BURKERT 20140437 Type 8652 valve island (20-bank). Features Industrial Ethernet, ATEX/IECEx Zone 2 approval, LC display diagnostics, and AirLINE Quick adapter.

BURKERT 20140437 Type 8652 AirLINE valve island has been especially developed for process automation requirements. This specific configuration features a 20-bank setup (20x 3/2-way WWC valves) with Industrial Ethernet protocols (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic). New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.
The hardware is optimised for installation at the bottom of the control cabinet via the included Aluminium AirLINE Quick adapter, though installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that prevent unplanned actuation due to pressure peaks. This model is certified for hazardous locations with ATEX/IECEx Zone 2 approvals (Ex ec IIC Gc, Ex tc IIIC Dc).

| Property | Value |
|---|---|
| Dimensions | Width per station: 11 mm |
| Material | Body: PA (polyamide) Seal: NBR and PUR Supply/Working connection: Brass AirLINE Quick: Aluminium |
| Valve Slots | 20 PCE (Max. 24 for family) |
| Pressure Range | -1 bar to 10 bar (Vac...10 bar) |
| External Supply Air | 3...10 bar (Internal auxiliary pilot air) |
| Flow Rate (Qn value air) | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Operating Voltage | 24 V DC (±10% tolerance) |
| Nominal Power | 0.7 W per valve (0.175 W after power reduction) |
| Nominal Current | 29 mA per valve (10 mA after power reduction) |
| Operating Medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Temperatures | Medium: -10 °C to +55 °C Ambient: -10 °C to +55 °C |
| Degree of Protection | IP20 (IP65 in closed control cabinets) |
| Product Connections | Pressure port: D10 Working port: D6 |
| Communication Interface | Industrial EtherNet (PROFINET IO, EtherNet IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) via RJ45 |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages

The valve island supports various circuit functions using Type 6534 solenoid valves. The standard functions include:
Type 6534 valves are available in an SIA variant equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).


Industrial Ethernet (PROFINET IO, EtherNet/IP, Modbus TCP, EtherCAT, CC-Link IE Field Basic) or PROFINET S2 utilizes Interface X1 and X2 RJ45.
| Pin | Assignment |
|---|---|
| 1 | TX+ |
| 2 | TX- |
| 3 | RX+ |
| 6 | RX- |
| 4, 5, 7, 8 | N.C. |
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

Danger from electrical voltage
Danger of explosion due to electrostatic charge
Special conditions for safe use