BURKERT 20120869 Type 8647 AirLINE SP is a 24-bank electropneumatic valve island with 11 mm width, 24x (2x 3/2) CF C valves, G 1/4 ports, integrated pressure sensor, and Siemens SIMATIC ET 200SP integration.

BURKERT 20120869 Type 8647 AirLINE SP is a modular electropneumatic automation system engineered for direct integration into Siemens SIMATIC ET 200SP and SIMATIC ET 200SP HA distributed I/O systems. Configured as a 24-station valve block with an 11 mm station pitch, this unit incorporates 24 double pilot valves providing 48 independent 3/2-way normally closed (circuit function C) pneumatic channels. Operating across a pressure span of 2.5 bar to 10 bar, it features pneumatic HotSwap on port 1 (P), integrated non-return check valves on exhaust ducts 3 (R) and 5 (S), and an integrated electronic pressure sensor on the supply unit.
Built to Revision 2 (REV.2) manufacturing standards, the island uses a unified FM20 pneumatic flange pattern, blue push-in release rings, and an optimized internal flow architecture. The system mounts directly on a standard DIN rail inside control cabinets, providing IP20 protection individually and achieving IP65 integrity within closed enclosures.
Type 8647 consists of connection units, pneumatic base modules, electronic base modules (PQ modules), and integrated solenoid pilot valves. Supply air and deaeration occur through specialized pneumatic supply units (PSU):


The 24 valve stations are assembled from electronic PQ modules and corresponding pneumatic base modules. The pneumatic modules house the D6 push-in connectors in a wavy channel arrangement characteristic of REV.2, delivering working air downward through the module base.
| Feature | Specification Details |
|---|---|
| Article Number | 20120869 |
| System Type | Type 8647 AirLINE SP |
| Hardware Generation | Revision 2 (REV.2) |
| Number of Valve Stations | 24 stations (48 valve channels) |
| Valve Configuration | 24x Type 6524 2x 3/2-way normally closed (CF C) |
| Station Pitch | 11 mm |
| Operating Pressure Range | 2.5 bar to 10.0 bar (gauge pressure) |
| Nominal Air Flow Rate ($Q_{Nn}$) | 300 l/min (reduced by approx. 20% with integrated P-shutoff) |
| Fluid Medium | Compressed dry air (lubricated or unlubricated), neutral gases (ISO 8573-1:2010 Class 7.4.4, 5 µm filtration recommended) |
| Medium Temperature | 0 °C to +50 °C |
| Ambient Operating Temperature | 0 °C to +55 °C |
| Supply / Exhaust Ports (1/P, 3/R, 5/S) | G 1/4 female thread |
| Working Connections (2/A, 4/B) | Push-in coupling D6 mm (bottom orientation) |
| Operating Voltage | 24 V DC (±10% allowable tolerance, residual ripple 2.4 Vss) |
| Power Consumption per Double Valve | 2x 0.8 W (with electronic power reduction) |
| Nominal Current per Valve Position | 40 mA peak (28 mA holding current after 120 ms) |
| Operating Mode | 100% continuous operation (100% ED) |
| Degree of Protection | IP20 (IP65 in closed control cabinet) |
| Protection Class | Class III according to DIN EN 61140 / VDE 0140 |
| Integrated Check Valves | Factory fitted in exhaust ports 3 (R) and 5 (S) |
| Pneumatic HotSwap | Integrated P-shutoff check valve in port 1 (P) |
SKU 20120869 integrates an electronic pressure sensor within the left connection unit (PSU-L-PS). The sensor continuously tracks system line pressure across a 0 to 10 bar relative span with a precision of 0.2 bar and a measurement cycle exceeding 10 readings per second. It withstands overload pressures up to 14 bar without loss of calibration.
Diagnostic and status information is displayed through module-level LEDs and graphic LC displays on each electronic PQ module:
Diagnostic Reporting via Bus
Diagnostic messages such as wire break and short circuit are evaluated per channel when the respective channel is enabled. If supply voltage drops below the 21.6 V DC low threshold, the system triggers a "No supply voltage L+" diagnostic and turns off the valve coils to avoid undefined mechanical states.
Type 8647 connects to the backplane bus of Siemens SIMATIC ET 200SP and ET 200SP HA interface modules without external communication cabling. The PLC exchanges cyclic I/O data, module parameters, and detailed channel diagnostics over PROFINET IO or PROFIBUS DP.
| Integration Aspect | SIMATIC ET 200SP | SIMATIC ET 200SP HA |
|---|---|---|
| PROFINET Configuration | GSDML file / HSP | GSDML file / HUP |
| PROFIBUS Configuration | GSD file / HSP | Not supported |
| TIA Portal Software | V14 SP1 or higher (via HSP0225) | Not applicable |
| SIMATIC STEP 7 Classic | V5.5 SP4 or higher (via HSP2105) | Not applicable |
| PCS 7 Integration | V9.0 SP2 or higher (via HUP) | V9.0 SP2 or higher (via HUP) |
| Upstream BaseUnit Requirement | Light-colored BaseUnit (BU...D) recommended | Light-colored BaseUnit (BU...D) mandatory |
| Modules to the Right of Valve Block | Supported (requires new light BU) | Not supported (valve block at right end) |
| Maximum Stations per Valve Island | Multiple valve blocks allowed | Exactly 1 valve block per station |
Safety Shutdown with Siemens F-PM-E
Type 8647 REV.2 modules marked "FC" are compatible with the Siemens F-PM-E 24VDC/8A PPM ST fail-safe power module. When de-energized by the F-PM-E module, Type 6524 pilot valves return safely to their rest position. Configure the F-PM-E dark test readback time between 1.5 ms and 2.5 ms, and the switch-on test readback time to 0.8 ms to prevent false trips.
Mount the valve block horizontally or vertically on a standard DIN rail (TH 35-7.5 or TH 35-15) inside an IP54 or higher industrial enclosure. Ensure a minimum clearance of 5 cm between the upper edge of the valve block and the cabinet ceiling (8 cm if external valve shutdown EVS modules are present) to facilitate heat dissipation and screwdriver access.

Push-in connections adhere to ISO 14743:2020. Tubing must be cut straight and pushed firmly beyond the stainless steel holding claws. Minimum retention forces are 120 N for polyamide (PA) tubing and 100 N for polyurethane (PU) tubing.

SKU 20120869 includes integrated P-shutoff valves beneath each valve position. This pneumatic HotSwap mechanism permits the replacement of individual pilot valves while the island remains under line pressure (up to 10 bar). When removing a valve, air vents briefly until the shutoff mechanism seats automatically, allowing all other 23 stations to continue uninterrupted operation.
Maintenance Safety Instructions
Removing a valve on a base module with P-shutoff depressurizes working ports 2 and 4 for that specific station, which may cause connected actuators to move unexpectedly. Mechanically secure all connected actuators before loosening valve fastening screws.
| Item Description | Part Number | Scope and Notes |
|---|---|---|
| Replacement Valve Type 6524 (2x 3/2-way CF C with manual override) | 300817 | 24 V DC, 2.5-10 bar, standardized FM20 flange interface for REV.2 |
| Replacement Valve Type 6524 (2x 3/2-way CF C without manual override) | 300818 | 24 V DC, 2.5-10 bar, used for safety shut-off channels |
| Blanking Cover Plate | 661092 | Covers unused pneumatic slots on REV.2 base modules |
| Electrical Connection Plug Cover | 653670 | Covers unused valve electrical sockets on PQ modules |
| Replacement Valve Seal Set FM20 | 20016305 | Pack of 12 molded seals for Type 6524 double valves |
| Module Base Seal Set MP16 | 20024339 | Pack of 4 pneumatic base-to-base seals for REV.2 |
| Brass Push-in Connector D6 | 20024340 | Pack of 8 push-in cartridges for 6 mm OD tubing |
| Stainless Steel Push-in Connector D6 | 20024341 | Pack of 8 push-in cartridges in stainless steel 1.4401 |