Skip to content
12 Valve SlotsPROFIBUS DPV1AirLINE Quick ALPneumatic HotSwapIP20 / IP65

BURKERT 20117753 Type 8652 AirLINE Valve Island, 12 Slots, PROFIBUS DPV1, AirLINE Quick AL

BURKERT 20117753 (Type 8652) 12-slot AirLINE valve island integrates 24 CF-C 3/2-way NC valve functions, PROFIBUS DPV1, AirLINE Quick aluminium adapter, check valves, and pneumatic hot swap.

BURKERT 20117753 Type 8652 AirLINE Valve Island, 12 Slots, PROFIBUS DPV1, AirLINE Quick AL

BURKERT 20117753 (Type 8652) is an AirLINE valve island engineered for process automation, configured with 12 valve stations and an anodised aluminium AirLINE Quick adapter plate. Each valve station is fitted with a 2 × 3/2-way circuit function C (CF-C) normally closed pilot valve, providing 24 independent, servo-controlled valve functions across an installation pitch of 11 mm per station. Process communication is handled through an integrated ME43 gateway variant operating PROFIBUS DPV1 via a standard Sub-D 9-pin interface.

The hardware architecture of article 20117753 is pre-configured with integrated check valves in exhaust ducts 3 (R) and 5 (S) to prevent unintended actuator movement caused by backpressure peaks. A pneumatic HotSwap function on supply port 1 (P) enables individual valve replacement under operating pressure without stopping the main pressure supply, reducing flow by only approximately 3% during servicing.

BURKERT 20117753 BURKERT Type 8652 24 V interface plate and valve assembly without modular shut-off

Technical Specifications ​

Technical ParameterSpecification Value
Article number (Ident)20117753
Valve island typeType 8652 AirLINE
Number of valve slots12 stations (12 PCE)
Valve configuration per slot2 × 3/2-way CF-C (servo-assisted, normally closed)
Width per station11 mm
Body materialPolyamide (PA)
Seal materialsNBR and PUR
AirLINE Quick adapter plateAnodised aluminium
Compressed air supply connection (Port 1/P)Push-in D10 mm (brass)
Working ports (Ports 2 and 4)Push-in D6 mm (brass)
Additional supply portsLeft and right G 1/4" and M7 threaded ports; middle: none
Auxiliary pilot airInternal feed
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 µm filter recommended)
Compressed air qualityISO 8573-1:2010, Class 7.4.4
Nominal pressure range-1.00 bar to 10.00 bar (vacuum to 10 bar)
Pilot pressure range3.00 bar to 10.00 bar
Nominal flow rate QNn (air)270 l/min (at +20 °C, 6 bar inlet pressure, 1 bar differential pressure)
Switching times (CF-C)Opening: 15 ms, Closing: 15 ms (measured to ISO 12238)
Operating voltage24 V DC (±10%, residual ripple 1 Vss)
Nominal power per valve0.7 W (0.175 W after electronic power reduction)
Nominal current per valve29 mA (10 mA after electronic power reduction)
Protection classClass III according to DIN EN 61140, VDE 0140
Degree of protectionIP20 naked / IP65 when mounted in closed control cabinet via AirLINE Quick
Ambient and medium temperature-10 °C to +55 °C
Storage temperature-20 °C to +60 °C
Rated operating modeContinuous operation (100% duty cycle)

AirLINE Quick Cabinet Floor Mounting ​

Article 20117753 uses the AirLINE Quick adapter system with an anodised aluminium baseplate. This adapter mounts directly into the floor or side wall of a control cabinet, placing pneumatic tubing connections outside the cabinet interior. This architecture eliminates internal bulkhead fittings, conserves cabinet volume, and isolates pneumatic exhaust and supply air from internal electronics.

BURKERT 20117753 BURKERT Type 8652 AirLINE Quick adapter plate in anodised aluminium

AirLINE Quick FeatureSpecification Value
Adapter plate materialAnodised aluminium (optional series material: Stainless steel 1.4301)
Pneumatic connection materialNickel-plated brass (optional series material: Stainless steel 1.4401)
Supply / exhaust connectionsPush-in D10 mm (3/8")
Working connectionsPush-in D6 mm (1/4")
Mounting locationControl cabinet floor or control cabinet wall
Ingress protectionIP65 inside closed cabinet / Type 4X with stainless steel option

Installation Clearance for HotSwap

When installing the valve terminal inside the control cabinet, observe minimum distances between the front edge of the valve block and the cabinet door, as well as the clearance from the rear cabinet wall. Adequate forward clearance ensures that individual 6534 valves can be unlatched and pulled vertically from their sub-base during pneumatic HotSwap operations while the main system remains pressurised.

Dimensions for 12-Slot Island Execution ​

The dimensional layout for the 12-slot variant defines precise drilling and cutout coordinates for cabinet base integration.

BURKERT 20117753 BURKERT Type 8652 12-valve slot dimensional diagram and mounting dimensions

Island VariantDimension A (mm)Dimension B (mm)Fastening Pattern CSlots mSegments n
4-fold66—4 × M531
8-fold351118 × M572
12-fold (20117753)7715410 × M5113

Standard EN 50022 DIN rail mounting (35 × 7.5 mm or 35 × 15 mm) is supported as an alternative mechanical mounting method when floor adapter cutouts are not implemented.

Electrical Interfaces and PROFIBUS DPV1 Pinout ​

Article 20117753 separates communication power from valve actuator coil supply to prevent fieldbus communication loss during safety-related valve cut-offs or coil voltage dips.

5-Pin Spring-Loaded Terminal (Communication and Display Power) ​

  • Conductor cross-section: ≤ 1.5 mm²
  • Pin 1 (Red): 24 V DC
  • Pin 2 (White): CAN_H (büS interface)
  • Pin 3 (Green): Shielding
  • Pin 4 (Blue): CAN_L (büS interface)
  • Pin 5 (Black): GND (0 V DC)

2-Pin Spring-Loaded Terminal (Pneumatic Valve Power Supply) ​

  • Conductor cross-section: ≤ 1.5 mm²
  • Terminal 1 (Red): AUX 24 V
  • Terminal 2 (Black): GND (0 V DC)

PROFIBUS DPV1 Fieldbus Interface (Sub-D 9-Pin Socket) ​

BURKERT 20117753 BURKERT Type 8652 PROFIBUS DPV1 D-Sub 9-pin connector pin assignment

Pin NumberAssignmentDescription
1SHIELDINGCable shielding / protective earth
2M24Optional 24 V ground reference
3RxD/TxD-PB-line (Receive / Transmit data positive)
4CNTR-PControl signal P (optional)
5DGNDData ground (0 V)
6+5 VRegulated bus termination supply voltage
7+24 VOptional 24 V positive supply
8RxD/TxD-NA-line (Receive / Transmit data negative)
9CNTR-NControl signal N (optional)

Pilot Valve Functions and Spare Parts ​

Each of the 12 stations on 20117753 incorporates two 3/2-way NC pilot valves Type 6534 (circuit function C). The valve features integrated manual overrides (latching or spring-return).

Circuit FunctionOrifice (mm)QNn Air (l/min)Pressure Range (bar)Opening Time (ms)Closing Time (ms)VoltageSpare Part Article No. (incl. screws)
CF C (2 × 3/2-way NC, fitted on 20117753)4270Vac...10 (pilot 3...10)151524 V DC301374 (REF 296031)
CF C (1 × 3/2-way NC)4270Vac...10 (pilot 3...10)151524 V DC20102334 (REF 20088974)
CF D (2 × 3/2-way NO)4310Vac...10 (pilot 3...10)151524 V DC301375 (REF 296032)
CF H (5/2-way monostable)4290Vac...10 (pilot 3...10)202524 V DC301376 (REF 296033)
CF Z (5/2-way bistable impulse)4290Vac...10 (pilot 3...10)202524 V DC301377 (REF 296034)
CF L (5/3-way mid-position closed)4275Vac...10 (pilot 3...10)151524 V DC301380 (REF 296036)
CF M (5/3-way mid-position pressurised)4300Vac...10 (pilot 3...10)202024 V DC301379 (REF 296035)
CF N (5/3-way mid-position exhausted)4300Vac...10 (pilot 3...10)202024 V DC301381 (REF 296039)
Dummy valve plate——————335779 (REF 327614)

Explosion Protection and Hazardous Area Guidelines ​

When ordered with explosion-proof options (code PX68 or PU17), Type 8652 valve islands hold certifications under ATEX certificate BVS 20 ATEX E 031 U and IECEx certificate IECEx BVS 20.0024 U:

  • ATEX Gas: II 3G Ex ec IIC Gc
  • ATEX Dust: II 3D Ex tc IIIC Dc
  • IECEx Gas/Dust: Ex ec IIC Gc / Ex tc IIIC Dc
  • North America (PU17): Class I, Zone 2, AEx ec IIC Gc / Class II, Zone 22, AEx tc IIIC Dc; Class I, Div 2, Groups A, B, C, D / Class II, III, Div 2, Groups F, G
  • China CCC: Certified according to GB/T 3836 series

Hazardous Area Operational Restrictions

  • Enclosure Protection: Install within an enclosure rated at least IP54 for gas atmospheres (type of protection "ec" according to EN/IEC 60079-7) or at least IP6X for dust atmospheres (type of protection "tc" according to EN/IEC 60079-31).
  • HotSwap Restriction: Do not disconnect or connect electrical terminals, and do not perform pneumatic HotSwap valve removal in a potentially explosive atmosphere unless the atmosphere has been proven non-explosive by authorised personnel using suitable testing equipment.
  • Transient Voltage: Ensure external surge protection limits transient peak voltages to no more than 140% of the nominal 24 V supply voltage.
  • Temperature Limit: The maximum external cabinet operating temperature must not exceed 80 °C with AirLINE Quick, and internal ambient temperature must remain between -10 °C and +55 °C.

Commissioning and System Accessories ​

Configuration and diagnostics are performed through Bürkert Communicator software Type 8920 using an EDIP (Efficient Device Integration Platform) USB-to-büS adapter set.

Accessory DescriptionOrder Article No.
Fastening screw set M5 × 10 A2 DIN 6912 (10 pcs, for cabinet base mounting)308661
Height adapter for 12-fold base (without intermediate feed)754961
Retaining plate for 12-fold base (for cabinet exterior)60005567
Blind plate for 12-fold base (without intermediate feed)754966
USB büS interface set 1 (Type 8923) for Bürkert Communicator software772426
5-pin spring-loaded terminal plug (communication and displays)920180
2-pin spring-loaded terminal plug (valve power supply)920442
Replacement fieldbus gateway ME43 PROFIBUS DP301803