Skip to content
DN 10 (3/8")Kvs 2.7 m³/hPN 2524 V DCIP65/IP67EC 1935/2004

BURKERT 20143399 Type 3361 Electromotive 2-Way Globe Control Valve, G 3/8", 24 V DC

Burkert 20143399 Type 3361 is an electromotive 2-way globe control valve with G 3/8" thread, stainless steel body, 24 V DC actuator, 2.7 m³/h Kvs, and 50:1 equal percentage control.

BURKERT 20143399 Type 3361 Electromotive 2-Way Globe Control Valve, G 3/8", 24 V DC

BURKERT 20143399 (Type 3361) is an electromotive 2-way globe control valve engineered for high-precision, dynamic continuous flow control in industrial liquid, gas, and steam processes. Built with an AG2 electromotive linear actuator exerting 1,300 N nominal driving force and a ball screw drive mechanism, the unit achieves a travel speed of 6 mm/s and positions the control cone with a dead band of ±0.1%. Pressure shocks and load variations in the medium do not alter the valve position during operation or at powerless standstill. Configured with a G 3/8" internal thread connection (DN 10), a 10 mm seat diameter, and an equal percentage 50:1 control cone, this valve delivers a nominal flow coefficient Kvs of 2.7 m³/h across an operating pressure range from 0 to 25 bar(g).

Article 20143399 features a stainless steel CF3M globe body, an all-metal stainless steel 1.4571 seat seal conforming to DIN EN 60534-4 leakage Class IV, and a self-adjusting PTFE V-ring packing gland with spring compensation. A robust digital display module with integrated operation keys provides direct on-site setup, diagnostics, and status readout, accompanied by an optical 360° LED ring indicator and a mechanical position display. Electrical signals are handled via M12 circular connectors, supporting analogue setpoint control (0/4 to 20 mA or 0 to 5/10 V), digital switching inputs/outputs, and configuration via the Service-büS interface using Bürkert Communicator software.

Operating Principle and Product Architecture ​

The electromotive linear drive consists of a brushless DC motor, a gear train, and a low-friction ball screw spindle assembly that directly translates motor rotation into axial movement of the control cone. The integrated positioner continuously compares the setpoint signal (CMD) with the actual spindle position (POS) measured by an internal displacement transducer. If a system deviation (Xd1) occurs, the electronics drive the motor via variable CTRL until the setpoint position is matched within ±0.1% accuracy.

BURKERT 20143399 Type 3361 AG2 electromotive globe control valve construction layout

In standard static operation without the optional SAFEPOS energy storage module, the non-reversing mechanical spindle blocks in its last position upon power failure, preventing back-driving caused by fluid differential pressure. Fluid enters against the closing direction (flow below the seat, flow direction indicated by embossed body markings 2 -> 1).

BURKERT 20143399 Type 3361 integrated position controller functional diagram

Technical Specifications ​

Specification ParameterValue / Characteristic
Product Type3361 Electromotive 2-way globe control valve
Article Number20143399
Port ConnectionG 3/8" female thread (DIN ISO 228-1)
Nominal DiameterDN 10 (NPS 3/8")
Seat Diameter (Orifice)10 mm
Flow Coefficient (Kvs)2.7 m³/h (Cv 3.1 gpm)
Theoretical Rangeability50:1
Flow CharacteristicEqual percentage (DIN EN 60534-2-4)
Operating Pressure Range0 to 25 bar(g) (PN 25 / Class 150)
Seat Leakage ClassClass IV according to DIN EN 60534-4
Actuator Size / Nominal ForceAG2 / 1,300 N
Travel Speed6 mm/s
Typical Closing Time3.4 s (3,400 ms)
Position Control Dead Band±0.1%
Supply Voltage24 V DC ±10% (max. residual ripple 10%)
Operating CurrentMax. 3 A at peak load; standby 2 to 5 W
Duty Cycle100% continuous
Medium Temperature Range-10 °C to +185 °C
Permissible Ambient Temperature-25 °C to +65 °C (see derating limits)
Fluid Viscosity LimitUp to 600 mm²/s
Enclosure RatingIP65 / IP67 (DIN EN 60529), NEMA 4X
Protection ClassClass III (DIN EN 61140)
Fail-Safe ActionBlocking of static position (no SAFEPOS pack)
ConformityFood contact EC Regulation 1935/2004

Materials of Construction ​

Wetted valve body parts and non-wetted actuator assemblies utilize high-grade industrial alloys and engineered polymers resistant to harsh industrial atmospheres and cleaning agents evaluated according to Ecolab F&E/P3-E No. 40-1.

BURKERT 20143399 Type 3361 AG2 actuator component materials

ItemActuator ComponentMaterial
1Display housing / blind coverPolyphenylene sulphide (PPS)
2Actuator coverPolyphenylene sulphide (PPS)
3, 6Housing O-rings and sealsEPDM
4Actuator main housingPowder-coated die-cast aluminium
7Actuator basePolyphenylene sulphide (PPS)

BURKERT 20143399 Type 3361 globe control valve body and trim materials

ItemFluidic Body ComponentMaterial
1SpindleStainless steel 1.4401 (316) / 1.4404 (316L)
2Spindle gland sealPTFE V-rings (filled) with spring compensation
3Spindle guideStainless steel 1.4404 (316L)
4Packing gland tubeStainless steel 1.4401 (316)
5Valve body sealGraphite or PTFE
6Seat sealStainless steel 1.4571 (metallic seat)
7Control coneStainless steel 1.4571
8Replaceable valve seatStainless steel 1.4571
9Valve seat O-ringEPDM or PTFE
10Valve bodyCast stainless steel CF3M

Dimensional Data ​

BURKERT 20143399 Type 3361 AG2 electromotive actuator dimensions

Actuator SizeNominal Diameter (DN)Thread Size (NPS)Standard Total Height H1 [mm]Fieldbus Height H2 [mm]
AG2103/8"417489
AG2151/2"417489
AG2203/4"423495
AG2251"446518

Note: Without tight-closing function, the actuator is raised by approximately 2 mm in the closed position.

BURKERT 20143399 Type 3361 threaded port valve body dimensional drawings

DNNPSG Thread Depth E [mm]NPT Depth E [mm]RC Depth E [mm]Body Length LM [mm]Hex Wrench Flat AF [mm]
103/8"12.010.310.16527
151/2"14.013.713.26527
203/4"16.014.014.57534
251"18.016.816.89041

Electrical Connections and Control Interfaces ​

Article 20143399 uses M12 circular connectors for power supply, analogue/digital signal control, and digital service communication.

BURKERT 20143399 Type 3361 AG2 circular plug electrical connections

BURKERT 20143399 Type 3361 analogue control interface wiring architecture

M12 Connector Pin Assignments (AG2 Analogue Version) ​

ConnectorPinFunction / Signal AssignmentElectrical Characteristics
X1 (M12 plug, 8-pin, A-coded)1Digital input +0 to 5 V = log "0", 10 to 30 V = log "1"
2GND (Digital input & digital outputs)Common digital return
3Digital output 2 +PNP, current limited to 100 mA
4Digital output 1 +PNP, current limited to 100 mA
5Analogue output -Galvanically isolated return
6Analogue output +0/4 to 20 mA (load 0 to 800 Ω) or 0 to 5/10 V (max. 10 mA)
7Analogue setpoint input -Galvanically isolated return
8Analogue setpoint input +0/4 to 20 mA (input resistance 70 Ω) or 0 to 5/10 V (22 kΩ)
X3 (M12 plug, 5-pin, A-coded)1CAN Shield / functional shieldScreen connection
2Operating voltage +24 V DC ±10%
3GND / CAN_GNDPower supply ground
4CAN_HbüS / CANopen high communication line
5CAN_LbüS / CANopen low communication line

Service Interface Communication

The Service-büS interface on connector X3 communicates directly with personal computers via the optional USB-büS interface stick (article 772426 or 772551) and the Bürkert Communicator software Type 8920 for parameter configuration, diagnostic logging, and firmware maintenance.

Fluidic Characteristics and Flow Progression ​

The equal-percentage flow characteristic conforms to DIN EN 60534-2-4. For DN 10 with a 10 mm seat diameter, the theoretical rangeability is 50:1. The progression of flow rate values across valve opening stroke is detailed below:

BURKERT 20143399 Type 3361 equal percentage flow characteristic curve

DNNPSSeat Size [mm]Actuator Force [N]Max Operating Pressure [bar]Leakage ClassRangeability10% Stroke20% Stroke30% Stroke40% Stroke50% Stroke60% Stroke70% Stroke80% Stroke90% Stroke100% Kvs [m³/h]
103/8"101,30025IV50:10.110.130.190.300.480.731.01.62.32.7
103/8"81,30025VI50:10.0700.0900.120.180.260.420.610.921.52.0
103/8"61,30025VI50:10.0070.0110.0450.0850.160.260.410.651.11.25
103/8"41,30025IV30:10.0230.0330.0490.0700.0970.140.180.260.350.5
103/8"31,30025IV20:10.0090.0150.0230.0330.0460.0630.0850.110.160.2
103/8"31,30025IV20:10.0050.0090.0130.0190.0260.0340.0440.0600.0770.1

Installation, Operation, and Maintenance Instructions ​

Mounting and Piping Installation ​

  1. Ensure piping is depressurized, drained, and thoroughly flushed prior to installation.
  2. Observe fluid flow direction from port 2 to port 1 (flow below the seat), matching the direction arrow cast into the stainless steel body.
  3. The valve can be installed in any orientation; upright mounting with the actuator positioned vertically upwards is recommended.
  4. When threading the body connection into the line, apply counter-torque directly at the hex wrench flats AF (27 mm for G 3/8"). Never apply tightening torque through the actuator housing.

Body Connection Tightening Torques

When reassembling the valve body to the actuator body connection, adhere strictly to specified torque ratings:

  • DN 10 / DN 15: 45 ± 3 Nm (33 ± 2 lbf ft)
  • DN 20: 50 ± 3 Nm (37 ± 2 lbf ft)
  • DN 25: 60 ± 3 Nm (44 ± 2 lbf ft) Always lubricate external connection threads with Klüberpaste UH1 96-402 and replace the intermediate graphite seal gasket.

Manual Actuation Methods ​

  • Electrical Manual Actuation: Switch the device to MANUAL mode via the display context menu (MANU / AUTO layout), then actuate open or closed using the upper and lower navigation keys.
  • Mechanical Manual Override: When the supply voltage is disconnected, mechanical manual adjustment is performed using a 3 mm Allen key.

Mechanical Override Limits

Operate the mechanical manual override only when the actuator is completely de-energized. Depress the manual override mechanism gently and rotate the 3 mm Allen key counter-clockwise to open or clockwise to close. Never exceed the maximum torque limit of 2 Nm; exceeding 2 Nm will damage the internal manual override gearing.

Position Control Calibration (X.TUNE) ​

After replacing the valve body, spindle packing gland, control cone, or valve seat, an X.TUNE calibration must be conducted to adapt the electronic positioner to the physical mechanical stroke limits.

Avoid Process Disruption

Never execute the X.TUNE function while the system is pressurized with medium. Running X.TUNE under process pressure causes incorrect limit determination and leads to uncontrolled fluid flow.

  • Via Local Pushbuttons: Remove dummy cover or access internal buttons; press and hold OPEN and CLOSE buttons simultaneously for 5 seconds until the LED light ring illuminates orange.
  • Via Display / Bürkert Communicator: Navigate to Position Controller -> MAINTENANCE -> CALIBRATION -> X.TUNE. Select the valve seat seal material ("Steel/Steel") and confirm start. Once completed, the 360° LED ring returns to its normal operational state.

Spare Parts and Ordering Accessories ​

Component / Accessory DescriptionSpecification / ConnectionArticle Number
Replacement Control Cone SetSeat size 10, DN 10/15, Steel/Steel (1.4571)149 912
Replacement Valve Seat SetSeat size 10, DN 10/15, 1.4571 + graphite seal262 149
Packing Gland Seal SetSpindle ø10 mm, DN 10 to DN 20285 685
Stainless Steel Spindle GuideSpindle ø10 mm, DN 15 body246 577
Valve Seat Installation ToolFor seat replacement, DN 10/15652 604
Modified Socket Wrench SW19Spindle ø10 mm, DN 10/15 packing gland683 220
M12 Connection Cable (Power)4-pin, A-coded socket, 5 m length (for X3)918 038
M12 Connection Cable (Signals)8-pin, A-coded socket, 2 m length (for X1)919 061
USB-büS Interface Stick Set 1USB-büS stick, power supply, load resistor, Y-distributor772 426
USB-büS Interface Stick Set 2USB-büS stick, load resistor, Y-distributor, 0.7 m cable772 551
büS Service Adapter CableM12 to Micro-USB büS service interface, 0.3 m774 931
SIM Card ModuleFor parameter cloning and data backup291 773