BURKERT 20131371 Type 8652 AirLINE Valve Island for Process Automation

Burkert Type 8652 AirLINE valve island optimised for process automation. Features LC display diagnostics, PROFINET S2, AirLINE Quick installation, and ATEX/IECEx Zone 2 approvals.

BURKERT 20131371 Type 8652 AirLINE Valve Island for Process Automation

The Burkert Type 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet. Moreover, key pneumatic functions ensure increased process reliability. For instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks.

General Technical Data

Product propertiesDescription
Body materialPA (polyamide)
Seal materialNBR and PUR
Width per station11 mm
Number of valve slotsMax. 24
Maximum number of valve functionsMax. 48
Pressure rangeVac...10 bar
External supply air3...10 bar
Flow rate QNn value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Operating voltage24 V DC (±10% tolerance)
Nominal power of each valve0.7 W (0.175 W after power reduction)
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Ambient temperature-10 °C...+55 °C
Degree of protectionIP20, IP65 in closed control cabinets

INFO

The maximum flow rate depends on the valve function. Flow is reduced by approx. 3% with the integrated Hot Swap function.

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • This makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet
AirLINE Quick PropertiesDescription
Adapter Plate MaterialStainless steel 1.4301 or Anodised aluminium
Pneumatic connection MaterialStainless steel 1.4401 or Nickel-plated brass
Pneumatic Supply / ExhaustPush-in D 10 mm, 3/8"
Pneumatic working portsPush-in D 6 mm, 1/4"

BURKERT 20131371 Burkert Type 8652 AirLINE Quick Adapter in stainless steel or anodised aluminium

Circuit Functions

Circuit functionDescription
C (CF C)3/2-way solenoid valve, Servo-controlled, Normally closed
D (CF D)2 × 3/2-way solenoid valve, Servo-controlled, Normally open
H (CF H)5/2-way solenoid valve, Servo-controlled, Pressure applied via port (1)
L (CF L)5/3-way solenoid valve, In middle position all ports locked
M (CF M)5/3-way solenoid valve, In middle position ports 2 and 4 ventilated
N (CF N)5/3-way solenoid valve, In middle position ports 2 and 4 exhausted
Z (CF Z)5/2-way solenoid valve, Impulse variant with 2 coils

SIA Variant (for safety-related shut-off)

Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants.

Approvals and Conformities

  • Explosion protection: Optional as a category 3 device suitable for zone 2/22. ATEX: II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc. IECEx: Ex ec IIC Gc / Ex tc IIIC Dc.
  • North America (USA/Canada): Optional UL Listed (UL 61010-1) and UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Division 2).
  • China Compulsory Certification (CCC): Optional for hazardous applications in China.

Dimensions

Variant 4-, 8- and 12-fold

BURKERT 20131371 Burkert Type 8652 dimensions for 4-, 8- and 12-fold variants

VariantABCmn
4-fold66-4 x M531
8-fold351118 x M572
12-fold7715410 x M5113

Variant 16-, 20- and 24-fold

BURKERT 20131371 Burkert Type 8652 dimensions for 16-, 20- and 24-fold variants

VariantABCDmm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116

Product Connections

Power supply for communication and displays (5-pin spring-loaded terminal):

  • Red: 24 V DC
  • White: CAN_H (büS connection)
  • Green: SHIELDING
  • Blue: CAN_L (büS connection)
  • Black: GND

Power supply for pneumatic valves (2-pin spring-loaded terminal):

  • Red: AUX 24 V
  • Black: GND

Product Installation

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 20131371 Burkert Type 8652 installation situation and clearance inside the control cabinet

Example Configuration

The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

BURKERT 20131371 Burkert Type 8652 example configuration network with Industrial Ethernet

Safety Instructions for Hazardous Locations

Danger from voltage and electrostatic charge

  • Before working on the device or system, switch off the power supply. Secure against reactivation.
  • In an existing explosive atmosphere, the connection terminals for 24 V supply, SIA, EVS, and digital inputs may only be plugged in or unplugged when the power is switched off.
  • Take suitable measures to ensure that there is no electrostatic charge in the potentially explosive area. Only clean the device surfaces by wiping them gently with a damp or antistatic cloth.

Special conditions for using the Hot Swap function

The use of the Hot Swap function is prohibited in an existing explosive atmosphere. If it can be proven and ensured by means of suitable test equipment that there is no explosive atmosphere for a certain period of time, it is permissible to remove/insert valves using Hot Swap during this time.