BURKERT 326058 (Type 5404) is a servo-assisted 2/2-way solenoid valve without body, circuit function B (normally open), DN 12, 1-32 bar, 24 V DC, with PTFE/FKM seals and IP65 protection.

BURKERT 326058 (Type 5404) is a servo-assisted 2/2-way piston solenoid valve supplied without a fluidic body, configured for circuit function B (normally open, NO) with an orifice of DN 12 mm. Designed as a modular upper assembly comprising the solenoid actuator, armature guide tube, pilot stage, and piston control mechanism, it installs directly onto matching Type 5404 DN 12 fluidic bodies with a 65 mm face-to-face length. The unit operates reliably across a pressure range of 1.0 to 32.0 bar with neutral gases and liquids such as compressed air, water, and hydraulic oil, achieving a water flow coefficient Kv of 2.0 m³/h and a nominal gas flow rate QNn of 2,200 l/min.
The electromagnetic drive utilizes a 24 V DC Class H epoxy resin molded coil with a power consumption of 8 W in hot operating state (9.5 W cold). Internal sealing combines a PTFE valve seat seal and piston guide ring with FKM elastomers for the plunger and body interface O-rings, providing dependable sealing across medium temperatures from -10 °C to +120 °C and ambient temperatures up to +55 °C. When paired with an approved DIN EN 175301-803 Form A cable plug (such as Burkert Type 2518), the assembly achieves IP65 environmental protection.

Type 5404 utilizes pilot control to actuate a main piston seal. In circuit function B (normally open, NO), inlet pressure acts below the seat and through pilot passages. In the unpowered state, the spring-loaded pilot valve remains open, relieving pressure from the chamber above the main piston to the outlet port. The incoming line pressure beneath the piston overcomes the return spring, lifting the piston and opening the valve passage.
When electrical power is applied to the 24 V DC solenoid coil, magnetic force pulls the plunger down to seal the pilot bore. Medium pressure accumulates above the piston through equalization orifices. Because the effective surface area on top of the piston exceeds the area exposed below, the resulting downward force drives the piston firmly against the brass valve seat, closing the valve. Switching requires a sustained differential pressure between the inlet and outlet ports.
Minimum Operating Differential Pressure
Type 5404 is a servo-assisted piston valve that requires a minimum pressure difference of 1.0 bar between inlet and outlet to switch open and shut. Operating below this differential pressure will cause erratic operation or incomplete closure.
| Parameter | Specification | Source Details |
|---|---|---|
| Product Type | Type 5404 servo-assisted 2/2-way piston valve | Manufacturer type designation |
| Article Number | 326058 | Specific manufacturer SKU |
| Circuit Function | Circuit function B (WW B / CF B) | Normally open in unpowered state |
| Orifice Size | DN 12 mm (equivalent to 7/16") | Main valve seat diameter |
| Valve Construction | Without fluidic body | Solenoid actuator and internal mechanism |
| Flow Direction | Above seat | Directional flow according to body casting arrow |
| Port Sizing Baseline | Fits 1/2" connection bodies | Body installation length: 65 mm |
| Flow Rate Kv (Water) | 2.0 m³/h | Water flow measurement at 1 bar differential |
| Nominal Flow QNn (Air) | 2,200 l/min | Air flow rating at reference conditions |
| Operating Pressure Range | 1.0 to 32.0 bar | Applicable to neutral gases and liquids |
| Nominal Voltage | 24 V DC | DC voltage only, tolerance ±10% |
| Coil Power Consumption | Hold DC: 8 W (warm coil) / 9.5 W (cold coil) | Continuous 100% ED rating |
| Thermal Insulation Class | Class H | Epoxy resin encapsulation |
| Medium Temperature | -10 °C to +120 °C | Standard PTFE/FKM material combination |
| Ambient Temperature | -10 °C to +55 °C | Standard operational environment |
| Medium Viscosity Limit | Max. 21 mm²/s (cSt) | Neutral liquids, hydraulic oil, water |
| Switching Time (Opening) | 20 to 400 ms | Dependent on differential pressure and medium |
| Switching Time (Closing) | 100 to 1,500 ms | Dependent on differential pressure and medium |
| Electrical Interface | Form A according to DIN EN 175301-803 | Cable plug ordered separately |
| Ingress Protection | IP65 | Valid when assembled with suitable cable plug |

The internal components of the DN 12 actuator assembly are engineered from corrosion-resistant steels, brass, and fluoropolymer sealing materials:
| Item No. | Component | Material | Standard / Notes |
|---|---|---|---|
| 1 | Fixing Nut | Steel | Thick-film passivated (RoHS compliant) |
| 2 | Solenoid Coil | Epoxy resin | Class H insulation (polyamide optional) |
| 3 | Magnetic Stopper | Stainless steel 1.4105 / 1.4113 | AISI 303 / AISI 434 |
| 4 | Armature Guide Tube | Stainless steel 1.4303 | AISI 305 / AISI 308 |
| 5 | Plunger Core | Stainless steel 1.4105 | AISI 430F |
| 6 | Plunger Return Spring | Stainless steel 1.4310 | AISI 301 |
| 7 | Plunger Seal | FKM | Fluor rubber |
| 8 | Retaining Flange | Steel | Thick-film passivated (RoHS compliant) |
| 9 | Housing Cover | Brass | Upper pressure boundary |
| 10 | Housing O-Ring | FKM | Fluor rubber |
| 11 | Piston Return Spring | Stainless steel 1.4310 | AISI 301 |
| 12 | Piston Guide Ring | PTFE | Polytetrafluoroethylene |
| 13 | Piston Body | Brass | Precision machined piston |
| 14 | Valve Body Interface | Brass | Compatible with Type 5404 DN 12 brass bodies |
| 15 | Piston Seat Seal | PTFE | Polytetrafluoroethylene |

Dimensions below define the DN 12 valve envelope with standard threaded bodies (all linear values in mm). Model 326058 matches the actuator dimensions for DN 12 Circuit Function B (CF B):
| Coil Size | DN | CF A Height A1 | CF A Height B1 | CF B Height A1 | CF B Height B1 | G 1/2 (D1/F1) | NPT 1/2 (D2/F2) | Rc 1/2 (D3/F3) | E | L1 | SW | H | J | K |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 5 | 12.0 | 83.0 | 96.5 | 90.5 | 104.0 | G 1/2 (14 mm) | NPT 1/2 (13.7 mm) | Rc 1/2 (13.2 mm) | 33 | 65 | 27 | 32 | 20.5 | 45 |
| 6 | 12.0 | 83.0 | 96.5 | 90.5 | 104.0 | G 1/2 (14 mm) | NPT 1/2 (13.7 mm) | Rc 1/2 (13.2 mm) | 33 | 65 | 27 | 40 | 23.5 | 51 |
Dimensional Notes
Pressure and Electrical Hazard
Before disassembling or performing maintenance on the valve assembly, depressurize the pipeline completely, drain all residual media, and disconnect the electrical supply to prevent accidental activation.
Connect the valve using an approved DIN EN 175301-803 Form A cable socket (such as Burkert Type 2518 or Type 2509). Fasten the center retention screw to a maximum torque of 1.0 Nm. Verify that the flat profile gasket is correctly positioned between the plug base and coil terminal block to maintain IP65 sealing, and verify that the earth protective conductor is firmly grounded.

When mounting or replacing the solenoid coil assembly on the armature guide tube, observe the specified tightening torques:
| Joint / Fastener | Valve Type & DN | Tightening Torque | Tool / Method |
|---|---|---|---|
| Solenoid Fixing Nut | Type 5404, DN 12 | 4.5 to 5.5 Nm | Open-end wrench (do not use pliers) |
| Housing Cover Screws | Type 5404, DN 12 | 2.1 to 2.3 Nm | Calibrated torque wrench |
| Flange Screws | Type 5404, DN 12 | 2.1 to 2.3 Nm | Calibrated torque wrench |
| Cable Plug Center Screw | DIN EN 175301-803 Form A | Max. 1.0 Nm | Screwdriver |
Solenoid Burnout Hazard
Never energize the solenoid coil while it is detached from the valve core tube. Connecting power to an unmounted coil causes rapid inductive overheating and destructive coil burnout.

When ordering replacement parts for Type 5404 DN 12, specify the valve article number (326058) and the corresponding kit item: