Skip to content
12-BankIndustrial EthernetAirLINE QuickHotSwap

BURKERT 20110864 Type 8652 Valve Island, 12-Bank, Industrial Ethernet

Burkert Type 8652 (20110864) 12-bank valve island with AirLINE Quick aluminium adapter. Features Industrial Ethernet, -1 to 10 bar pressure, and IP20 protection.

BURKERT 20110864 Type 8652 Valve Island, 12-Bank, Industrial Ethernet

Burkert Type 8652 (Article No. 20110864) is a 12-bank AirLINE valve island optimised for process automation. This specific configuration features an AirLINE Quick aluminium adapter plate, brass D10 pressure ports, and brass D6 working ports. It supports Industrial Ethernet protocols (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) and operates within a pressure range of -1 to 10 bar and temperatures from -10 °C to 55 °C. The system includes integrated check valves in the exhaust air ducts to prevent unplanned actuation from pressure peaks, and supports pneumatic HotSwap functionality.

Burkert 20110864 Type 8652 valve island overview

Valve Island Configuration (Article 20110864)

This specific model is pre-configured with the following setup:

PositionConfiguration
Valve positions 1-82x 3/2-way WWC (Circuit function C)
Valve positions 9-12Blind plate
Pressure portD10 (Brass)
Working portD6 (Brass)
AirLINE Quick materialAluminium
Auxiliary pilot airInternal
Additional supply right/leftPush-in connector D6 and D10

General Technical Data

PropertyValue
Body materialPA (polyamide)
Seal materialNBR and PUR
Width per station11 mm
Nominal operating modeContinuous operation (100 % duty cycle)
Operating voltage24 V DC (±10% tolerance)
Nominal power of each valve0.7 W (0.175 W after power reduction)
Nominal current of each valve29 mA (10 mA after power reduction)
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Degree of protectionIP20 (IP65 in closed control cabinets)

AirLINE Quick Adapter

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Burkert 20110864 AirLINE Quick adapter plate

Advantages

  • Reduced space requirement in the control cabinet, making it possible to use more compact enclosures.
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet.

Approvals and Conformities

  • Explosion protection: As a category 3 device suitable for zone 2/22. ATEX: II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc. IECEx: Ex ec IIC Gc / Ex tc IIIC Dc.
  • North America (USA/Canada): UL Listed (UL 61010-1, CAN/CSA-C22.2 No. 61010-1). UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Div 2).
  • China Compulsory Certification (CCC): Suitable for import and use for hazardous applications in China.

Dimensions

The following dimensions apply to the 12-fold variant:

Burkert 20110864 dimensions for 12-fold variant

VariantABCmn
12-fold77 mm154 mm10 x M5113

Fieldbus Interface

This model is equipped with an Industrial Ethernet interface (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) via X1 and X2 RJ45 ports.

Burkert 20110864 Industrial Ethernet RJ45 pinout

PinAssignment
1TX+
2TX-
3RX+
6RX-
4, 5, 7, 8N.C.

Safety Instructions for EX Areas

  • Danger from voltage: Before working on the device or system, disconnect the power supply and secure against reactivation.
  • Hot Swap restriction: The use of the Hot Swap function is prohibited in a present explosive atmosphere. It is only permitted if the absence of an explosive atmosphere can be proven and ensured for a certain period of time using suitable test equipment.
  • Electrostatic charge: Sudden discharge of electrostatically charged devices or persons can cause an explosion. Take appropriate measures to ensure that no electrostatic charges can occur in the potentially explosive area.