BURKERT 466595 Type 5282 Servo-Assisted 2/2-Way Diaphragm Solenoid Valve

BURKERT Type 5282 (Model 466595) servo-assisted 2/2-way solenoid valve. Features a brass body, NBR seal, G 1 1/4 internal thread, 24V DC operation, and handles pressures from 0.2 to 10 bar.

BURKERT 466595 Type 5282 Servo-Assisted 2/2-Way Diaphragm Solenoid Valve

BURKERT Type 5282 (Model 466595) is a servo-assisted 2/2-way diaphragm solenoid valve designed to control, shut off, and meter neutral media. A minimum differential pressure is required for the valve to function. The standard brass body satisfies European drinking water requirements, and the separating diaphragm makes it suitable for aggressive and contaminated media. The 3/2-way pilot valve can be easily converted from a normally closed (NC) to a normally open (NO) circuit function by rotating it on the armature. The solenoid coils are moulded with a chemically resistant epoxy, and the valve is equipped with a service-friendly manual override for start-up and testing.

General Technical Data

PropertyDescription
DimensionsSee Dimensions section
Seal MaterialNBR, EPDM, FKM (Model 466595 uses NBR)
Threaded BodyBrass according to DIN EN 50930-6 (DN 13 stainless steel CF3M, DN 20...DN 50 stainless steel 1.4581/316CB)
CoilEpoxy
Internal Valve PartsStainless steel, brass
OrificeDN 13...DN 65 (Model 466595 is 32 mm)
Circuit FunctionA (Normally closed) and B (Normally open)
Thermal Insulation ClassEpoxy coil class H
Duty Cycle100% continuous operation
Switching TimeOpening: 0.1...0.8 s, Closing: 1.0...4.0 s
Operating Voltage24 V DC, 24 V 56 Hz, 230 V 56 Hz, 24 V AC/DC, 230 V AC/DC (Model 466595 is 24 V DC)
Voltage Tolerance±10%
Operating Medium (NBR)Neutral gases and liquids (e.g. compressed air, water, hydraulic oil)
Medium Temperature (NBR)0 °C...+ 80 °C
Degree of ProtectionIP65 with cable plug according to DIN EN 175301-803 form A
Installation PositionAs required, preferably with actuator upright
Ambient TemperatureMax. + 55 °C

Circuit Functions

SymbolDescription
BURKERT 466595 Circuit Function ACircuit function A (CF A)
2/2-way solenoid valve
Servo-controlled, with manual override
Normally closed
BURKERT 466595 Circuit Function BCircuit function B (CF B)
2/2-way solenoid valve
Servo-controlled, with manual override
Normally open

Materials

BURKERT 466595 BURKERT 466595 Type 5282 material specifications cross-section

No.ElementMaterial
1CoilEpoxy
2O-ringNBR, EPDM, FKM
3CoverBrass (DN 13 stainless steel 1.4408/316, DN 20...DN 50 stainless steel 1.4581/316CB)
4SpringStainless steel 1.4310/302
5DiaphragmNBR, EPDM, FKM
6Diaphragm holderBrass, stainless steel 1.4401/316
7Valve bodyBrass (DN 13 stainless steel CF3M, DN 20...DN 50 stainless steel 1.4581/316CB)
8Manual overridePA

Dimensions

Standard Threaded Variant

Note

  • Dimensions in mm
  • The dimensions D1 and F1 apply to G thread.
  • The dimensions D2 and F2 apply to NPT thread.
  • The dimensions D3 and F3 apply to Rc thread.

BURKERT 466595 BURKERT 466595 Type 5282 dimensions for threaded variant

DNA1B1G (D1)G (F1)NPT (D2)NPT (F2)Rc (D3)Rc (F3)E1L1SW
13109.0123.0G 1/214NPT 1/213.7Rc 1/213.2406527
20115.0131.0G 3/416NPT 3/414.0Rc 3/414.56010032
25121.5142.0G 118NPT 116.8Rc 116.87011541
32122.0147.0G 1 1/420NPT 1 1/417.3Rc 1 1/419.18512650
40126.0156.0G 1 1/222NPT 1 1/217.3Rc 1 1/219.18512660
50142.5177.5G 224NPT 217.6Rc 223.411516470
65142.5185.0G 2 1/227NPT 2 1/223.6--11518085

Product Installation

Before Installation

Installation can be in any position, preferably with the actuator upright. Prior to installation, check pipelines for dirt and clean if required.

Dirt Filter

To ensure that the solenoid valve functions reliably, a dirt filter (≤ 500 µm) must be installed in front of the valve inlet.

Manual Emergency Actuation

BURKERT 466595 BURKERT 466595 Type 5282 manual emergency actuation

Caution

When the manual emergency actuation is locked, the valve can no longer be actuated electrically.

Changing Valve Function

The delivery condition corresponds to the order key. Turning the pilot valve through 180° changes the circuit function of the valve. The circuit function can only be changed for variants up to 10 bar.

BURKERT 466595 BURKERT 466595 Type 5282 installing the pilot valve to change function

Discharge of medium due to leaking device

If the O-rings are forgotten or incorrectly inserted during installation of the pilot valve, the device will be damaged and medium will be discharged. Before screwing in the pilot valve, correctly insert O-rings into the depressions.

  • Function NC: The pilot valve is installed in such a way that the manual emergency actuation points in the direction opposite to the direction of flow arrow.
  • Function NO: The pilot valve is installed in such a way that the manual emergency actuation points in the same direction as the identification for the flow direction.

Setting the Switching Times

The closing and opening times of the valve can be changed if required with the side throttle screws.

Pressure surges

If closing times are fairly short, liquid media cause higher pressure surges. These may reduce the service life of the diaphragm and destroy other devices and components in the system. Discharge of medium can occur if the throttle screws are unscrewed too far.

Electrical Connection

BURKERT 466595 BURKERT 466595 Type 5282 electrical connection of the cable plug

Risk of injury due to electrical shock

Before reaching into the device / equipment switch off the power supply and secure to prevent reactivation. Always connect the protective conductor and check electrical continuity between coil and body.

  1. Tighten cable plug (observing max. torque 1 Nm).
  2. Check that seal is fitted correctly.
  3. Connect protective conductor and check electrical continuity between coil and body.

Maintenance and Troubleshooting

If malfunctions occur, check whether:

  • the device has been installed according to the instructions,
  • the electrical and fluid connections are correct,
  • the device is not damaged,
  • all screws have been tightened,
  • the voltage and pressure have been switched on,
  • the pipelines are clean.
MalfunctionPossible cause
Valve does not switchShort-circuit or coil interrupted
Medium pressure outside the permitted pressure range
Manual emergency actuation locked
Valve does not closeInternal space of the valve is dirty
Manual emergency actuation locked