Burkert 20111050 (Type 8652 AirLINE) 16-slot pneumatic valve island features stainless steel AirLINE Quick plate, Industrial Ethernet RJ45, 13 standard and 3 SIA safety 2x3/2-way valves.

BURKERT 20111050 (Type 8652 AirLINE) is a 16-slot modular pneumatic valve island configured with a stainless steel AirLINE Quick baseplate for direct mounting to control cabinet floors or walls. Designed specifically for process automation environments, the unit is fitted with 13 standard valve slots each carrying two 3/2-way servo-assisted normally closed solenoid valves (Circuit Function C), and three dedicated safety shut-off slots (slots 14, 15, and 16) carrying 2x 3/2-way Circuit Function C SIA valves. All pneumatic pilot functions are powered through an internal auxiliary pilot air supply operating between 3 bar and 10 bar, controlling process operating pressures from vacuum up to 10 bar (-1.00 bar to 10.00 bar).
The assembly includes one central intermediate supply and exhaust module to ensure uniform pneumatic distribution across all 16 stations. Process connections are executed entirely in stainless steel, featuring push-in D10 connectors for primary air supply and exhaust, alongside push-in D6 connectors for working ports 2 and 4. Electrical communication is handled by an integrated Industrial Ethernet interface supporting PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic over dual RJ45 ports. Integrated process reliability features include pneumatic HotSwap non-return valves in channel 1 (P) to enable valve replacement under operational line pressure, and integrated check valves in exhaust ducts 3 (R) and 5 (S) to prevent unwanted actuator movement caused by backpressure spikes.
| Specification Parameter | Value / Technical Rating |
|---|---|
| Article Number | 20111050 |
| Device Type Family | 8652 AirLINE |
| Base Configuration | 16 valve slots (accommodating up to 32 valve functions) |
| Slot Loading 1 to 13 | 13× 2× 3/2-way CF-C (normally closed, manual override) |
| Slot Loading 14 to 16 | 3× 2× 3/2-way CF-C SIA (safety shut-off variant) |
| Baseplate Interface | AirLINE Quick stainless steel 1.4301 adapter plate |
| Pneumatic Port Materials | Stainless steel 1.4401 push-in cartridges |
| Supply Port Connection | D10 push-in (internal auxiliary pilot feed) |
| Working Port Connections | D6 push-in (ports 2 and 4) |
| Intermediate Feed Unit | 1 PCE (factory-integrated intermediate supply/exhaust module) |
| Operating Pressure Range | -1.00 bar to 10.00 bar (vacuum to 10 bar overpressure) |
| Auxiliary Pilot Air Pressure | 3.00 bar to 10.00 bar (internal pilot air supply) |
| Standard Air Flow Rate QNn | 310 l/min (at +20 °C, 6 bar inlet, 1 bar differential pressure) |
| Flow Rate with HotSwap | Flow reduced by approx. 3% through integrated non-return seat |
| Nominal Operating Mode | Continuous operation (100% duty cycle ED) |
| Nominal Supply Voltage | 24 V DC (±10% tolerance, residual ripple ≤ 1 Vss) |
| Power per Valve Station | 0.7 W nominal inrush (0.175 W after electronic power reduction) |
| Current per Valve Station | 29 mA nominal inrush (10 mA after electronic power reduction) |
| Housing & Seal Materials | Polyamide (PA) housing; NBR and PUR elastomer seals |
| Station Width | 11 mm per valve slot |
| Digital Inputs | 0 (no electronic DI input modules installed) |
| Exhaust Check Valves | Integrated check valves in ducts 3 (R) and 5 (S) |
| Supply HotSwap Protection | Integrated pneumatic check valve in channel 1 (P) |
| Fieldbus Communication | Industrial Ethernet: PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic |
| Physical Hardware Bus Port | 2× RJ45 female sockets (switched interface X1 / X2) |
| Media Compatibility | Oil-free or lubricated dry compressed air, neutral gases (ISO 8573-1:2010 Class 7.4.4; 5 μm filtration recommended) |
| Ambient & Medium Temperature | -10 °C to +55 °C |
| Storage Temperature | -20 °C to +60 °C |
| Ingress Protection Rating | IP20 unhoused; IP65 / NEMA Type 4X when mounted through cabinet wall with AirLINE Quick stainless steel plate |
| Electrical Protection Class | Class III according to DIN EN 61140, VDE 0140 |

The AirLINE Quick adapter plate integrates the pneumatic connections directly into the cut-out floor or side wall of the control cabinet. For article 20111050, the adapter plate is manufactured from 1.4301 stainless steel and equipped with 1.4401 stainless steel push-in fittings, delivering chemical resistance and physical strength for hygienic and aggressive process areas.
Direct cabinet-floor mounting eliminates internal tubing runs from the valve terminals to bulkheads on the cabinet exterior, reducing internal cabinet volume requirements and installation labour. When installed with its surrounding seal in a closed control cabinet, the assembly establishes ingress protection compliant with IP65 and NEMA 250 Type 4X.
| Component | Material / Specification |
|---|---|
| AirLINE Quick Adapter Plate | Stainless steel 1.4301 (V2A) |
| Pneumatic Push-In Cartridges | Stainless steel 1.4401 (V4A) |
| Pneumatic Supply / Exhaust Ports | Push-in D10 mm (for primary supply line 1 and exhaust lines 3/5) |
| Pneumatic Working Ports | Push-in D6 mm (ports 2 and 4 for 16 valve stations) |
| Cabinet Mounting Location | Control cabinet floor or control cabinet side wall |
Article 20111050 carries 16 pneumatic stations populated by pilot-operated sliding spool valves belonging to the Type 6534 family:
| Circuit Function Code | Valve Type & Operation | Pneumatic Flow Scheme |
|---|---|---|
| CF C (Slots 1–13) | 2× 3/2-way solenoid valve, servo-controlled, normally closed with manual override | Pressure applied via port 1; energised coils open working ports 2 and 4; unpowered state exhausts via 3 and 5 |
| CF C SIA (Slots 14–16) | 2× 3/2-way solenoid valve, servo-controlled, normally closed, safety shut-off variant | Independent coil circuit with dedicated 2-wire shutdown loop; unpowered or interrupted loop maintains closed state |
| CF D (Reference) | 2× 3/2-way solenoid valve, servo-controlled, normally open with manual override | Working ports pressurised when de-energised; closed upon electrical actuation |
| CF H (Reference) | 5/2-way solenoid valve, servo-controlled, single coil | Alternates pressure between port 2 and port 4 via port 1 |
| CF Z (Reference) | 5/2-way bistable impulse solenoid valve, 2 coils | Bistable switching maintained by impulse commands |
| CF L (Reference) | 5/3-way solenoid valve, middle position closed | All ports blocked in de-energised middle position |
| CF M (Reference) | 5/3-way solenoid valve, middle position pressurised | Ports 2 and 4 connected to supply in middle position |
| CF N (Reference) | 5/3-way solenoid valve, middle position exhausted | Ports 2 and 4 vented to exhaust in middle position |

Article 20111050 incorporates an intermediate supply module between its valve stations. The precise dimensions must be followed during mechanical planning and cabinet sheet-metal cutouts:
| Mechanical Dimension Key | Dimension (mm) | Description / Notes |
|---|---|---|
| Dimension A | 112 mm | Spacing from left edge to intermediate feed module centreline |
| Dimension B | 224 mm | Total mounting pitch between lateral mounting points |
| Fastening Hole Pattern C | 10× M5 | Screws M5×10 A2 DIN 6912 for baseplate clamping |
| Intermediate Supply Offset D | 114.3 mm | Centerline position of central air feed module |
| Left Slot Array Pitch m | 7 | Number of valve stations situated to the left of the central feed |
| Right Slot Array Pitch m' | 7 | Number of valve stations situated to the right of the central feed |
| Sub-base Partition Index n | 4 | Number of 4-slot modular pneumatic sub-base segments |
| Valve Width per Station | 11 mm | Width of individual Type 6534 valve slice |

Installation Clearance for HotSwap
When positioning the valve terminal within a control cabinet, maintain sufficient clearance between the front edge of the valve modules and the cabinet door/frame. A clearance of at least 60 mm is required in front of the valve latches to allow manual release and withdrawal of individual Type 6534 valve slices during live hot swapping.

The Type 8652 terminal separates logic power supply, valve actuator power, and fieldbus communication across distinct terminal blocks.
Power for the internal electronics, LC display, and internal büS communication is supplied via a 5-pin spring-clamp terminal block accepting conductor cross-sections up to 1.5 mm²:
| Pin Position | Terminal Colour Marking | Function Assignment |
|---|---|---|
| Pin 1 | Red | +24 V DC (Logic and display electronics) |
| Pin 2 | White | CAN_H (büS service interface) |
| Pin 3 | Green | Functional Earth / Cable Shield |
| Pin 4 | Blue | CAN_L (büS service interface) |
| Pin 5 | Black | 0 V DC (GND) |
To allow emergency de-energisation of actuators without losing bus communication or diagnostics, pneumatic solenoid valves are fed separately through an AUX 24 V terminal:
| Clip Position | Terminal Wire Colour | Function Assignment |
|---|---|---|
| Terminal 1 | Red | AUX +24 V DC (Valve solenoid driver power) |
| Terminal 2 | Black | 0 V DC (GND) |

The terminal includes an integrated Ethernet switch with two RJ45 ports (X1 and X2), supporting line and ring topologies across PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic:
| RJ45 Pin | Industrial Ethernet Signal | Notes |
|---|---|---|
| Pin 1 | TX+ | Transmit Data Positive |
| Pin 2 | TX- | Transmit Data Negative |
| Pin 3 | RX+ | Receive Data Positive |
| Pin 4 | N.C. | Not connected |
| Pin 5 | N.C. | Not connected |
| Pin 6 | RX- | Receive Data Negative |
| Pin 7 | N.C. | Not connected |
| Pin 8 | N.C. | Not connected |

Valve slots 14, 15, and 16 on article 20111050 are equipped with Type 6534 SIA variants for safety shut-off. Unlike standard valves driven solely by the internal electronics, each SIA station incorporates independent, external wiring terminals that interrupt coil power directly:

Module-Based vs. Valve-Specific SIA
Article 20111050 implements valve-specific SIA directly on stations 14–16. In applications requiring broader zone control, Bürkert also provides module-based SIA interface boards with 12-pin spring terminals (switching capacity 1.5 A / 24 V DC) that isolate power across entire valve groups simultaneously.

Article 20111050 can operate as an Industrial Ethernet master island within a decentralized control architecture. Through its büS extension port, additional AirLINE 8652 slave islands can be connected in line, allowing multiple valve blocks to share a single Ethernet IP address and bus drop.
Configuration, diagnosis, and parameter settings are conducted using the Bürkert Communicator Type 8920 software running on the Efficient Device Integration Platform (EDIP):

Type 8652 valve islands carry certifications for installation in hazardous locations when properly housed inside certified control cabinets:
| Standard / Certification | Protection Classification & Marking | Certificate Number |
|---|---|---|
| ATEX (Europe) | II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc | BVS 20 ATEX E 031 U |
| IECEx (International) | Ex ec IIC Gc / Ex tc IIIC Dc | IECEx BVS 20.0024 U |
| cURus HazLoc (USA / Canada) | Class I, Zone 2, AEx ec IIC Gc / Class II, Zone 22, AEx tc IIIC Dc; Class I Div 2 Gr A, B, C, D / Class II, III Div 2 Gr F, G | UL Recognized E-file |
| CCC (China) | Ex ec IIC Gc / Ex tc IIIC Dc (GB/T 3836) | CCC Certificate |
Hazardous Area Safety Restrictions
Replacement valve slices for the Type 8652 valve island must be selected according to their designated circuit function. Each replacement unit includes mounting screws:
| Circuit Function | Width | Flow QNn | Pressure Range | Response Open / Close | Article No. (Valve Only) | Article No. (Spare Set) |
|---|---|---|---|---|---|---|
| CF C (2× 3/2 NC, manual override) | 11 mm | 270 l/min | Vac. to 10 bar | 15 ms / 15 ms | 20102334 | 20088974 |
| CF C SIA (2× 3/2 NC, safety shut-off) | 11 mm | 270 l/min | Vac. to 10 bar | 15 ms / 15 ms | 20102335 | 20092052 |
| CF D (2× 3/2 NO, manual override) | 11 mm | 310 l/min | Vac. to 10 bar | 15 ms / 15 ms | 301375 | 296032 |
| CF H (5/2-way, single coil) | 11 mm | 290 l/min | Vac. to 10 bar | 20 ms / 25 ms | 301376 | 296033 |
| CF H SIA (5/2-way, safety shut-off) | 11 mm | 290 l/min | Vac. to 10 bar | 20 ms / 25 ms | 338805 | 336444 |
| CF Z (5/2-way impulse, 2 coils) | 11 mm | 290 l/min | Vac. to 10 bar | 20 ms / 25 ms | 301377 | 296034 |
| CF L (5/3-way, middle position closed) | 11 mm | 275 l/min | Vac. to 10 bar | 15 ms / 15 ms | 301380 | 296036 |
| CF L SIA (5/3-way, middle closed SIA) | 11 mm | 275 l/min | Vac. to 10 bar | 15 ms / 15 ms | 346830 | 336523 |
| CF M (5/3-way, middle pressurised) | 11 mm | 300 l/min | Vac. to 10 bar | 20 ms / 20 ms | 301379 | 296035 |
| CF N (5/3-way, middle exhausted) | 11 mm | 300 l/min | Vac. to 10 bar | 20 ms / 20 ms | 301381 | 296039 |
| Dummy Valve Plate | 11 mm | — | — | — | 335779 | 327614 |
| Accessory Description | Quantity / Scope | Article No. |
|---|---|---|
| Screw Set M5×10 A2 DIN 6912 (Cabinet base clamping) | Set of 10 screws | 308661 |
| Height Adapter (16-slot with intermediate supply) | 1 piece | 754962 |
| Retaining Plate (16-slot with intermediate supply, cabinet exterior) | 1 piece | 60005568 |
| Blanking Blind Plate (16-slot with intermediate supply) | 1 piece | 754967 |
| 5-Pin Spring Terminal Plug (Logic and display power) | 1 piece | 920180 |
| 2-Pin Spring Terminal Plug (Pneumatic valve power AUX 24V) | 1 piece | 920442 |
| USB büS Interface Set 1 (for Type 8920 Communicator PC connection) | Complete set with stick and cables | 772426 |