Skip to content
PROFINET S2ATEX/IECEx Zone 2Hot SwapAirLINE Quick

BURKERT 20140796 8652 AirLINE Valve Island

BURKERT Type 8652 AirLINE valve island for process automation. Features PROFINET S2, LC display, Hot Swap, and ATEX/IECEx Zone 2 approvals. Up to 24 valve slots.

BURKERT 20140796 8652 AirLINE Valve Island

BURKERT 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.

The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability. For instance, check valves in the exhaust air ducts make sure there is no unplanned actuation due to pressure peaks. The system supports PROFINET S2 (system redundancy) for higher plant availability and allows for safety-related shut-off of valves.

General Technical Data

Product properties
Material
BodyPA (polyamide)
SealNBR and PUR
Width per station11 mm
Manual overrideLatching, spring return (optional: lockable)
Number of valve slotsMax. 24
Maximum number of valve functionsMax. 48
Performance data
Pressure rangeVac...10 bar
External supply air (auxiliary pilot air)3...10 bar
Flow rate QNn value air310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure)
Nominal operating modeContinuous operation (100 % duty cycle)
Electrical data
Operating voltage24 V DC (Voltage tolerance ±10%)
Nominal power of each valve0.7 W (0.175 W after power reduction)
Nominal current of each valve29 mA (10 mA after power reduction)
Medium data
Operating mediumOil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended)
Compressed air qualityISO 8573-1: 2010, Class 7.4.4
Environment and installation
Ambient temperature-10 °C...+55 °C
Degree of protectionIP20, IP65 in closed control cabinets

AirLINE Quick

AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.

Advantages:

  • Reduced space requirement in the control cabinet
  • Makes it possible to use more compact control cabinets
  • Reduced installation effort due to hose connections directly at the bottom of the control cabinet

BURKERT 20140796 BURKERT 8652 AirLINE Quick Adapter in stainless steel or anodised aluminium

Circuit Functions

SymbolDescription
BURKERT 20140796 CF CCircuit function C (CF C)
3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed
BURKERT 20140796 CF C 2xCircuit function C (CF C)
2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally closed
BURKERT 20140796 CF D 2xCircuit function D (CF D)
2 × 3/2-way solenoid valve, Servo-controlled, with manual override, Normally open

Approvals and Conformities

  • Explosion protection: As a category 3 device suitable for zone 2/22. ATEX: II 3G Ex ec IIC Gc / II 3D Ex tc IIIC Dc. IECEx: Ex ec IIC Gc / Ex tc IIIC Dc.
  • North America (USA/Canada): UL Listed (UL 61010-1). Optional UL Recognized for Hazardous Locations (Class I, Zone 2; Class II, Zone 22; Class I, Division 2).
  • China Compulsory Certification (CCC): Products with Ex approval are suitable for import and use for hazardous applications in China.

Dimensions

Variant 4-, 8- and 12-fold

BURKERT 20140796 BURKERT 8652 dimensions for 4-, 8- and 12-fold variants

VariantABCmn
4-fold66-4 x M531
8-fold351118 x M572
12-fold7715410 x M5113

Variant 16-, 20- and 24-fold

BURKERT 20140796 BURKERT 8652 dimensions for 16-, 20- and 24-fold variants

VariantABCDmm'n
16-fold with intermediate supply11222410 x M5114.3774
20-fold with intermediate supply13426810 x M5158.31175
24-fold with intermediate supply15631210 x M5158.311116

Product Installation

Hot Swap Function

To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.

BURKERT 20140796 BURKERT 8652 installation situation inside the control cabinet

Explosion Protection (EX) Safety Instructions

Danger due to voltage and electrostatic charge

  • Before working on the device or system, disconnect the power supply and secure against reactivation.
  • In an existing explosive atmosphere, the connection terminals for 24 V power supply, SIA, EVS, and digital inputs may only be plugged in or unplugged when the power is switched off.
  • The use of the Hot Swap function is prohibited in an existing explosive atmosphere unless it can be proven by suitable test equipment that no explosive atmosphere is present for a certain period.
  • Take suitable measures to ensure that no electrostatic charge can build up in the potentially explosive area. Clean the device surface by gently wiping it with a damp or antistatic cloth only.