PN16
The BURKERT 8644 AirLINE SP electropneumatic automation system integrates electric and pneumatic building blocks with direct WAGO I/O System 750 connection.

The BURKERT 8644 AirLINE SP electropneumatic automation system represents a universal interface between process and system control. It integrates electric and pneumatic building blocks into an assembly, enabling a modular and flexible structure of fieldbus modules, pilot valves, and I/O modules thanks to simple locking technology on the standard rail.



The system features direct connection to the WAGO I/O System 750, an innovative fieldbus interface, compact design, high flexibility, and high flow rates.
| Product properties | Type 0460, Type 6524, Type 6525 | Type 0461, Type 6526, Type 6527 |
|---|---|---|
| Material | ||
| Body | PA (polyamide), aluminium (Type 0460) | PA (polyamide), aluminium (Type 0461) |
| Seal | FKM, NBR and PUR | NBR |
| Maximum installation width | ||
| Width per station | 11 mm | 16.5 mm |
| Manual override | Standard | Standard |
| Number of valve slots | For single valves: max. 64 For impulse and double valves: max. 32 | Max. 32 When using Type 0461: 24 |
| Maximum number of valve functions | Max. 64 | Max. 32 |
| Pneumatic intermediate supply | Necessary for single valves after 24 valve functions. Necessary after 16 valve functions for double valves | Necessary after 16 valve functions |
| Performance data | ||
| Pressure data | Overpressure to atmospheric pressure | Overpressure to atmospheric pressure |
| Pressure range | Vac...10 bar | Vac...10 bar |
| External supply air | >2.5 bar (Type 0460: not possible) | >2.5 bar (Type 0461: not possible) |
| Flow rate $Q_{\text{Nn}}$ value air | 200...300 l/min | 500...700 l/min |
| Nominal operating mode | Continuous operation (100 % duty cycle) | Continuous operation (100 % duty cycle) |
| Electrical data | ||
| Operating voltage | 24 V DC | 24 V DC |
| Voltage tolerance | +20%/-15% (when using Type 0460: ±10%) | +20%/-15% (when using Type 0461: ±10%) |
| Residual ripple (at DC) | 1 Vss | 1 Vss |
| Nominal power of each valve | For single valves: 0.8 W For impulse and double valves: 2× 0.8 W with power reduction | 2 W, 1 W |
| Nominal current of each valve | 43 mA (28 mA holding current after 120 ms) 41 mA (when using Type 0460) | 85 mA (52 mA holding current after 120 ms) 41 mA (when using Type 0461) |
| Protection class | III according to VDE 106, IEC 60536 | III according to VDE 106, IEC 60536 |
| Medium data | ||
| Operating medium | Oil-free or lubricated compressed dry air (5 μm filter recommended) | Oil-free or lubricated compressed dry air (5 μm filter recommended) |
| Compressed air quality | ISO 8573 - 1: 2010, Class 7.4.4 | ISO 8573 - 1: 2010, Class 7.4.4 |
| Approvals and conformities | ||
| Degree of protection | IP20 IP65 in closed control cabinets | IP20 IP65 in closed control cabinets |
| Product connections | ||
| Working connection | D 4, D 6, D 1/4, D 8, NPT 1/8, G 1/8 | D 8, NPT 3/8, G 1/8 |
| Air supply connection | G 1/4, NPT 1/4, D 10, G 3/8, NPT 3/8 | G 3/8, NPT 3/8 |
| Communication module | WAGO I/O System 750 | WAGO I/O System 750 |
| Communication interface | PROFIBUS DP, INTERBUS, DeviceNet, CANopen, Ethernet. Others on request | PROFIBUS DP, INTERBUS, DeviceNet, CANopen, Ethernet. Others on request |
| Environment and installation | ||
| Installation position | As required, preferably with actuator upright | As required, preferably with actuator upright |
| Storage temperature | -20 °C...+60 °C | -20 °C...+60 °C |
| Ambient temperature | 0 °C...+55 °C (when using Type 0460: 0 °C...+50 °C) | 0 °C...+55 °C (when using Type 0461: 0 °C...+50 °C) |
| Symbol | Description |
|---|---|
![]() | Circuit function C (CF C) 3/2-way solenoid valve Servo-controlled, with manual override Normally closed |
![]() | Circuit function C (CF C) 2 × 3/2-way solenoid valve Servo-controlled, with manual override Normally closed |
![]() | Circuit function D (CF D) 3/2-way solenoid valve Servo-controlled, with manual override Normally open |
![]() | Circuit function H (CF H) 5/2-way solenoid valve Servo-controlled, with manual override Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |
![]() | Circuit function L (CF L) 5/3-way solenoid valve With manual override In middle position all ports locked |
![]() | Circuit function N (CF N) 5/3-way solenoid valve With manual override In middle position ports 2 and 4 exhausted |
![]() | Circuit function Z (CF Z) 5/2-way solenoid valve Impulse variant with 2 coils and manual override Pressure applied via port (1), therefore one of the two ports (2) or (4) is under pressure. |