar, the unit provides a nominal air flow rate of 310 l/min per valve station at 6 bar inlet pressure and 1 bar differential pressure.

BURKERT 20081087 Type 8652 AirLINE valve island overview

Technical Specifications ​

Product PropertyTechnical Data
Valve Island TypeType 8652 AirLINE (Article 20081087)
Body MaterialPolyamide (PA)
Seal MaterialNBR and PUR
Number of Valve Slots16 slots (configured: 13x 2x 3/2-way CF-C, 3x blind plates)
Width per Station11 mm
Manual OverrideLatching, spring return (optional lockable)
Pneumatic Intermediate Supply1 intermediate supply module included (standard on 16-, 20-, and 24-slot variants)
Nominal Operating Pressure-1.00 bar to 10.00 bar (vacuum to 10 bar)
Auxiliary Pilot Air3 bar to 10 bar (internal feed configured)
Nominal Flow Rate QNn (Air)310 l/min (measured at +20 °C, 6 bar inlet pressure, 1 bar pressure drop)
Flow Rate with Hot Swap ActiveFlow reduced by approximately 3%
Operating ModeContinuous operation (100% duty cycle)
Switching Time MeasurementAccording to ISO 12238
Operating Voltage24 V DC (±10%), residual ripple 1 Vss
Nominal Power per Valve0.7 W (0.175 W after power reduction)
Nominal Current per Valve29 mA (10 mA after power reduction)
Digital Inputs0 (basic version without display or input modules)
Protection ClassClass III according to DIN EN 61140, VDE 0140
Operating MediumOil-free or lubricated compressed dry air, neutral gases (5 µm filter recommended)
Compressed Air QualityISO 8573-1:2010, Class 7.4.4
Degree of ProtectionIP20 (bare unit); IP65 when mounted in closed control cabinet with AirLINE Quick
Storage Temperature-20 °C to +60 °C
Medium and Ambient Temperature-10 °C to +55 °C

AirLINE Quick Adapter Plate ​

BURKERT 20081087 AirLINE Quick adapter plate for cabinet mounting

AirLINE Quick enables direct mechanical mounting of the valve terminal onto the control cabinet floor or wall, eliminating separate bulkhead connections and internal tubing runs.

  • Space saving inside the electrical control cabinet, permitting smaller cabinet enclosures
  • Direct connection of pneumatic tubing underneath the cabinet base
  • Reduced cabinet wiring and assembly time
PropertySpecification
Adapter Plate MaterialAnodised aluminium (Article 20081087 configuration; optional 1.4301 stainless steel)
Pneumatic Connector MaterialNickel-plated brass (optional 1.4401 stainless steel)
Pneumatic Supply / Exhaust Ports (1, 3, 5)Push-in connector D10 mm, 3/8"
Pneumatic Working Ports (2, 4)Push-in connector D6 mm, 1/4"
Mounting PositionControl cabinet floor or control cabinet wall

Valve Configuration and Circuit Functions ​

The 20081087 unit is pre-assembled with 16 valve slots allocated as follows:

  • Slots 1 to 13: 2x 3/2-way solenoid valve, Circuit Function C (CF C), servo-controlled, normally closed without power, with manual override
  • Slots 14 to 16: Blind plate covering reserve slots for subsequent expansion

Type 8652 accommodates multiple standard and safety-related valve circuit functions using Type 6534 sub-base solenoid valves:

Circuit FunctionDescription
CF C (Single)3/2-way solenoid valve, servo-controlled, with manual override, normally closed
CF C (Dual)2x 3/2-way solenoid valve, servo-controlled, with manual override, normally closed
CF D (Dual)2x 3/2-way solenoid valve, servo-controlled, with manual override, normally open
CF H5/2-way solenoid valve, servo-controlled, with manual override; pressure applied via port 1 feeds port 2 or 4
CF L5/3-way solenoid valve, servo-controlled, with manual override; all ports locked in middle position
CF M5/3-way solenoid valve, servo-controlled, with manual override; ports 2 and 4 pressurized in middle position
CF N5/3-way solenoid valve, servo-controlled, with manual override; ports 2 and 4 exhausted in middle position
CF Z5/2-way solenoid valve, impulse variant with 2 coils and manual override
SIA CF CSafety-related 3/2-way or 2x 3/2-way valve without manual override, with external shutdown terminal
SIA CF HSafety-related 5/2-way valve without manual override, with external shutdown terminal
SIA CF LSafety-related 5/3-way valve without manual override, all ports locked in middle position

Approvals and Hazardous Area Operation ​

Type 8652 holds certifications for international industrial installations and hazardous location categories:

  • ATEX: BVS 20 ATEX E 031 U, II 3G Ex ec IIC Gc, II 3D Ex tc IIIC Dc
  • IECEx: IECEx BVS 20.0024 U, Ex ec IIC Gc, Ex tc IIIC Dc
  • North America (USA/Canada): UL Listed per UL 61010-1 and CAN/CSA-C22.2 No. 61010-1
  • UL Recognized for Hazardous Locations: Class I, Zone 2, AEx ec IIC Gc / Ex ec IIC Gc U; Class II, Zone 22, AEx tc IIIC Dc / Ex tc IIIC Dc U; Class I, Division 2, Groups A, B, C, D; Class II/III, Division 2, Groups F, G
  • China Compulsory Certification (CCC): Conformity per GB/T 3836 series standards for hazardous applications
  • Enclosure Rating: Type 4X per NEMA 250 in closed enclosures when using stainless steel AirLINE Quick hardware

Hazardous Location Operating Restrictions

  • For Type of Protection 'ec', install the equipment in an enclosure certified to EN/IEC 60079-0 and EN/IEC 60079-7 with a minimum ingress rating of IP54.
  • For Type of Protection 'tc' (dust), install in an enclosure complying with EN/IEC 60079-0 and EN/IEC 60079-31 with a minimum rating of IP6X.
  • Only operate the device in areas with an environmental pollution degree of at least 2 as defined in IEC 60664-1.
  • Ensure transient overvoltage protection limits peaks to no more than 140% of the nominal peak supply voltage.
  • Disconnecting or plugging electrical terminal connections (24 V supply, SIA, EVS, digital inputs) while energized is prohibited in explosive atmospheres.
  • The pneumatic Hot Swap function must not be used in an explosive atmosphere unless the absence of an explosive atmosphere has been established and verified by suitable testing equipment.

Dimensions and Control Cabinet Installation ​

BURKERT 20081087 Type 8652 16-fold valve island dimensional drawing with intermediate supply

Dimensional layout for Type 8652 valve islands with 16, 20, and 24 valve slots (all dimensions in mm):

VariantABCDmm'n
16-fold with intermediate supply (20081087)11222410x M5114.3774
20-fold with intermediate supply13426810x M5158.31175
24-fold with intermediate supply15631210x M5158.311116
16-fold without intermediate supply9919810x M5—15—4
20-fold without intermediate supply12124210x M5—19—5
24-fold without intermediate supply14328610x M5—23—6

Installation Clearance for Hot Swap

When mounting the valve island inside a control cabinet, maintain sufficient clearance between the valve island front and the cabinet door/front edge to permit unhindered insertion and removal of valve bodies during maintenance. Observe the specified rear-wall-to-mounting-plate spacing.

Electrical and Fieldbus Connections ​

Type 8652 separates electronic communications power from pneumatic valve actuation power via independent terminal blocks.

Communication and Display Power Supply (5-Pin Spring-Loaded Terminal) ​

  • Terminal Type: 5-pin spring terminal (pluggable, Article 920180)
  • Conductor cross-section: ≤ 1.5 mm²
PinWire ColourAssignment
1Red24 V DC
2WhiteCAN_H (büS connection)
3GreenShielding
4BlueCAN_L (büS connection)
5BlackGND (0 V DC)

Pneumatic Valve Power Supply (2-Pin Spring-Loaded Terminal) ​

  • Terminal Type: 2-pin spring terminal (pluggable, Article 920442)
  • Independent feed for solenoid coils
ClipWire ColourAssignment
1RedAUX 24 V
2BlackGND (0 V DC)

Industrial Ethernet Hardware Interface (RJ45 Ports X1 and X2) ​

BURKERT 20081087 Industrial Ethernet RJ45 terminal pin assignment

Article 20081087 includes an ME43 Industrial Ethernet gateway with dual RJ45 Ethernet ports (X1 and X2) supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic:

PinAssignment
1TX+
2TX-
3RX+
4Not connected (N.C.)
5Not connected (N.C.)
6RX-
7Not connected (N.C.)
8Not connected (N.C.)

Product Architecture and Modular Options ​

BURKERT 20081087 interface plate 24 V product assembly

Article 20081087 is built with a standard 24 V interface plate without modular shut-off. Modular configurations within Type 8652 accommodate optional electronic sub-modules:

Digital Input Modules (8DI Module, Optional) ​

Type 8652 supports up to 48 digital inputs across modular stations. Each input is supplied with 24 V DC, current-limited to 30 mA, accepting 2-wire, 3-wire, or dry contact mechanical switches.

PropertyValue
DiagnosticsOpen-circuit detection (2-wire sensors), short-circuit detection (3-wire sensors)
Switching ThresholdV_OFF = 0 to 5 V; V_ON = 10 to 30 V
Input Current at V_ONMax. 5.7 mA per channel (typical at 24 V DC)
Input Impedance> 4 kΩ
Galvanic IsolationNo, common reference potential for all channels
Maximum Cable Length< 30 m (cross-section ≤ 1.5 mm²)

For functional safety architectures, Type 6534 SIA replacement valves integrate dedicated terminal blocks to cut coil power independently of fieldbus commands via external potential-free contacts. Alternatively, a 12-pin spring-loaded terminal module provides group-based emergency shut-off with contact switching ratings up to 1.5 A at 24 V DC.

Network Topology Architecture ​

BURKERT 20081087 Industrial Ethernet master and büS slave network architecture

An AirLINE Type 8652 valve island equipped with an Industrial Ethernet interface functions as an intelligent master valve terminal. Downstream sub-networks of Type 8652 islands fitted with büS interfaces connect as slave terminals via CANopen-based büS links, consolidating fieldbus nodes into a single Ethernet IP address.

Commissioning with Bürkert Communicator Software ​

BURKERT 20081087 Bürkert Communicator Type 8920 configuration software

Configuration and diagnostics are carried out through the Bürkert Communicator software (Type 8920), which operates on the EDIP (Efficient Device Integration Platform) framework.

  • Complete monitoring of cyclic process values and acyclic diagnostic data
  • Address mapping between fieldbus gateways and sub-network bus devices
  • Graphical configuration interface for sub-system control logic
  • Firmware upgrades, backup, and restore routines for connected EDIP hardware
  • Physical connection to PC via USB büS interface set (Article 772426)

Ordering Information and Spare Parts ​

Type 6534 Replacement Solenoid Valves for Type 8652 ​

All replacement valves include mounting screws and operate at 24 V DC with a 4 mm nominal orifice across vacuum to 10 bar (minimum 3 bar pilot pressure):

Circuit FunctionQNn (Air)Opening TimeClosing TimeArticle No. (Valve)Article No. (Spare Kit)
CF C (Single 3/2-way NC)270 l/min15 ms15 ms2010233420088974
CF C (Dual 2x 3/2-way NC)270 l/min15 ms15 ms301374296031
CF D (Dual 2x 3/2-way NO)310 l/min15 ms15 ms301375296032
CF H (5/2-way)290 l/min20 ms25 ms301376296033
CF Z (5/2-way impulse, 2 coils)290 l/min20 ms25 ms301377296034
CF L (5/3-way, middle locked)275 l/min15 ms15 ms301380296036
CF M (5/3-way, middle vented)300 l/min20 ms20 ms301379296035
CF N (5/3-way, middle exhausted)300 l/min20 ms20 ms301381296039
Dummy Valve (Blind Plate)———335779327614

AirLINE Quick Mechanical Accessories (16-Slot Variant) ​

DescriptionVariantQuantityArticle No.
M5 x 10 A2 DIN 6912 Fastening ScrewsControl cabinet base mounting10308661
Height Adapter16-fold with intermediate feed1754962
Height Adapter16-fold without intermediate feed160041928
Retaining Plate (Cabinet Exterior)16-fold with intermediate feed160005568
Retaining Plate (Cabinet Exterior)16-fold without intermediate feed160005880
Blind Plate16-fold with intermediate feed1754967
Blind Plate16-fold without intermediate feed160041929

ME43 Fieldbus Gateways and Plugs ​

DescriptionArticle No.
ME43 Fieldbus Gateway — Industrial Ethernet (PROFINET, EtherNet/IP, Modbus TCP, EtherCAT)301799
ME43 Fieldbus Gateway — PROFIBUS DP301803
ME43 Fieldbus Gateway — CANopen / büS301802
ME43 Fieldbus Gateway — PROFINET S220081296
5-Pin Spring-Loaded Terminal (Power & büS)920180
2-Pin Spring-Loaded Terminal (Valve 24 V Power)920442
USB büS Interface Set 1 (Type 8923) for Bürkert Communicator772426