BURKERT Type 8652 AirLINE valve island optimised for process automation. Features LC display diagnostics, up to 24 valve slots, ATEX/IECEx Zone 2 approvals, and Industrial Ethernet.

BURKERT 8652 AirLINE is a valve island especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, and key pneumatic functions ensure increased process reliability.

Key features include:
| Product properties | Specification |
|---|---|
| Body Material | PA (polyamide) |
| Seal Material | NBR and PUR |
| Width per station | 11 mm |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Pressure range | Vac...10 bar |
| External supply air | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Operating voltage | 24 V DC (±10% tolerance) |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Degree of protection | IP20, IP65 in closed control cabinets |
| Ambient temperature | -10 °C...+55 °C |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:
The Type 8652 supports various circuit functions including:

The valve island supports various communication interfaces including PROFIBUS DP, Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic), PROFINET S2, CANopen, and büS.
WARNING
CANopen requires 2 terminating resistors: one at the beginning of the network and one at the end. An indicator of the correct bus scheduling is the resistance between CAN_H and CAN_L when the power is switched off. This should be approx. 60 Ω.
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).