BURKERT 378776 (Type 2873) is a direct-acting 2/2-way proportional solenoid control valve with NPT 1/4 stainless steel body, 2.0 mm orifice, 12 V DC coil, FKM seals, and oxygen service cleaning.

BURKERT 378776 (Type 2873) is a direct-acting 2/2-way proportional solenoid control valve designed for regulating gaseous media in continuous control loops. Operating under circuit function A (normally closed, flow directed below the seat), this unit combines a wetted stainless steel body, NPT 1/4 female process connections, a 2.0 mm orifice, and FKM seat seals. Engineered for specialized dry gas and oxygen systems, article 378776 is delivered oil-, fat-, and silicon-free according to DIS 1000020797 standards. Its frictionless plunger suspension eliminates stick-slip behavior, yielding a 1:200 control range, repeatability under 0.5% FS, and an operating response time under 20 ms across nominal pressures from -1 to 8 bar.
| Parameter | Value |
|---|---|
| Valve Type | Type 2873 direct-acting proportional solenoid valve |
| Article Number | 378776 |
| Circuit Function | A (2/2-way, normally closed, inlet port 1 P/NC) |
| Actuator Type | Plunger valve with frictionless suspension |
| Orifice Size (DN) | 2.0 mm |
| Flow Direction | Below seat |
| Fluidic Port Connection | 2 ports, NPT 1/4 internal thread |
| Wetted Body Material | Stainless steel |
| Seat & External Seal | FKM (Fluor rubber) |
| Suitable Media | Gaseous media (not suitable for liquid media in this configuration) |
| Nominal Pressure Range | -1.0 bar to 8.0 bar |
| Maximum Differential Pressure | 4.0 bar |
| Flow Coefficient Kv (Water) | 0.100 m³/h |
| Nominal Flow Rate QNn (Gas) | 108 l/min |
| Operating Voltage | 12 V DC (rated min/max 12 V DC) |
| Maximum Power Consumption | 9 W |
| PWM Frequency | 1100 Hz to 1200 Hz (nominal 1200 Hz) |
| Duty Cycle | 100% continuous operation |
| Setting Range | 1:200 |
| Medium Temperature | -10 °C to +60 °C |
| Ambient Temperature | -10 °C to +55 °C |
| Electrical Connection | Plug pattern Form A according to DIN EN 175301-803 |
| Cable Plug Delivery Status | Not included (must be ordered separately) |
| Degree of Protection | IP65 (with properly mounted Type 2518 cable plug) |
| Cleanliness Standard | Free of oil, grease, and silicon per DIS 1000020797 (Oxygen version) |
Type 2873 functions as an actuator in closed control loops. The solenoid core is mounted without mechanical sliding friction, preventing hysteresis spikes and stick-slip resistance when modulating flow.

Positioning behaviour is characterized by the following verified values:
Valve positioning is executed through pulse-width modulation (PWM). The duty cycle of the PWM signal sets the coil current and armature stroke position. The 12 V DC coil operates at a PWM frequency between 1100 Hz and 1200 Hz.

The threaded version of Type 2873 provides female pipe ports in brass or stainless steel. Dimensions for female thread depth are standardized per connection type:
| Port Connection | Thread Specification (A) | Thread Depth B (mm) |
|---|---|---|
| NPT 1/4 (Article 378776) | NPT 1/4 | 10 |
| G 1/4 | G 1/4 | 12 |
| G 1/8 | G 1/8 | 8 |
| NPT 1/8 | NPT 1/8 | 7 |
INFO
Article 378776 features an NPT 1/4 female thread connection with a thread engagement depth of 10 mm and a compact stainless steel valve body.
Flow rate through the valve orifice is calculated using standardized pneumatic formulas for subcritical and supercritical flow regimes:
Subcritical flow regime ($p_2 > \frac{p_1}{2}$): $$K_v = \frac{Q_N}{514} \sqrt{\frac{T_1 \rho_N}{p_2 \Delta p}}$$
Supercritical flow regime ($p_2 < \frac{p_1}{2}$): $$K_v = \frac{Q_N}{257 p_1} \sqrt{T_1 \rho_N}$$
Where:

Sizing Recommendation
To prevent the linear valve characteristic curve from degenerating into a curved system characteristic, design the process such that $\Delta p_{valve} > 25%$ of the total system pressure drop at maximum flow. Discontinuities in the characteristic curve can occur if the differential pressure between inlet and outlet exceeds half the nominal pressure rating.
Article 378776 is manufactured for gaseous service and oxygen applications:
Operating the 12 V DC proportional coil requires an external electronic driver capable of generating the required PWM signal:
| Accessory | Type / Designation | Details & Article Reference |
|---|---|---|
| Cable Plug | Type 2518, Form A | DIN EN 175301-803 connector without internal circuitry (0–250 V AC/DC), Article 314802. Must be ordered separately. |
| Control Electronics | Type 8605 Cable Plug | Converts 4–20 mA or 0–10 V analogue setpoints to PWM. Features coil temperature compensation and ramp profiling. Suitable for 12 V DC coils up to 2000 mA (e.g., Article 316529 / 316526). |
| Universal Controller | Type 8611 eCONTROL | Multi-parameter continuous controller supporting proportional valve loop integration. |