DN 80 Flange10 kN Actuator (AG3)PEEK Seat SealProcess ControllerSAFEPOS Energy-PackbüS / CANopenIP65/IP67

BURKERT 20108885 Type 3361 Electromotive 2-Way Globe Control Valve DN 80 Flange

Burkert 20108885 Type 3361 is an electromotive 2-way globe control valve with DN 80 flange, AG3 10 kN actuator, PEEK seat seal, integrated PID process controller, display, and SAFEPOS fail-safe pack.

BURKERT 20108885 Type 3361 Electromotive 2-Way Globe Control Valve DN 80 Flange

BURKERT 20108885 (Type 3361) is an electromotive 2-way globe control valve engineered for continuous modulating control in demanding industrial and hygienic process environments. Configured with a DN 80 flanged stainless steel body (DIN EN 1092-1 PN 25), the valve combines an AG3 linear electromotive actuator delivering 10,000 N of driving force with an exchangeable PEEK seat seal. The brushless DC motor and ball screw system provide dynamic positioning at 3 mm/s with a positioning dead band of ±0.1%, remaining immune to process pressure fluctuations without line hunting. Fluid flow enters below the valve seat, providing smooth control characteristics and tight shut-off conforming to DIN EN 60534-4 Class VI up to 17 bar(g).

Article 20108885 integrates an onboard PID process controller and a display module with operating keys, allowing direct closed-loop control of external sensor variables such as pressure, temperature, level, or flow. Power failure protection is provided by the factory-installed SAFEPOS energy-pack storage module, which automatically drives the control cone to a defined safety position (normally closed delivery state). The drive and valve body share an enclosed, weather- and vibration-resistant stainless steel and powder-coated aluminium construction rated to IP65/IP67 and NEMA 4X, certified for food contact compliance under Regulation (EC) 1935/2004 and tested for detergent resistance per Ecolab standards.

Product Assembly and Mechanical Design ​

The Type 3361 AG3 assembly integrates an electric drive module, mechanical gear transmission, and valve trim into an enclosed housing. Force generated by the brushless DC motor is transferred through a precision ball screw to the valve spindle, ensuring reproducible stem positioning under maximum line pressures.

BURKERT 20108885 Type 3361 AG3 electromotive globe control valve construction diagram

Construction Materials ​

Item / ComponentMaterial Description
Display housing / coverPPS (polyphenylene sulfide)
Actuator coverPC (polycarbonate)
Actuator housingPowder-coated aluminium
Actuator baseStainless steel 1.4308
SAFEPOS energy-pack housingPC (polycarbonate)
Housing and base sealsEPDM
Valve bodyStainless steel CF3M
Valve spindleStainless steel 1.4401 (316) / 1.4404 (316L)
Spindle guideStainless steel 1.4404 (316L)
Packing gland tubeStainless steel 1.4401 (316)
Spindle sealPTFE V-seals (filled) with spring compensation
Body sealGraphite or PTFE
Control coneStainless steel 1.4571
Valve seatStainless steel 1.4571 (screwed-in, exchangeable)
Seat seal washerPEEK (Polyetheretherketone)
Seat O-ringEPDM or PTFE

Fluidic Performance and Flow Characteristics ​

The control cone provides an equal percentage flow characteristic according to DIN EN 60534-2-4 with a theoretical rangeability of 50:1. The screwed-in seat design permits seat replacement or reduction to adapt to evolving process flow rates.

Flow Data for Flow Below Seat (DN 80, Seat Size 80) ​

Specification ParameterTechnical Value
Nominal port connectionDN 80 (NPS 3)
Seat size80 mm
Actuator driving force10,000 N (AG3)
Maximum operating pressure (PEEK seal)17 bar(g) (leakage Class VI)
Maximum operating pressure (PED 97/23/EC Group 1 gases)12.5 bar(g)
Theoretical rangeability50:1
Nominal flow coefficient (Kvs)100 m³/h
Flow coefficient (Cv)115.6 gal/min
Typical closing time12.0 s (12,000 ms)

Intermediate Kv Values Across Stroke (Water measurement per DIN EN 60534-2-4) ​

Stroke (%)5%10%20%30%40%50%60%70%80%90%100%
Kv (m³/h)2.12.64.27.010.516.025.040.060.083.0100.0

PEEK Seat Sealing Limits

Soft-sealing PEEK seat washers provide tight shut-off (Class VI) over a medium temperature range from -10 °C up to +185 °C on article 20108885. This construction prevents internal seat leakage and eliminates the requirement for a separate upstream isolation valve in standard liquid and steam installations.

Dimensions and Flange Specifications ​

Dimensions below detail the Type 3361 AG3 linear actuator mounted on a DN 80 flanged body.

BURKERT 20108885 Type 3361 AG3 actuator dimension drawing

Actuator Height (AG3) ​

Nominal Diameter DNNPSH1 Standard Height (mm)H2 Fieldbus Gateway Height (mm)
401 ½560632
502566638
652 ½620692
803628700
1004638710

Note: Dimensions exclude tight sealing stroke function. In the fully closed position, the actuator spindle elevates by approximately 2 mm.

BURKERT 20108885 Type 3361 flanged valve body dimensional drawing

Flange Dimensions per DIN EN 1092-1 PN 25 (Face-to-Face FTF 1 per DIN EN 558-1) ​

DNFlange ∅ DF (mm)Length LF (mm)Bolt Circle ∅ BF (mm)Flange Thick. AF (mm)Hole ∅ D (mm)Holes A × αInside ∅ MF (mm)
10901306016144 × 90°13.6
15951306516144 × 90°18.1
201051507518144 × 90°23.7
251151608518144 × 90°29.7
3214018010018184 × 90°38.4
4015020011018184 × 90°44.3
5016523012520184 × 90°56.3
6518529014522188 × 45°66.0
8020031016024188 × 45°81.0
10023535019024228 × 45°100.0

ANSI B16.5 Class 150 Reference Dimensions (Face-to-Face FTF 37 per DIN EN 558-2) ​

NPSFlange ∅ DF (mm)Length LF (mm)Bolt Circle ∅ BF (mm)Flange Thick. AF (mm)Hole ∅ D (mm)Holes A × αInside ∅ MF (mm)
3"190298152.523.919.14 × 90°78.0

Electrical Connections and Pin Assignment ​

Article 20108885 is wired via M12 circular multipole connectors situated on the actuator body. For the AG3 platform with process controller function, four dedicated connectors are implemented.

Connector Overview for AG3 Process Controller Configuration ​

Connector DesignationConnector TypeCodingDescription
X4M12 circular plug, 5-pinL-codedActuator supply voltage (24 V DC)
X1M12 circular plug, 8-pinA-codedDigital/analogue control inputs and outputs
X2M12 circular socket, 5-pinA-codedProcess actual value sensor input
X3M12 circular plug, 5-pinA-codedbüS / CANopen communication interface

X4 Power Supply Pin Assignment (M12, 5-Pin, L-Coded) ​

PinSignal Assignment
1Operating voltage +24 V DC (±10%, max ripple 10%)
2Do not connect
3GND (power supply ground)
4Do not connect
FEFunctional earth (connected to metallic housing)

X1 Control Inputs/Outputs Pin Assignment (M12, 8-Pin, A-Coded) ​

PinSignal Assignment
1Digital input + (0-5 V = log "0", 10-30 V = log "1")
2GND for digital input and digital outputs
3Digital output 2 + (PNP, max 100 mA)
4Digital output 1 + (PNP, max 100 mA)
5Analogue output -
6Analogue output + (0/4-20 mA or 0-5/10 V)
7Setpoint value / Analogue input -
8Setpoint value / Analogue input + (0/4-20 mA or 0-5/10 V)

X2 Process Actual Value Input Pin Assignment (M12, 5-Pin, A-Coded) ​

PinAssignment for 4 to 20 mA Signal (External Sensor Supply)
1Do not connect
2Do not connect
3Do not connect
4Process actual value input (4..20 mA, input impedance 70-80 Ω, 12 bit)
5Process actual value GND

Note: Terminal X2 also accepts frequency inputs (up to 1,000 Hz, >30 kΩ) or Pt100 RTD sensor inputs (-20 °C to +220 °C) through parameter selection.

X3 büS / CANopen Pin Assignment (M12, 5-Pin, A-Coded) ​

PinSignal Assignment
1CAN Shield / functional shield
2Operating voltage 24 V DC ±10%
3GND / CAN_GND
4CAN_H
5CAN_L

Process Controller Operation and Software Configuration ​

Article 20108885 features an integrated PID process controller. The valve drive computes the required valve position autonomously by comparing the process setpoint (supplied via büS or analogue input) with the measured process actual value connected to port X2.

BURKERT 20108885 Type 3361 integrated process controller block diagram

Operating Features ​

  • Display Module: Equipped with a multi-line backlit digital screen and capacitive touch keys for parameter configuration, process value monitoring, and manual valve positioning.
  • 360° LED Light Ring: Integrated into the housing cover to display operational status, limit positions, warnings, and device diagnostics in accordance with NAMUR NE 107 recommendations.
  • Mechanical Position Indicator: A yellow indicator visible through the transparent window shows physical stroke position even in a de-energized state.
  • SAFEPOS Energy-Pack: Onboard capacitive energy storage moves the actuator to the configured safety position upon loss of mains power. Recharging completes within 120 seconds of power restoration.
  • Bürkert Communicator: Parameterization, diagnostic recording, and firmware management can be carried out using PC software connected via the büS service adapter.

Operating Limits and Derating ​

Operating pressures and ambient temperatures are interrelated and subject to standard pressure-temperature boundaries.

BURKERT 20108885 Type 3361 AG3 ambient and medium temperature operating limits

Temperature Limits Curve Identification (AG3) ​

  1. Devices without additional modules (curve 1).
  2. Devices fitted with SAFEPOS energy-pack (curve 2).
  3. Devices equipped with display module, with or without SAFEPOS energy-pack (curve 3).
  4. Devices fitted with fieldbus gateway, with or without display module or SAFEPOS energy-pack (curve 4).

When medium temperatures approach the maximum limit of +185 °C, maximum allowable ambient temperature derates to avoid overheating internal electronic assemblies. At minimum operating temperature (-25 °C), heating elements draw an additional 6 A on AG3 actuators.

Mechanical Override, Maintenance, and Calibration ​

Routine maintenance of the valve body and drive must be performed by qualified personnel using authorized procedures and specified tools.

Mechanical Manual Override Torque Limit

The mechanical manual override is located beneath the pressure compensation element on AG3 actuators and is actuated using a 3 mm Allen key. Maximum tightening torque is 2 Nm. Exceeding 2 Nm upon reaching the stroke end position will cause mechanical damage to the drive. Use the manual override only when the supply voltage is disconnected.

Calibration Under Pressure Prohibited

Do not execute the X.TUNE calibration function while medium pressure is present in the pipeline. Medium pressure induces incorrect controller adaptation, resulting in severe process instability and loss of calibration accuracy.

Body Connection Tightening Torques ​

When reassembling the actuator onto the flanged body, always fit a new graphite body seal and apply Klüberpaste UH1 96-402 to the body connection thread.

Valve Body Connection SizeOrifice DNTightening Torque (Nm)Tightening Torque (lbf ft)
DN 10 / 1510 / 1545 ± 333 ± 2
DN 202050 ± 337 ± 2
DN 252560 ± 344 ± 2
DN 32 / DN 4032 / 4065 ± 348 ± 2
DN 505070 ± 352 ± 2
DN 6565100 ± 374 ± 2
DN 8080120 ± 589 ± 2
DN 100100150 ± 5111 ± 2

Accessories and Spare Parts ​

Accessory / Spare Part DescriptionArticle Number
SAFEPOS energy-pack wearing part (AG3 replacement module)20046438
SIM card for device parameter backup and transfer291773
Plastic blind cover277881
Valve seat installation tool for Type 3361 DN 80655563
M12 cable socket, 5-pin, L-coded, 5 m (for X4 operating voltage AG3)20010840
M12 cable socket, 8-pin, A-coded, 2 m (for X1 input/output signals)919061
M12 cable plug shielded, 5-pin, A-coded, 2 m (for X2 process actual value)559177
USB-büS interface set 1 (Type 8923 with power supply, stick, load resistor, cable)772426
USB-büS interface set 2 (Type 8923 with stick, load resistor, cable)772551
büS adapter cable for büS service interface (M12 to micro-USB, 0.3 m)774931
Bürkert Communicator configuration softwareType 8920