BURKERT 20086194 (Type 8652) AirLINE Valve Island for Process Automation

Burkert Type 8652 AirLINE valve island (SKU 20086194) optimised for process automation. Features 24 valve ports, PROFIBUS DPV1, LC display diagnostics, and AirLINE Quick.

BURKERT 20086194 (Type 8652) AirLINE Valve Island for Process Automation

Burkert Type 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.

The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that prevent unplanned actuation due to pressure peaks.

Burkert 20086194 Type 8652 AirLINE valve island overview

INFO

Key Features:

  • Safety-related shut-off of valves possible
  • Higher plant availability with PROFINET S2 (system redundancy)
  • Process reliability through pneumatic functions
  • Optimised for installation at the bottom of the control cabinet
  • EX-variants: ATEX / IECEx Zone 2, CCC, cURus HazLoc CL I, II, III Div 2

General Technical Data

PropertyValue
Body MaterialPA (polyamide)
Seal MaterialNBR and PUR
Width per station11 mm
Number of valve slotsMax. 24 (Configured as 24 PCE for SKU 20086194)
Pressure rangeVac...10 bar
External supply air3...10 bar
Flow rate $Q_{Nn}$ value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Operating voltage24 V DC (±10% tolerance)
Nominal power per valve0.7 W (0.175 W after power reduction)
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Degree of protectionIP20, IP65 in closed control cabinets
Ambient temperature-10 °C...+55 °C

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • Makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

Burkert 20086194 Type 8652 AirLINE Quick adapter plate

FeatureSpecification
Adapter Plate MaterialStainless steel 1.4301 or Anodised aluminium
Pneumatic connectionStainless steel 1.4401 or Nickel-plated brass
Pneumatic Supply / ExhaustPush-in D 10 mm, 3/8"
Pneumatic working portsPush-in D 6 mm, 1/4"

Circuit Functions

The Type 8652 supports various standard circuit functions (CF) including:

  • CF C: 3/2-way solenoid valve, normally closed
  • CF D: 2 × 3/2-way solenoid valve, normally open
  • CF H: 5/2-way solenoid valve
  • CF L: 5/3-way solenoid valve, all ports locked in middle position
  • CF M: 5/3-way solenoid valve, ports 2 and 4 ventilated in middle position
  • CF N: 5/3-way solenoid valve, ports 2 and 4 exhausted in middle position
  • CF Z: 5/2-way solenoid valve, impulse variant with 2 coils

SIA Variant

A special SIA variant is available for safety-related shut-off. These valves (Type 6534) are equipped with additional connection terminals, allowing a valve circuit to be interrupted by an external switch. Manual override is not required for these valve variants.

Approvals and Conformities

  • Explosion Protection: ATEX (II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc) and IECEx (Ex ec IIC Gc / Ex tc IIIC Dc) suitable for zone 2/22.
  • North America: UL Listed (UL 61010-1) and UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Div 2).
  • CCC: China Compulsory Certification for hazardous applications in China.

Dimensions (16-, 20- and 24-fold)

Burkert 20086194 Type 8652 dimensions for 16, 20, and 24-fold variants

VariantABCDmm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116
24-fold without intermediate supply14328610 x M5-23-6

(Dimensions in mm)

Product Connections

Power Supply for Communication and Displays

Connect the 5-pin spring-loaded terminal according to the pin assignment (24 V DC, CAN_H, SHIELDING, CAN_L, GND). Possible cable cross-section: ≤ 1.5 mm².

Power Supply for Pneumatic Valves

The interface plate has a 2-pin spring-loaded terminal to which the pneumatic valves’ power supply is connected (AUX 24 V, GND).

Fieldbus Interface

For PROFIBUS DPV1 (as configured in SKU 20086194), a 9-pin D-Sub socket is utilized. Other available interfaces include Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) via RJ45, and CANopen/büS.

Product Installation

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

Burkert 20086194 Type 8652 installation situation inside control cabinet

WARNING

For installations in hazardous areas (Ex zones), the control cabinet must be approved for use in hazardous areas and sized sufficiently to dissipate heat. The internal temperature must not exceed the maximum permitted ambient temperature of the device.