TLV JH7.5R-B JH7.5R-X / Cast Steel Free Float Steam Trap

TLV JH7.5R-X and JH7.5R-B cast steel free float steam traps with thermostatic air venting for large-size and high-pressure process equipment. Max operating pressure up to 46 barg.

TLV JH7.5R-B JH7.5R-X / Cast Steel Free Float Steam Trap

TLV JH7.5R-X and JH7.5R-B are reliable and durable cast steel free float steam traps designed for use on large-size process equipment. The JH7.5R-B model is also suitable for high-pressure process equipment, handling pressures up to 46 barg and temperatures up to 425 °C. These traps discharge condensate continuously and automatically at a temperature slightly lower than the saturation temperature.

TLV JH7.5R-B cast steel free float steam trap exterior view

Features

  1. Self-modulating free float provides continuous, smooth, low-velocity condensate discharge as process loads vary.
  2. Constant water seal design ensures a steam-tight seal, even under low-load conditions.
  3. JH7.5R-X: Thermostatic capsule (X-element) with "fail open" feature vents air automatically at close-to-steam temperature.
  4. JH7.5R-B: Thermostatic bimetal air vent valve vents air automatically for rapid startup.
  5. Built-in screen with large surface area ensures extended trouble-free operation.
  6. Easy, inline access to internal parts simplifies cleaning and reduces maintenance costs.

Specifications

ModelJH7.5R-XJH7.5R-B
ConnectionSocket Welded, FlangedSocket Welded, Flanged
SizeDN 40, 50, 80DN 40, 50, 80
Orifice No.2, 5, 10, 14, 22, 322, 5, 10, 14, 22, 32, 40, 46
Maximum Operating Pressure (barg) PMO2, 5, 10, 14, 22, 322, 5, 10, 14, 22, 32, 40, 46
Maximum Differential Pressure (bar) ΔPMX2, 5, 10, 14, 22, 322, 5, 10, 14, 22, 32, 40, 46
Maximum Operating Temperature (°C) TMO240400 / 425*
Type of Air VentX-element (6 °C subcooling)Bimetal (vents air up to approx. 100 °C)

With PN flange.

WARNING

PRESSURE SHELL DESIGN CONDITIONS (NOT OPERATING CONDITIONS): Maximum Allowable Pressure (barg) PMA: 40 (JH7.5R-X), 46 (JH7.5R-B) Maximum Allowable Temperature (°C) TMA: 400 / 425 To avoid abnormal operation, accidents or serious injury, DO NOT use this product outside of the specification range.

Materials and Configuration

TLV JH7.5R-B steam trap internal configuration and cross-section

No.DescriptionMaterialDINASTM/AISI
1BodyCast Steel A216 Gr.WCB1.0619-
2CoverCarbon Steel A1051.0460-
3FloatStainless Steel SUS316L1.4404AISI316L
4Orifice---
5Orifice GasketSoft Iron SUYP1.1121AISI1010
6Orifice PlugCast Stainless Steel A351 Gr.CF81.4312-
7Orifice Plug GasketSoft Iron SUYP1.1121AISI1010
8ScreenStainless Steel SUS4301.4016AISI430
9Screen HolderStainless Steel SUS3041.4301AISI304
10Snap RingStainless Steel SUS3041.4301AISI304
11Cover GasketGraphite/Stainless Steel SUS304-/1.4301-/AISI304
12Cover BoltAlloy Steel SNB161.7711A193 Gr.B16
13Cover NutCarbon Steel S45C1.0503AISI1045
16Socket/Flange (DN 40, 50)Carbon Steel A1051.0460-
16Flange (DN 80)Cast Steel A216 Gr.WCB1.0619-
17Air Vent Unit---
18Air Vent Unit GasketSoft Iron SUYP1.1121AISI1010
19Air Vent GuideStainless Steel SUS3031.4305AISI303
20Drain Plug GasketSoft Iron SUYP1.1121AISI1010
21Drain PlugCarbon Steel S25C1.0460AISI1025

Dimensions

Socket Welded

TLV JH7.5R-B socket welded dimensions diagram

DNL (mm)H (mm)H1 (mm)φW (mm)φD (mm)φC (mm)h (mm)Weight (kg)
404663892913056448.81351
5046638929130577.561.21656
8050638929130511289.8-65

Flanged

TLV JH7.5R-B flanged dimensions diagram

DNL (DIN PN25/40)L (ASME 150RF)L (ASME 300RF)L (ASME 600RF)H (mm)H1 (mm)φW (mm)Weight (kg)*
4047247147849438929130560
5047647548150038929130562
8050450451453338929130568

Weight is for DIN PN 25/40.

Discharge Capacity

  1. Line numbers within the graph are orifice numbers.
  2. Differential pressure is the difference between the inlet and outlet pressure of the trap.
  3. Recommended safety factor: at least 1.5.

DANGER

Do not use traps under conditions that exceed maximum differential pressure, as condensate backup will occur!

JH7.5R-X

TLV JH7.5R-B TLV JH7.5R-X discharge capacity chart

JH7.5R-B

TLV JH7.5R-B discharge capacity chart

Installation & Piping Arrangement

TLV JH7.5R-B allowable installation inclination

  1. Before installation, be sure to remove all protective seals.
  2. Before installing the trap, blow out the inlet piping to remove all dirt and oil.
  3. Install the steam trap within the allowable inclination (horizontal and vertical tolerance). Make sure that the arrow mark on the body corresponds with the direction of flow.
  4. Install the trap in the lowest part of the pipeline or equipment so the condensate flows naturally into the trap by gravity. The inlet pipe should be as short and have as few bends as possible.
  5. Support the pipes properly within 800 mm (2.5 ft) on either side of the trap.
  6. Install a bypass valve to discharge condensate, and inlet and outlet valves to isolate the trap in the event of trap failure or when performing maintenance.
  7. Install a check valve at the trap outlet whenever more than one trap is connected to the condensate collection pipeline.

Inspection and Maintenance

Operational inspections should be performed at least twice per year, or as called for by trap operating conditions. Steam trap failure may result in temperature drop in the equipment, poor product quality or losses due to steam leakage.

DANGER

NEVER apply direct heat to the float. The float may explode due to increased internal pressure, causing accidents leading to serious injury or property and equipment damage.

Tightening Torques (JH7.5R-B)

PartTorque (N·m)Distance Across Flats (mm)
Cover Nut20030
Orifice60046
Orifice Plug80046
Drain Plug10026
Air Vent Valve Seat3019
Air Vent Guide15030

Troubleshooting

ProblemCauseRemedy
No condensate is discharged (blocked) or discharge is poorFloat is damaged or filled with condensateReplace the float
Orifice, screen or piping are clogged with rust or scaleClean
The bimetal is damagedReplace with new bimetal
The trap operating pressure exceeds the maximum specified pressure, or there is insufficient pressure differentialCompare specifications and actual operating conditions
Steam locking has occurredBlowdown through the bypass or close the trap inlet valve and allow the trap to cool
Steam is discharged or leaks from the trap outlet (blowing) (steam leakage)Rust and scale have accumulated around the valve seat or under the floatClean
Orifice is damagedReplace with new orifice
Float is deformed or coated with scaleClean or replace the float
Trap is installed above the maximum allowable inclination angleCorrect the installation
Vibration of trap occursLengthen inlet piping, then fasten it securely
The bimetal air vent valve surface and/or the air vent valve seat has a build-up or is scratchedClean or replace with new bimetal and/or air vent valve seat
Steam leaks from a place other than the trap outletDeterioration of or damage to gasketsReplace the gaskets
Leakage from eroded cavities of body or coverReplace the trap
Improper tightening torque for cover was usedTighten to the proper torque
Float is frequently damagedWater hammer occursExamine the piping for problems that can cause water hammer