Skip to content
Type 8652Industrial EtherNet4-SlotAirLINE Quick ALATEX / IECEx Zone 2/2224 V DC

BURKERT 20087556 Type 8652 AirLINE Modular Valve Island, 4-Slot Industrial Ethernet

BURKERT 20087556 (Type 8652 AirLINE) is a 4-slot modular valve island with Industrial Ethernet, D10/D6 brass push-in connections, -1 to 10 bar nominal pressure, and ATEX/IECEx Zone 2/22 compliance.

BURKERT 20087556 Type 8652 AirLINE Modular Valve Island, 4-Slot Industrial Ethernet

BURKERT 20087556 (Type 8652 AirLINE) is an electro-pneumatic modular valve island designed to pilot and control pneumatic loads such as process valves and actuators in automation architectures. The 20087556 configuration integrates a 4-slot valve base with an aluminium AirLINE Quick interface, external pilot air routing, and multi-protocol Industrial Ethernet connectivity terminating in RJ45 ports.

BURKERT 20087556 BURKERT Type 8652 modular valve island AirLINE Quick assembly

Hardware Setup and Port Allocation ​

Model 20087556 provides 4 modular valve slots preconfigured with two pneumatic valves and two blanking positions. Pneumatic lines terminate via push-in connections built from brass, while mechanical docking through control cabinet walls is established by the aluminium AirLINE Quick adapter.

Setup ParameterConfiguration Value
Total Valve Slots4 PCE
Valve Position 12x 3/2-way CF-C
Valve Position 2Blind plate
Valve Position 32x 3/2-way CF-D
Valve Position 4Blind plate
Supply ConnectionD10 (Brass)
Working PortsD6 (Brass)
AirLINE Quick MaterialAluminium
Auxiliary Pilot AirExternal supply
Additional Supplies (Left / Middle / Right)Without additional feed
Intermediate Feed Quantity0 PCE
Integrated Check Valves (Ports 3/R and 5/S)No
Pneumatic HotSwap in Port 1 (P)No
Digital Inputs0 (No DI electronic module)

Pneumatic and Electrical Specifications ​

AirLINE Type 8652 operates across positive and partial-vacuum process pressures, utilizing Type 6164 pilot solenoid valves as pilot actuators on Type 6534 pneumatic directional spool valves.

Specification ParameterValue Range
Nominal Operating Pressure-1.00 bar to 10.00 bar
External Pilot Air Pressure3.00 bar to 10.00 bar
Medium Temperature Range-10.00 °C to +55.00 °C
Ambient Temperature Range-10.00 °C to +55.00 °C
Nominal Supply Voltage24 V DC (±10%)
Maximum Current Consumption3 A (typical marking reference)
Maximum Valve Functions per Base FamilyUp to 48 valve functions
Basic Ingress ProtectionIP20 (with appropriate connection)

Communication and Network Integration ​

BURKERT 20087556 incorporates a dedicated fieldbus communication module supporting real-time Industrial Ethernet standards over RJ45 physical media. Supported network protocols include:

  • PROFINET IO
  • EtherNet/IP
  • Modbus TCP
  • EtherCAT
  • CC-Link IE Field Basic

Internal communication across the valve manifold utilizes büS, a CANopen-based internal system bus developed by Bürkert for valve island diagnostics and status transmission.

Hazardous Area Approval and Rating Data ​

Type 8652 valve islands certified for potentially explosive atmospheres carry two nameplates defining general operational parameters and explosion-proof ratings. Ex certification is valid only when Bürkert-authorized Type 6164 and Type 6534 components are maintained.

BURKERT 20087556 BURKERT Type 8652 standard nameplate diagram and field layout

PositionDescriptionIndicated Data
1Device TypeType 8652 AirLINE
2Pressure Range3 to 10 bar
3Ambient Temperature Range-10 °C to +55 °C
4Rated Voltage / Current Consumption24 V DC / 3 A
5Serial NumberS/N (factory encoded)
6Manufacturing CodeW14AL (factory encoded)
7Device Order NumberIdent 20087556

BURKERT 20087556 BURKERT Type 8652 hazardous location nameplate marking for PX68 and PU17

Explosion Markings for Code PX68 ​

  • ATEX Certificate: BVS 20 ATEX E 031 U
  • ATEX Gas / Dust Marking: II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc
  • IECEx Certificate: IECEx BVS 20.0024 U
  • IECEx Marking: Ex ec IIC Gc / Ex tc IIIC Dc
  • CCC Certification: GB/T 3836.2021 audited by SITIIAS; PTB (CE0102) production monitoring

Explosion Markings for Code PU17 (North American Ratings) ​

  • Class I, Zone 2, AEx ec IIC Gc / Ex ec IIC Gc U
  • Class II, Zone 22, AEx tc IIIC Dc / Ex tc IIIC Dc U
  • Class I, Division 2, Groups A, B, C, D
  • Class II/III, Division 2, Groups F, G

Control Cabinet and Enclosure Requirements ​

Enclosure Protection Limits

Type 8652 has an open rating of IP20. When operated in hazardous areas, install the unit in a certified enclosure or control cabinet meeting the following ratings:

  • Category 3G / Zone 2: Minimum IP54 enclosure rating per EN/IEC 60079-0 and EN/IEC 60079-7 ("ec" protection type).
  • Category 3D / Zone 22: Minimum IP64 / IP6X enclosure rating per EN/IEC 60079-0 and EN/IEC 60079-31 ("tc" dust ignition protection).
  • Operating Environment: Pollution degree 2 or better per IEC 60664-1. Outdoor operation is prohibited.

Cabinet internal dimensions must ensure sufficient heat dissipation so the maximum allowable ambient temperature (+55 °C) is not exceeded. At +55 °C internal cabinet temperature, the assembly remains within temperature class T4 limits. When utilizing the AirLINE Quick interface through the cabinet wall, the outer surface operating temperature does not exceed +80 °C.

Wiring and Operational Safety Restrictions ​

Terminal and Connector Disconnection

Transient voltage protection must prevent line spikes from exceeding 140% of the peak rated voltage at the power input. Within explosive atmospheres, connecting or disconnecting terminal connectors for 24 V DC supply, SIA (Safety Shutdown), EVS (External Valve Shutdown), or digital inputs while energized is strictly prohibited.

Disconnect all circuits and ensure zero-voltage status before unplugging terminals or cable connectors, unless the area is confirmed non-hazardous using verified testing instruments.

HotSwap Restriction

HotSwap valve replacement under energized conditions is forbidden in explosive atmospheres. Removal or insertion of pneumatic valve modules is permitted only when the local atmosphere has been proven non-explosive by authorized monitoring devices.