Yoshitake GD-29S direct-acting pressure reducing valve for cold and hot water. Features cast stainless steel body, EPDM disc, and JIS 16K FF flanged connection up to 1.6 MPa.

Yoshitake GD-29S is a direct-acting pressure reducing valve designed for cold and hot water applications. Featuring a cast stainless steel body and EPDM diaphragm and valve disc, it provides excellent corrosion resistance and durability. The GD-29S supports inlet pressures up to 1.6 MPa and offers a maximum pressure reduction ratio of 10:1, making it highly reliable for stable pressure control.
INFO
The GD-29S is connected via JIS 16K FF flanged ends. A built-in strainer (40 mesh) is incorporated in sizes 20A to 50A, while sizes 65A to 100A do not include a strainer.
| Specification | Value |
|---|---|
| Application | Cold and hot water |
| Inlet pressure | 1.6 MPa or less |
| Reduced pressure | (A) 0.05-0.35 MPa (B) 0.3-0.7 MPa |
| Minimum differential pressure | 0.05 MPa |
| Maximum pressure reduction ratio | 10:1 |
| Application temperature | 5-90℃ |
| Body material | Cast stainless steel |
| Valve seat material | Cast stainless steel |
| Valve disc material | EPDM |
| Diaphragm material | EPDM |
| Connection | JIS 16K FF flanged |

| Nominal size | L (mm) | H (mm) | H1 (mm) | Weight (kg) |
|---|---|---|---|---|
| 20A | 160 | 170 | 41 | 3.9 |
| 25A | 160 | 170 | 41 | 4.8 |
| 32A | 200 | 224 | 57 | 8.0 |
| 40A | 200 | 224 | 57 | 8.3 |
| 50A | 220 | 239.5 | 61 | 10.8 |
| 65A | 220 | 329 | 77 | 20.6 |
| 80A | 234 | 345 | 82 | 25.0 |
| 100A | 278 | 412 | 94 | 36.5 |
(The differential pressure before and after the valve is 0.15 MPa or more.)
| Nominal size | 20A | 25A | 32A | 40A | 50A | 65A | 80A | 100A |
|---|---|---|---|---|---|---|---|---|
| Rated flow (L/min) | 40 | 60 | 100 | 150 | 250 | 300 | 450 | 700 |
If the differential pressure before and after the valve is less than 0.15 MPa, select a proper nominal size from the charts below.
Nominal size: 20A to 50A
Nominal size: 65A to 100A
Pressure Characteristic Chart
This chart shows variation in reduced pressure when the inlet pressure of 0.6 MPa is changed between 0.15 MPa and 1.0 MPa while the reduced pressure is set at 0.1 MPa.
Flow Characteristic Chart
Offset Pressure
| Nominal size | Pressure range | Reduced pressure range | Offset pressure |
|---|---|---|---|
| 20A-100A | A | 0.05-0.35 MPa | Within 0.05 MPa |
| 20A-100A | B | 0.30-0.70 MPa | Within 0.10 MPa |