Yoshitake GD-24 Water Pressure Reducing Valve

Yoshitake GD-24 direct acting water pressure reducing valve with stainless steel seat. Suitable for cold and hot water systems. 0.2-1.6 MPa inlet pressure.

Yoshitake GD-24 Water Pressure Reducing Valve

Yoshitake GD-24 water pressure reducing valve can be used as a pressure control unit in water supply systems of general residential housing, high-rise buildings, industrial plant, and factory equipment. It can also be used to provide stable water pressure in high-rise apartment units, and for hilly districts where each house requires an individual water supply system. Trouble-free flow control solutions are achieved through the use of a stainless steel valve seat and a suspension type clamp in the drive mechanism.

Features

  • Wetted parts are made of corrosion-resistant material to prevent rusty water.
  • Highly wear-resistant and durable stainless steel valve seat.
  • Closed structure keeps fluid inside even if the diaphragm is damaged or broken.
  • Horizontal or vertical piping is possible.
  • If a large capacity is required, valves can be installed in parallel.

Options

  • GD-24G: D-type 1.0MPa pressure gauge
  • GD-24S: Strainer (SY-24, 60 mesh as a standard)
  • GD-24GS: Gauge and strainer

Pressure gauge connection port is JIS Rc 1/8.

Specifications

ModelGD-24
ApplicationCold and hot water, Flushing water
Inlet pressure0.2-1.6 MPa
Reduced pressure0.05-0.55 MPa
Minimum differential pressure0.05 MPa
Maximum pressure reduction ratio10:1
Application temperature5-80°C*
ConnectionJIS Rc screwed

** Do not use the valve continuously at a temperature of 70°C or above (catalog notes).*

Material

PartMaterial
BodyCast bronze / Bronze
Valve discUrethane rubber
Valve seatStainless steel
DiaphragmEPDM / NBR
CapBronze / Brass
PlugStainless steel

Dimensions and Weights

Yoshitake GD-24 dimensions drawing

Nominal sizedLHH1Weight (kg)
15ARc 1/28019341.51.8
20ARc 3/490210452.4
25ARc 1100230503.3
32A (31A)Rc 1-1/4120265604.7
40ARc 1-1/2150315628.2
50ARc 21853657314.3

(Dimensions in mm)

Construction

Yoshitake GD-24 construction cross-section drawing

No.Name of partsNo.Name of parts
1Body12Washer
2Spring Chamber13Nut
3Cap14Adjusting Spring
4Valve (Disc)15O-ring
5Valve Seat16Bolt
6Suspension Metal17Sealed Nut
7Diaphragm Shell18Spring
8Diaphragm19Plug
9Spring Plate20Label
10Adjusting Screw21Spring Washer
11Lock Nut

Operation

Turning the adjusting screw (10) to compress the adjusting spring (14) and the load of adjusting spring is introduced to the diaphragm (8) and suspension metal (6) to open the valve (4). Then, the fluids begin to flow from the inlet side through the upper side of the valve. The reduced pressure is led to the diaphragm to be balanced with the adjusting spring load, and control the valve travel to maintain the reduced pressure.

Nominal Size Selection

Yoshitake GD-24 nominal size selection chartΔP: Inlet/reduced pressure differential (MPa)

Cv Value:

Nominal size15A20A25A32A40A50A
Cv value1.51.93.04.07.010.0

Characteristics Charts

Flow Rate Characteristics ChartYoshitake GD-24 flow rate characteristics chart

Pressure Characteristics ChartYoshitake GD-24 pressure characteristics chartThis chart shows variation in reduced pressure when the inlet pressure of 0.6 MPa is changed between 0.2 MPa and 1.6 MPa while the reduced pressure is set at 0.2 MPa.

Installation

Piping ExampleYoshitake GD-24 piping example

Installation Warnings & Cautions

  • Relief Valve: In case installing a safety relief valve as a safety device at the outlet side, joint relief pipe at the outlet of the safety relief valve and guide it to a safe place.
  • Strainer: Install a strainer (Screen: 60 mesh) at the valve inlet side.
  • Flushing: Remove foreign matter and scales from the lines before installing the valve.
  • Gauges: Install a pressure gauge at both the inlet and outlet sides of the valve.
  • Distance: When installing quick open and close valves (such as a solenoid valve), secure at least 3 m from the valve. When pressure reducing in two stages, secure at least 3 m between the valves.
  • Direction: Install the valve in proper direction of the fluid flow.

Maintenance Space Secure the necessary maintenance space at the installation site of the pressure reducing valve. Yoshitake GD-24 maintenance space requirements

Nominal sizeAB
15A245105
20A270115
25A290130
32A340145
40A420150
50A480165

Operating and Adjustment Procedure

Operating Cautions

  • Do not touch the pressure reducing valve directly with bare hands after flowing hot fluids to prevent burns.
  • When opening the by-pass stop valve, ensure that the reduced pressure will not exceed the set pressure of the safety relief valve.
  • When operation is discontinued for a long period of time, completely purge fluid from the pressure reducing valve and piping system.

GD-24 pressure reducing valve is set at 0.1MPa at the factory. Change the set pressure as appropriate:

  1. Close the stop valves at both sides of the pressure reducing valve, and thoroughly purge the system through the by-pass line. When completed, be sure to close the by-pass valve.
  2. Slowly open the inlet stop valve, then open the outlet stop valve slightly, allowing a trickle to be discharged.
  3. Loosen the lock nut, and slowly turn the adjusting screw (clockwise to increase, counterclockwise to reduce) while observing the outlet side pressure gauge.
  4. Slowly open the outlet stop valve to its full-open position.
  5. After the adjustment, tighten the lock nut.

Maintenance and Troubleshooting

Maintenance Precautions

Completely discharge internal pressure from the valves, lines, and equipment, and cool the valve down to a level where you can touch it with bare hands before disassembly and inspection.

Consumable parts and replacement period:

  • Diaphragm (8): 3 years
  • O-ring (15): 3 years

Troubleshooting:

ProblemCauseCountermeasure
Reduced pressure exceeds prescribed level1. Diaphragm is damaged.
2. Foreign matter is embedded in the valve and/or valve seat, or scratches exist.
1. Replace the diaphragm.
2. Disassemble and remove foreign matter. If scratches exist, replace it.
Pressure does not rise to the desired level1. Strainer is clogged.
2. Pressure gauge malfunction.
1. Disassemble and clean.
2. Replace the pressure gauge.
Leakage1. Loosen Bolt (16).
2. Loosen Cap (3).
3. Broken O-ring (15) for cap.
1. Tighten Bolt (16).
2. Tighten Cap (3).
3. Replace O-ring (15) for cap.
Abnormal noise is heardThe suspension metal (6) is in incorrect position.Correct the position of the suspension metal (6).

Exploded DrawingYoshitake GD-24 exploded drawing