Burkert Type 8652 AirLINE valve island optimised for process automation. Features LC display diagnostics, safety-related shut-off, and ATEX/IECEx Zone 2 approvals.

The Burkert Type 8652 AirLINE valve island has been especially developed for process automation requirements. New diagnostic functions can be visualised on the LC display, both in clear text as well as symbols. This makes it easy to relate to the shown messages and helps to save time during start-up and maintenance. Furthermore, the diagnostic message is also available at the controller, enabling a fast overview of the plant status.
The hardware is optimised for installation at the bottom of the control cabinet. Installation on a standard rail is also possible. Key pneumatic functions ensure increased process reliability, such as check valves in the exhaust air ducts that make sure there is no unplanned actuation due to pressure peaks.

| Product Properties | Description |
|---|---|
| Body Material | PA (polyamide) |
| Seal Material | NBR and PUR |
| Width per station | 11 mm |
| Manual override | Latching, spring return (optional: lockable) |
| Number of valve slots | Max. 24 |
| Maximum number of valve functions | Max. 48 |
| Pneumatic intermediate supply | Optional for the variants with 16, 20 and 24 valve slots |
| Pressure range | Vac...10 bar |
| External supply air | 3...10 bar |
| Flow rate QNn value air | 310 l/min (measured at +20 °C, 6 bar pressure at valve inlet and 1 bar differential pressure) |
| Operating voltage | 24 V DC (±10% tolerance) |
| Nominal power of each valve | 0.7 W (0.175 W after power reduction) |
| Nominal current of each valve | 29 mA (10 mA after power reduction) |
| Digital input | Max. 48 |
| Operating medium | Oil-free or lubricated compressed dry air, neutral gases (5 μm filter recommended) |
| Degree of protection | IP20, IP65 in closed control cabinets |
| Ambient temperature | -10 °C...+55 °C |
AirLINE Quick considerably reduces the use of components in the control cabinet. With the AirLINE Quick Adapter, the valve terminal is adapted directly to the control cabinet floor or control cabinet wall.
Advantages:

Safety Instructions for Potentially Explosive Areas

| Variant | A | B | C | m | n |
|---|---|---|---|---|---|
| 4-fold | 66 | - | 4 x M5 | 3 | 1 |
| 8-fold | 35 | 111 | 8 x M5 | 7 | 2 |
| 12-fold | 77 | 154 | 10 x M5 | 11 | 3 |

| Variant | A | B | C | D | m | m' | n |
|---|---|---|---|---|---|---|---|
| 16-fold with intermediate supply | 112 | 224 | 10 x M5 | 114.3 | 7 | 7 | 4 |
| 20-fold with intermediate supply | 134 | 268 | 10 x M5 | 158.3 | 11 | 7 | 5 |
| 24-fold with intermediate supply | 156 | 312 | 10 x M5 | 158.3 | 11 | 11 | 6 |
To use the Hot Swap function, always observe a minimum distance to the front edge of the control cabinet when installing the valve island inside the control cabinet.


The digital inputs are supplied (24 V) by the electronic module. Current is limited to maximum 30 mA per digital input. Standard 3-wire sensors and 2-wire sensors with voltages between 10…30 V as well as mechanical limit switches can be used.
Type 6534 valves are equipped with additional connection terminals. A valve circuit can therefore be interrupted by an external switch. Manual override is not required for these valve variants. To use the shut-off function, connect the terminal to a potential-free contact (mechanical switch or relay).
The following illustration shows a network with the example of AirLINE Type 8652 with Industrial Ethernet variant as master valve terminal and various AirLINE Type 8652 with büS variant as slave valve terminals.

Solenoid valve Type 6534
| Circuit function | Nominal diameter | QNn value Air | Pressure range | Voltage | Article no. |
|---|---|---|---|---|---|
| C (CF C) 3/2-way, NC | 4 mm | 270 l/min | Vac...10 bar | 24 V DC | 20102334 |
| D (CF D) 2 × 3/2-way, NO | 4 mm | 310 l/min | Vac...10 bar | 24 V DC | 301375 |
| H (CF H) 5/2-way | 4 mm | 290 l/min | Vac...10 bar | 24 V DC | 301376 |
| L (CF L) 5/3-way, all ports locked | 4 mm | 275 l/min | Vac...10 bar | 24 V DC | 301380 |
Solenoid valve Type 6534 SIA variant (2nd port for shutdown)
| Circuit function | Nominal diameter | QNn value Air | Pressure range | Voltage | Article no. |
|---|---|---|---|---|---|
| C (CF C) 3/2-way, NC | 4 mm | 270 l/min | Vac...10 bar | 24 V DC | 20102335 |
| H (CF H) 5/2-way | 4 mm | 290 l/min | Vac...10 bar | 24 V DC | 338805 |
| L (CF L) 5/3-way, all ports locked | 4 mm | 275 l/min | Vac...10 bar | 24 V DC | 346830 |