BURKERT Type 8652 AirLINE valve island optimised for process automation. Features LC display diagnostics, PROFINET S2, Hot Swap, and ATEX/IECEx Zone 2 approvals.

BURKERT Type 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, though installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that prevent unplanned actuation due to pressure peaks.
| Product properties | |
|---|---|
| Body Material | PA (polyamide) |
| Seal Material | NBR and PUR |
| Width per station | 11 mm |
| Manual override | Latching, spring return (optional: lockable) |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Pneumatic intermediate supply | Optional for the variants with 16, 20 and 24 valve slots |
| Pressure range | Vac...10 bar |
| External supply air | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Flow rate with Hot Swap | Flow reduced by approx. 3% |
| Operating voltage | 24 V DC (±10% tolerance) |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Digital input | Max. 48 |
| Protection class | III according to DIN EN 61140, VDE 0140 |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Degree of protection | IP20, IP65 in closed control cabinets |
| Ambient temperature | -10 °C...+55 °C |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages:
| Product properties | |
|---|---|
| Adapter Plate Material | Stainless steel 1.4301 or Anodised aluminium |
| Pneumatic connection Material | Stainless steel 1.4401 or Nickel-plated brass |
| Valve functions per station | 8, 16, 24, 32, 40 and 48 |
| Pneumatic Supply / Exhaust | Push-in D 10 mm, 3/8" |
| Pneumatic working ports | Push-in D 6 mm, 1/4" |

| Circuit function | Description |
|---|---|
| C (CF C) | 3/2-way solenoid valve, servo-controlled, with manual override, normally closed |
| C (CF C) | 2 × 3/2-way solenoid valve, servo-controlled, with manual override, normally closed |
| D (CF D) | 2 × 3/2-way solenoid valve, servo-controlled, with manual override, normally open |
| H (CF H) | 5/2-way solenoid valve, servo-controlled, with manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
| L (CF L) | 5/3-way solenoid valve, with manual override. In middle position all ports locked |
| M (CF M) | 5/3-way solenoid valve, servo-controlled, with manual override. In middle position ports 2 and 4 ventilated |
| N (CF N) | 5/3-way solenoid valve, with manual override. In middle position ports 2 and 4 exhausted |
| Z (CF Z) | 5/2-way solenoid valve, impulse variant with 2 coils and manual override. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
| Circuit function | Description |
|---|---|
| C (CF C) | 3/2-way solenoid valve, servo-controlled, normally closed |
| C (CF C) | 2 × 3/2-way solenoid valve, servo-controlled, normally closed |
| H (CF H) | 5/2-way solenoid valve, servo-controlled. Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
| L (CF L) | 5/3-way solenoid valve, servo-controlled. In middle position all ports locked |

| Variant | A | B | C | m | n |
|---|---|---|---|---|---|
| 4-fold | 66 | - | 4 x M5 | 3 | 1 |
| 8-fold | 35 | 111 | 8 x M5 | 7 | 2 |
| 12-fold | 77 | 154 | 10 x M5 | 11 | 3 |

| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply | 112 | 224 | 10 x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10 x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10 x M5 | 158.3 | 11 | 11 | 6 |
| 16-fold without intermediate supply | 99 | 198 | 10 x M5 | - | 15 | - | 4 |
| 20-fold without intermediate supply | 121 | 242 | 10 x M5 | - | 19 | - | 5 |
| 24-fold without intermediate supply | 143 | 286 | 10 x M5 | - | 23 | - | 6 |
Supports Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) or PROFINET S2 via RJ45 interfaces, as well as PROFIBUS DP and CANopen/büS.
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.


The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.
Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).
Optional connections for module-based safety shutdown (Terminal 1 = valve unit 1, Terminal 2 = valve unit 2, etc.). Connect the connection to a potential-free contact (mechanical switch or relay).
The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

Bürkert Communicator Software: The Bürkert Communicator is the most important software component of the EDIP (Efficient Device Integration Platform). It simplifies the configuration and parametrisation of devices equipped with a digital CANopen-based interface, providing a complete overview of cyclic process values and acyclic diagnostic data.
WARNING
Danger from voltage:
Danger of explosion due to electrostatic charge:
INFO
Special conditions for Ex use:
Explore similar products in our catalog