BURKERT 20134275 8652 AirLINE Valve Island for Process Automation

BURKERT Type 8652 AirLINE valve island optimised for process automation. Features LC display diagnostics, up to 24 valve slots, ATEX/IECEx Zone 2 approvals, and Industrial Ethernet.

BURKERT 20134275 8652 AirLINE Valve Island for Process Automation

BURKERT 8652 AirLINE is a valve island especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status. The hardware is optimised for installation at the bottom of the control cabinet, and key pneumatic functions ensure increased process reliability.

BURKERT 20134275 BURKERT 8652 AirLINE valve island overview

Key features include:

  • Safety-related shut-off of valves possible
  • Higher plant availability with PROFINET S2 (system redundancy)
  • Process reliability through pneumatic functions
  • Optimised for installation at the bottom of the control cabinet
  • EX-variants: ATEX / IECEx Zone 2, CCC, cURus HazLoc CL I, II, III Div 2

General Technical Data

Product propertiesSpecification
Body MaterialPA (polyamide)
Seal MaterialNBR and PUR
Width per station11 mm
Number of valve slotsMax. 24
Maximum number of valve functionsMax. 48
Pressure rangeVac...10 bar
External supply air3...10 bar
Flow rate QNn value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Operating voltage24 V DC (±10% tolerance)
Nominal power of each valve0.7 W (0.175 W after power reduction)
Degree of protectionIP20, IP65 in closed control cabinets
Ambient temperature-10 °C...+55 °C

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

BURKERT 20134275 BURKERT 8652 AirLINE Quick Adapter in stainless steel or anodised aluminium

Advantages:

  • Reduced space requirement in the control cabinet
  • Makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

Circuit Functions

The Type 8652 supports various circuit functions including:

  • Circuit function C (CF C): 3/2-way solenoid valve, servo-controlled, normally closed.
  • Circuit function D (CF D): 2 × 3/2-way solenoid valve, servo-controlled, normally open.
  • Circuit function H (CF H): 5/2-way solenoid valve, servo-controlled.
  • Circuit function L (CF L): 5/3-way solenoid valve, in middle position all ports locked.
  • Circuit function M (CF M): 5/3-way solenoid valve, in middle position ports 2 and 4 ventilated.
  • Circuit function N (CF N): 5/3-way solenoid valve, in middle position ports 2 and 4 exhausted.
  • Circuit function Z (CF Z): 5/2-way solenoid valve, impulse variant with 2 coils.

Approvals and Conformities

  • Explosion protection: ATEX (II 3G Ex ec IIC Gc, II 3D Ex tc IIIC Dc), IECEx (Ex ec IIC Gc, Ex tc IIIC Dc).
  • North America: UL Listed for the USA and Canada (UL 61010-1), UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Div 2).
  • Others: China Compulsory Certification (CCC).

Dimensions

BURKERT 20134275 BURKERT 8652 dimensions for 4-, 8- and 12-fold variants

Product Connections

The valve island supports various communication interfaces including PROFIBUS DP, Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic), PROFINET S2, CANopen, and büS.

WARNING

CANopen requires 2 terminating resistors: one at the beginning of the network and one at the end. An indicator of the correct bus scheduling is the resistance between CAN_H and CAN_L when the power is switched off. This should be approx. 60 Ω.

Product Installation

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 20134275 BURKERT 8652 installation situation inside the control cabinet

Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).