BURKERT 20122496 (Type 8652) is a 16-slot AirLINE valve island with 16x 2x 3/2-way CF-C valves, Industrial Ethernet RJ45 communication, and an aluminium AirLINE Quick baseplate for control cabinet integration.

BURKERT 20122496 (Type 8652) is an AirLINE pneumatic valve island engineered for process automation environments. Configured with 16 valve slots, each slot is equipped with a Type 6534 dual 3/2-way normally closed solenoid valve (Circuit Function C), providing 32 independently controllable pilot valve functions in an 11 mm slice format. The valve island communicates over Industrial Ethernet protocols (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, and CC-Link IE Field Basic) through dual RJ45 connectors, eliminating proprietary fieldbus dependency. Direct cabinet wall or floor mounting is established via an integrated AirLINE Quick adapter plate fabricated from anodised aluminium, providing IP65 protection within an enclosed cabinet enclosure.
Pneumatic connections are realised through brass push-in fittings, with D10 mm primary supply lines and D6 mm working lines routed directly through the baseplate adapter. The pilot stage operates using internal auxiliary pilot air supplied at 3 to 10 bar, enabling system vacuum to 10 bar operating pressure across media temperatures from -10 °C to +55 °C. Solenoid actuation requires a 24 V DC power feed, utilizing electrical power reduction after switching (0.7 W inrush dropping to 0.175 W holding power) to limit thermal generation within dense control enclosures.
| Feature | Specification |
|---|---|
| Article number | 20122496 |
| Valve island series | Type 8652 AirLINE |
| Number of valve slots | 16 PCE |
| Valve module configuration | 16x 2x 3/2-way CF-C (servo-assisted, normally closed) |
| Width per station | 11 mm |
| Manual override | Latching, spring return |
| Communication module | ME43 fieldbus module |
| Industrial Ethernet protocols | PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic |
| Ethernet physical ports | 2x RJ45 (ports X1 and X2) |
| Primary supply connection (1) | Push-in connector D10 mm, Brass |
| Working ports (2, 4) | Push-in connector D6 mm, Brass |
| Additional supply ports | Push-in D6 mm and D10 mm (left and right feed blocks) |
| Intermediate feed module | Without intermediate feed (0 PCE) |
| Operating pressure range | -1.00 bar to 10.00 bar (vacuum to 10 bar) |
| Auxiliary pilot air pressure | 3.00 bar to 10.00 bar (internal feed) |
| Nominal flow rate QNn (air) | 270 l/min per 3/2-way valve (at +20 °C, 6 bar inlet, 1 bar pressure drop) |
| Valve switching times | Opening: 15 ms, Closing: 15 ms (ISO 12238) |
| Operating voltage | 24 V DC (±10 %, residual ripple 1 Vss) |
| Valve nominal power | 0.7 W nominal, 0.175 W after holding power reduction |
| Valve nominal current | 29 mA nominal, 10 mA after power reduction |
| Display variant | Basic (without LC display) |
| Digital inputs | 0 (electronic DI module not fitted) |
| Check valves in exhaust 3 (R) / 5 (S) | No |
| Pneumatic HotSwap in port 1 (P) | No |
| Ingress protection | IP20 (bare unit), IP65 (cabinet bottom mounting with AirLINE Quick) |
| Permissible medium/ambient temperature | -10 °C to +55 °C |
| Storage temperature | -20 °C to +60 °C |
| Operating fluid | Lubricated or unlubricated dry air, neutral gases (ISO 8573-1:2010 Class 7.4.4) |
Direct floor or wall cabinet penetration is handled by the AirLINE Quick interface. By integrating pneumatic push-in bulkheads into an anodised aluminium adapter plate, working lines (D6 mm) and main supply lines (D10 mm) exit directly out of the control cabinet without intermediate bulkheads or terminal strips.

AirLINE Quick Cabinet Floor Mounting
Installing the AirLINE Quick adapter plate directly into the cabinet floor cutout provides an IP65 perimeter seal and reduces panel footprint. Piping connections remain accessible from the cabinet exterior, which accelerates tubing installation and simplifies field maintenance.
Article 20122496 is factory-populated with 16 identical Type 6534 solenoid valve slices in Circuit Function C. Each 11 mm station contains two independently controlled 3/2-way normally closed valves with integrated manual overrides. Air flow rate QNn reaches 270 l/min per pilot valve, measured with 6 bar inlet pressure and a 1 bar differential.

Replacement valve modules for this configuration correspond to Burkert Article no. 301374 (spare part reference REF 296031), which includes the solenoid slice, mounting screws, and interface seals.
The fieldbus architecture is powered by the integrated ME43 communication gateway supporting multi-protocol Industrial Ethernet. Network cabling connects to two switched RJ45 sockets (X1 and X2), enabling line and ring topologies.

| RJ45 Pin | Signal Assignment |
|---|---|
| 1 | TX+ (Transmit data +) |
| 2 | TX- (Transmit data -) |
| 3 | RX+ (Receive data +) |
| 4 | Not connected (N.C.) |
| 5 | Not connected (N.C.) |
| 6 | RX- (Receive data -) |
| 7 | Not connected (N.C.) |
| 8 | Not connected (N.C.) |
Power supply connections are divided into two isolated circuits:
Independent Coil Supply Circuit
Separating the logic power from the valve actuator supply permits external safety interlocks to interrupt coil power without dropping fieldbus communication or PLC node diagnostic availability.

For a 16-valve configuration without intermediate supply modules, the dimensional envelope is defined below (all values in mm):

| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold without intermediate feed | 99 mm | 198 mm | 10x M5 | — | 15 | — | 4 |
| 16-fold with intermediate feed (ref.) | 112 mm | 224 mm | 10x M5 | 114.3 mm | 7 | 7 | 4 |

During cabinet layout, adequate clearance between the front face of the valve island and the cabinet door/mounting plane must be maintained to facilitate manual override operation and wiring service access.
When ordered with explosion-proof options PU17 or PX68, Type 8652 complies with ATEX and IECEx standards for Zone 2 (Gas) and Zone 22 (Dust):
Hazardous Location Wiring Requirements
In hazardous atmospheres, terminal plugs (including 24 V power, SIA, and bus connections) must never be connected or disconnected while energised. Enclosures must provide an ingress protection rating of at least IP54 for gas (3G/Gc) and IP6X for dust (3D/Dc). External transient overvoltage protection must limit voltage surges to 140% of peak rated voltage.
| Item Description | Article Number |
|---|---|
| Replacement solenoid valve Type 6534 (2x 3/2-way CF-C, 24 V DC, incl. screws) | 301374 |
| 5-pin spring-loaded terminal plug (communication & display power supply) | 920180 |
| 2-pin spring-loaded terminal plug (pneumatic valve AUX power supply) | 920442 |
| Fastening screw set M5 x 10 A2 DIN 6912 (10 pieces for cabinet baseplate mounting) | 308661 |
| Height adapter for 16-fold baseplate without intermediate feed | 60041928 |
| Retaining plate for 16-fold baseplate without intermediate feed (cabinet exterior) | 60005880 |
| Blind plate for 16-fold baseplate without intermediate feed | 60041929 |
| Bürkert Communicator configuration software | Type 8920 |
| USB büS interface set 1 (Type 8923 programming kit with cables & terminating resistor) | 772426 |