Skip to content
24 Valve SlotsIndustrial EthernetAirLINE Quick AluminiumPneumatic HotSwapIntegrated Check ValvesIP20 / IP65 Cabinet Floor

BURKERT 20106520 Type 8652 AirLINE 24-Valve Slot Industrial Ethernet Valve Island

BURKERT 20106520 Type 8652 AirLINE valve island features 24 valve slots, aluminium AirLINE Quick base, D10 supply, D6 working ports, integrated check valves, HotSwap, and Industrial Ethernet via dual RJ45.

BURKERT 20106520 Type 8652 AirLINE 24-Valve Slot Industrial Ethernet Valve Island

BURKERT 20106520 is a pre-configured Type 8652 AirLINE 24-station pneumatic valve island developed specifically for process automation environments. Configured under article number 20106520, the unit features an anodised aluminium AirLINE Quick adapter plate for direct control cabinet floor installation, D10 brass push-in supply connections, D6 brass working ports, and internal auxiliary pilot air feed. The station layout incorporates 3 slots equipped with dual 3/2-way normally closed valves (circuit function C) and 21 slots equipped with 5/2-way monostable valves (circuit function H), backed by integrated check valves in exhaust ports 3 (R) and 5 (S), and a pneumatic HotSwap function in pressure port 1 (P).

BURKERT 20106520 Type 8652 AirLINE valve island modular assembly

Diagnostic functions on the integrated LC display present status indications both in clear text and graphic symbols. Diagnostic messages are simultaneously transferred to the higher-level automation controller over Industrial Ethernet, providing immediate feedback during commissioning and maintenance.

Station Configuration and Allocation (20106520) ​

Article number 20106520 delivers a fixed 24-slot pneumatic valve array optimised for process actuators:

Slot PositionValve Circuit FunctionDescriptionOperating State
Position 12x 3/2-way CF-CServo-controlled pilot valve pairNormally closed (de-energised)
Position 22x 3/2-way CF-CServo-controlled pilot valve pairNormally closed (de-energised)
Position 32x 3/2-way CF-CServo-controlled pilot valve pairNormally closed (de-energised)
Positions 4 to 245/2-way monostable CF-HServo-controlled single spool valve (21 stations)Pressure to port 2 or 4 via port 1

Additional physical supply configuration:

  • Pneumatic Supply Connection: Push-in connector D10 mm, nickel-plated brass
  • Pneumatic Working Ports: Push-in connector D6 mm, nickel-plated brass
  • Auxiliary Pilot Air: Internal pilot feed
  • Additional Supply Left: Push-in connector D6 and D10 mm
  • Additional Supply Middle: Without
  • Additional Supply Right: Without
  • Digital Inputs: 0 (No digital input modules installed on el. modules 1 through 6)
  • Check Valves: Integrated in ports 3 (R) and 5 (S)
  • Pneumatic HotSwap: Integrated in port 1 (P)

Technical Specifications ​

Specification ParameterValue / Range
Valve Island Type8652 AirLINE
Total Valve Slots24 stations (each station width: 11 mm)
Maximum Controllable Valve FunctionsUp to 48 functions
Housing MaterialPA (Polyamide)
Seal MaterialsNBR and PUR
Operating Pressure RangeVac to 10 bar (-1.00 bar to 10.00 bar)
External Supply Air (Auxiliary Pilot Air)3 to 10 bar
Nominal Air Flow Rate $Q_{Nn}$310 l/min (at +20 °C, 6 bar inlet, 1 bar $\Delta P$)
Flow Rate with HotSwap IntegratedReduced by approx. 3%
Operating Voltage24 V DC (±10%), residual ripple 1 Vss
Nominal Power per Valve0.7 W (0.175 W after electronic power reduction)
Nominal Current per Valve29 mA (10 mA after electronic power reduction)
Operating ModeContinuous operation (100% ED)
Switching Time MeasurementConforms to ISO 12238
Operating MediumOil-free or lubricated compressed dry air, neutral gases (5 µm filtration recommended)
Compressed Air Quality ClassISO 8573-1:2010, Class 7.4.4
Storage Temperature-20 °C to +60 °C
Ambient & Medium Temperature-10 °C to +55 °C
Degree of ProtectionIP20 naked; IP65 when installed to closed cabinet floor via AirLINE Quick
Electrical Protection ClassClass III according to DIN EN 61140, VDE 0140

AirLINE Quick Adapter Plate ​

The AirLINE Quick adapter plate integrates the valve island directly into the control cabinet floor or wall cutout. All working lines and main air supply hoses terminate directly at the bottom plate on the exterior of the enclosure, eliminating cabinet bulkhead fittings and internal routing hoses.

BURKERT 20106520 AirLINE Quick anodised aluminium floor mounting adapter plate

ComponentMaterial / Parameter
Adapter PlateAnodised aluminium (variant 20106520)
Pneumatic Push-in FittingsNickel-plated brass (supply D10 mm, working D6 mm)
Mounting OrientationControl cabinet floor or control cabinet wall
Ingress ProtectionIP65 inside closed control cabinet environment

Dimensions and Cabinet Installation ​

BURKERT 20106520 Type 8652 24-slot terminal dimensional drawing

Dimensional parameters for 16-, 20-, and 24-slot variants (all dimensions in mm):

VariantABCDm$m'$n
16-fold with intermediate supply11222410×M5114.3774
20-fold with intermediate supply13426810×M5158.31175
24-fold with intermediate supply15631210×M5158.311116
16-fold without intermediate supply9919810×M5—15—4
20-fold without intermediate supply12124210×M5—19—5
24-fold without intermediate supply14328610×M5—23—6

Installation Clearance for HotSwap

When installing the valve island inside the control cabinet, maintain the required clearance between the valve island and the front edge of the cabinet door or panel. Sufficient front clearance allows individual valve slices to be unlocked and disengaged upwards during online hot swap without mechanical interference.

BURKERT 20106520 control cabinet front edge clearance for HotSwap valve replacement

BURKERT 20106520 distance from control cabinet rear wall to mounting plate

Electrical and Industrial Ethernet Connections ​

The 20106520 terminal communicates via Industrial Ethernet and isolates valve actuation power from digital communication circuits.

BURKERT 20106520 Type 8652 product assembly and 24 V interface board

Power Supply for Communication and LC Display ​

A 5-pin spring-loaded terminal connector (article no. 920180) provides bus and electronics power (wire cross-section $\le 1.5\text{ mm}^2$):

TerminalWire ColourAssignment
1Red+24 V DC
2WhiteCAN_H (büS connection)
3GreenShielding
4BlueCAN_L (büS connection)
5BlackGND (0 V DC)

Power Supply for Pneumatic Valves ​

A separate 2-pin spring-loaded terminal connector (article no. 920442) supplies valve coil actuators:

TerminalWire ColourAssignment
1RedAUX 24 V DC
2BlackGND (0 V DC)

Industrial Ethernet Physical Interface (Dual RJ45 Ports X1 and X2) ​

BURKERT 20106520 Industrial Ethernet dual RJ45 fieldbus communication ports

The unit integrates two RJ45 ports (X1 and X2) supporting Industrial Ethernet protocols: PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic, as well as PROFINET S2 system redundancy:

RJ45 PinSignal Assignment
Pin 1TX+ (Transmit Data +)
Pin 2TX- (Transmit Data -)
Pin 3RX+ (Receive Data +)
Pin 4Not connected (N.C.)
Pin 5Not connected (N.C.)
Pin 6RX- (Receive Data -)
Pin 7Not connected (N.C.)
Pin 8Not connected (N.C.)

BURKERT 20106520 Industrial Ethernet master and büS slave network architecture

Pneumatic Reliability and Circuit Functions ​

Type 8652 incorporates internal pneumatic safeguards designed for process continuity:

  1. Integrated Check Valves in 3 (R) and 5 (S): Check valves embedded in exhaust lines prevent back-pressure waves generated by exhausting actuators from feeding back into adjacent pilot lines. This eliminates unintended valve movements during parallel switching events.
  2. Pneumatic HotSwap in Port 1 (P): A manual mechanical valve slice replacement can occur while main supply pressure remains on channel 1 (P). An internal check seat closes when the pilot valve is disengaged, avoiding main system depressurisation.

Standard Circuit Functions on Type 8652 Terminals ​

Function CodeValve TypeSwitching MechanismDe-energised Position
CF C3/2-way solenoid valveServo-controlled, manual overrideNormally closed (NC)
CF C (2×)2× 3/2-way solenoid valveServo-controlled, manual overrideBoth normally closed (NC)
CF D (2×)2× 3/2-way solenoid valveServo-controlled, manual overrideBoth normally open (NO)
CF H5/2-way solenoid valveServo-controlled, monostable, manual overridePort 2 or 4 pressurised via port 1
CF Z5/2-way solenoid valveImpulse bistable (2 coils), manual overridePressure maintained at last switched port
CF L5/3-way solenoid valveServo-controlled, manual overrideMiddle position all ports blocked
CF M5/3-way solenoid valveServo-controlled, manual overrideMiddle position ports 2 and 4 ventilated
CF N5/3-way solenoid valveServo-controlled, manual overrideMiddle position ports 2 and 4 exhausted

Explosion Protection and Hazardous Location Requirements ​

When equipped under explosive atmosphere classification options (e.g. code PU17 or PX68), Type 8652 complies with ATEX, IECEx, and North American hazardous location standards:

  • ATEX Approval: BVS 20 ATEX E 031 U; II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc
  • IECEx Approval: IECEx BVS 20.0024 U; Ex ec IIC Gc / Ex tc IIIC Dc
  • North America (cURus): Class I, Zone 2, AEx ec IIC Gc / Class II, Zone 22, AEx tc IIIC Dc; Class I, Division 2, Groups A, B, C, D / Class II, III, Division 2, Groups F, G
  • CCC Ex: Certified under GB/T 3836 series by SITIIAS
  • Type Rating (NEMA 250): Type 4X in closed enclosures (with stainless steel hardware)

Hazardous Location Special Conditions

  1. Enclosure Requirements: For gas protection 'ec', house the device in an enclosure providing at least IP54 per EN/IEC 60079-0 and EN/IEC 60079-7. For dust protection 'tc', house in an enclosure providing at least IP6X per EN/IEC 60079-31.
  2. Transient Voltage Protection: Set external transient voltage protection not to exceed 140% of the nominal peak supply voltage.
  3. De-energised Operation: In an active explosive atmosphere, plug-in terminal connectors for 24 V power, SIA safety contacts, and digital inputs must only be connected or disconnected when completely de-energised.
  4. HotSwap Restriction in Hazardous Areas: Using the pneumatic HotSwap feature is prohibited while an explosive atmosphere is present. Valve replacement under pressure is permitted only when the local atmosphere is verified to be non-hazardous.
  5. Operating Temperature Class: Temperature class T4 is maintained at maximum internal cabinet ambient temperatures up to +55 °C. The outer surface temperature of the AirLINE Quick plate must not exceed +80 °C.

Replacement Valves and Accessories ​

Replacement Pilot Valves (Type 6534 Series) ​

Individual pilot valve slices (width 11 mm, nominal diameter 4 mm, 24 V DC) for Type 8652 valve islands:

FunctionCircuit TypeFlow $Q_{Nn}$Pressure RangeOpening TimeClosing TimeArticle No. (incl. screws)
CF CSingle 3/2-way NC270 l/minVac to 10 bar15 ms15 ms20102334
CF C (2×)2× 3/2-way NC270 l/minVac to 10 bar15 ms15 ms301374
CF D (2×)2× 3/2-way NO310 l/minVac to 10 bar15 ms15 ms301375
CF H5/2-way monostable290 l/minVac to 10 bar20 ms25 ms301376
CF Z5/2-way impulse290 l/minVac to 10 bar20 ms25 ms301377
CF L5/3-way closed275 l/minVac to 10 bar15 ms15 ms301380
CF M5/3-way ventilated300 l/minVac to 10 bar20 ms20 ms301379
CF N5/3-way exhausted300 l/minVac to 10 bar20 ms20 ms301381
—Dummy / blanking plate————335779

Connection Plugs and AirLINE Quick Accessories ​

Item DescriptionQuantityArticle No.
5-pin spring-loaded terminal (communication & display power supply)1 piece920180
2-pin spring-loaded terminal (valve coil power supply)1 piece920442
Fastening screw set M5×10 A2 DIN 6912 (cabinet floor fixing)10 pieces308661
Height adapter for 24-fold base (with intermediate feed)1 piece754964
Height adapter for 24-fold base (without intermediate feed)1 piece60041932
Retaining plate for 24-fold base (with intermediate feed)1 piece60005570
Retaining plate for 24-fold base (without intermediate feed)1 piece60005882
Blind cover plate for 24-fold base (with intermediate feed)1 piece754969
Blind cover plate for 24-fold base (without intermediate feed)1 piece60041933

Software and Configuration Tools ​

Bürkert Communicator Type 8920 connects to the Type 8652 via the USB büS interface set. It enables complete configuration, diagnostics, and parameter backup/restore over EDIP:

  • USB büS Interface Set 1 (Type 8923): Article no. 772426 (cables, büS stick with terminating resistor, power supply, Communicator software)
  • USB büS Interface Set 2 (Type 8923): Article no. 772551
  • 120 Ω M12 Terminating Resistor Plug: Article no. 772424
  • 120 Ω M12 Terminating Resistor Socket: Article no. 772425
  • Direct Plug Terminating Resistor (büS/CANopen): Article no. 303833
  • Type 1573 Power Supply (24 V DC / 1.25 A, NEC Class 2): Article no. 772438