BURKERT 20137167 Type 3361 electromotive 2-way globe control valve. Features DN 40 flange connection, 0-25 bar pressure range, 24 V DC supply, and stainless steel body for highly precise, dynamic closed-loop control.

BURKERT 20137167 Type 3361 is an innovative electromotive 2-way globe control valve designed for demanding operating conditions. The electromotive actuator with a ball screw positions the control cone with the highest precision at a high positioning speed of up to 6 mm/s, reacting almost delay-free to process signals. This specific variant features a DN 40 flange connection, a stainless steel body, and operates at 24 V DC with a pressure range of 0 to 25 bar. The closed design and robust surface ensure hygienic requirements for fast and residue-free cleaning, while the IP65/IP67 protection class makes it highly resistant to harsh environmental conditions, impacts, and vibrations.
Unrivalled service life and tightness are guaranteed by the proven self-adjusting packing gland with exchangeable V-seals. The fieldbus-compatible Type 3361 provides many helpful functions for process monitoring, valve diagnostics, and predictive maintenance, offering a decisive advantage in modern process automation.
| Product Properties | Specification |
|---|---|
| Design | Globe control valve |
| Nominal diameter | DN 40 (Variant 20137167) |
| Safety setting (power failure) | With energy storage SAFEPOS energy-pack: open, closed or freely programmable position. Without: blocked in last position |
| Flow direction | Against closing direction (below seat) |
| Controller variant | Positioner or process controller (option) |
| Operating pressure | 0...25 bar(g) |
| Nominal pressure | PN 25 (DIN EN 1333) |
| Kv value (water) | 13.6 m³/h (Variant 20137167) |
| Flow characteristic | Equal percentage, linear (on request) |
| Seat leakage | Class III, IV and VI (DIN EN 60534-4) |
| Travel speed | 6 mm/s (for AG2 actuator force 1300 N) |
| Operating voltage | 24 V DC ± 10 % (maximum residual ripple 10 %) |
| Operating medium | Steam, neutral gases, water, alcohols, oils, fuels, hydraulic fluids, salt solutions, organic solvents |
| Medium temperature | -40 °C...+230 °C |
| Degree of protection | IP65/IP67 (DIN EN 60529), NEMA 4X |
| Component | Material |
|---|---|
| Actuator housing | Powder-coated aluminium |
| Display housing/blind cover | PPS (standard), stainless steel 1.4301 (for ATEX/IECEx) |
| Spindle | Stainless steel 1.4401 (316)/1.4404 (316L) |
| Spindle seal | PTFE V-seals (filled) with spring compensation |
| Valve body | Stainless steel CF3M |
| Seat seal | Stainless steel 1.4571 (optionally hardened), PTFE or PEEK seal washer |
| Control cone | Stainless steel 1.4571 (optionally hardened) |

Dimensions in mm, unless otherwise stated.
| DN | NPS | H1 (Standard variant) | H2 (Fieldbus variant) |
|---|---|---|---|
| 10 | 3/8 | 417 | 489 |
| 15 | 1/2 | 417 | 489 |
| 20 | 3/4 | 423 | 495 |
| 25 | 1 | 446 | 518 |
| 32 | 1 1/4 | 474 | 546 |
| 40 | 1 1/2 | 479 | 551 |
| 50 | 2 | 485 | 557 |

Dimensions in mm, unless otherwise stated.
| DN | ∅ DF | LF | ∅ BF | AF | ∅ D | A x α | ∅ MF |
|---|---|---|---|---|---|---|---|
| 15 | 95 | 130 | 65 | 16 | 14 | 4 × 90° | 18.1 |
| 20 | 105 | 150 | 75 | 18 | 14 | 4 × 90° | 23.7 |
| 25 | 115 | 160 | 85 | 18 | 14 | 4 × 90° | 29.7 |
| 32 | 140 | 180 | 100 | 18 | 18 | 4 × 90° | 38.4 |
| 40 | 150 | 200 | 110 | 18 | 18 | 4 × 90° | 44.3 |
| 50 | 165 | 230 | 125 | 20 | 18 | 4 × 90° | 56.3 |
In addition to the maximum operating pressures, the application range of Bürkert process valves is limited by the nominal pressure in accordance with the relevant standard.

Operating Limits for Seat Seal
The electromotive linear drive consists of a brushless DC motor, a gear, and a spindle system that transfers the force to the closing element. The integrated electronics are controlled either by standard signals or via a fieldbus (digital).

Risk of injury from high pressure
Before working on the system or device, switch off the pressure and vent or drain lines.
Risk of injury due to improper replacement
Spare parts may be replaced only by trained technicians and with the appropriate tools. Do not reach into the openings of the valve body if electrically connected devices are not installed in the pipeline.
Running X.TUNE
Do not run X.TUNE without requirement! The X.TUNE function must be run again only when the actuator has been removed afterwards or the valve body has been changed. Never run the X.TUNE under medium pressure.